Mission-critical bypass-isolation ATS for hospitals, data centers, and defense. Up to 4000A, 200kA withstand rating, maintenance without power interruption.
The Russelectric RTS-03 is a bypass-isolation automatic transfer switch designed for mission-critical facilities where maintenance cannot interrupt power. It's the premium ATS choice for hospitals, Tier III/IV data centers, airports, military installations, and any facility where the cost of a 15-minute power interruption exceeds the cost of the switch itself.
Now a Siemens business, Russelectric has manufactured transfer switches in Hingham, Massachusetts since 1955. Every unit is custom-engineered to the specific application — there is no "standard catalog" configuration.
Russelectric switches are the most complex ATS in our service portfolio. Maintenance includes exercising the bypass mechanism, verifying interlock integrity, testing controls in both automatic and bypass modes, and inspecting contacts. The positive mechanical interlocks (which prevent unsafe configurations) require careful inspection — they protect against human error during bypass operations. These switches are over-engineered by design, and field failures are rare when properly maintained.
Frequently Asked Questions
What does bypass-isolation mean?
Bypass-isolation allows you to manually transfer the load to either source (utility or generator) while completely isolating the automatic transfer mechanism for maintenance — without any interruption to the load. This means the ATS can be serviced, replaced, or tested while the building remains powered. It's mandatory for hospitals and Tier III+ data centers.
Why is Russelectric more expensive than ASCO?
Russelectric is custom-engineered per application with the highest withstand ratings in the industry (200kA at 480V with fuses). Every unit is essentially a one-off build. The premium buys you: maintenance without downtime (bypass-isolation), highest available fault current protection, and the most conservative engineering margins. For facilities where a 15-minute power interruption costs millions, the premium is trivial.
What is the 200kA withstand rating?
The Russelectric RTS-03 can close into and withstand 200kA of fault current at 480V when equipped with current-limiting fuses — the highest rating in the ATS industry. This means it can safely operate in locations with very high available fault current without requiring additional upstream current-limiting devices.
Who owns Russelectric now?
Russelectric is now a Siemens business (acquired 2019). Product quality and custom-engineering approach remain unchanged. Parts and service continue through the same channels.
Found in these gensets
Generator models that ship with or are commonly paired with the Russelectric RTS-03 Bypass-Isolation ATS.
Blue Star Power Systems
Blue Star MD1000-01
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for industrial, data center, and campus power where value engineering and non-proprietary component independence matter.
1000 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S12H-Y2PTAW-1 37.1L V12 engine, S6L1D alternator, DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD1250-01
1.3 MW standby · Diesel · Liquid-cooled
1250 kW diesel standby for industrial, data center, and utility-scale applications where value engineering and open-architecture components matter.
1250 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S12R-Y2PTAW-1 49.0L V12 engine, S6L1D alternator, DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD1600-01
1.6 MW standby · Diesel · Liquid-cooled
1600 kW diesel standby for industrial, data center, and utility-scale applications where value engineering and non-proprietary components matter.
1600 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S16R-Y2PTAW-1 65.4L V16 engine, S7L1D alternator, DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD2000-01
2 MW standby · Diesel · Liquid-cooled
2000 kW diesel standby for data centers, hospitals, and utility-scale applications where component independence and value engineering matter.
2000 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S16R-Y2PTAW2-1 65.4L V16 engine, S7L1D alternator, DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star MD800-01
800 kW standby · Diesel · Liquid-cooled
800 kW diesel standby for industrial plants, campus power, and data centers where value engineering and non-proprietary component access matter.
800 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Mitsubishi S12A2-Y2PTAW-2 33.9L V12 engine, S6L1D alternator, DCP7310 controller. Three-phase, 208–4160V.
Tier 23-phaseindustrialmunicipal
Blue Star Power Systems
Blue Star NG1050-01
1.1 MW standby · Natural Gas / LPG · Liquid-cooled
1050 kW natural gas standby for data centers, campus power, and utility-scale gas applications where component independence matters.
1050 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 53L V16 turbocharged-aftercooled, DCP7310 controller, three-phase 480-4160V.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star NG1050-01P
Standby: see spec sheet · Natural Gas / LPG · Liquid-cooled
900 kW prime natural gas for continuous-duty data center, CHP, and utility-scale applications needing 24/7 gas-fueled power.
900 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 53L V16 turbocharged-aftercooled, DCP7310 controller, three-phase 480-4160V.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star NG1250-01
1.3 MW standby · Natural Gas · Liquid-cooled
1250 kW natural-gas-only standby for data centers and utility-scale facilities where gas-fueled backup and component independence matter.
1250 kW natural-gas-only standby generator from Blue Star Power Systems. PSI 53LHO high-output V16 turbocharged-aftercooled, DCP7310 controller, three-phase 480-4160V. LP not available.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star NG800-01
800 kW standby · Natural Gas / LPG · Liquid-cooled
800 kW natural gas standby for data center, campus, and industrial facilities where gas-fueled backup and component independence matter.
800 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 40L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-4160V.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star NG800-01P
Standby: see spec sheet · Natural Gas / LPG · Liquid-cooled
660 kW prime natural gas for continuous-duty data center, CHP, and campus applications needing 24/7 gas-fueled power at scale.
660 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 40L V12 turbocharged-aftercooled, DCP7310 controller, three-phase 208-4160V.
3-phaselarge-commercialdata-center
Blue Star Power Systems
Blue Star VD600-01
Standby: see spec sheet · Diesel · Liquid-cooled
Blue Star Power Systems VD600-01 diesel generator set.
3-phaselarge-commercialhospital
Caterpillar
Cat 3412C
800 kW Cat diesel with 3412C V-12. Updated 3400-series with EMCP 4 controls. Proven reliability.
800 kW standby · Diesel · Liquid-cooled
800 kW standby for data centers, hospitals, and campuses with existing 3400-series fleet.
800 kW standby diesel generator with Cat 3412C V12 engine, 27.0L displacement. The current-generation 3412 with upgraded controls and improved fuel efficiency.
Tier 23-phasedata-centerhospital
Caterpillar
Cat 3508
850 kW Cat diesel with 3508 V-8. 34.5L between the 3412 and 3512. Proven 3500-series reliability.
850 kW standby · Diesel · Liquid-cooled
850 kW standby for industrial facilities, campuses, and mining operations with 3500-series standardization.
850 kW standby diesel generator with Cat 3508 V8 engine, 34.5L displacement. Purpose-built for industrial facilities, mining operations, and mission-critical power.
Tier 23-phaseindustrialcampus
Caterpillar
Cat 3508B
1 MW Cat diesel with 3508B V-8. Upgraded 3500-series for data centers. Megawatt from 8 cylinders.
1 MW standby · Diesel · Liquid-cooled
1 MW standby for data centers, hospitals, and mission-critical facilities preferring 3500-series platform.
1000 kW standby diesel generator with Cat 3508B V8 engine, 34.5L displacement. Built for data centers, hospitals, and paralleling arrays requiring 1 MW per unit.
Tier 23-phasedata-centerhospital
Caterpillar
Cat 3512
Diesel generator set with the Cat 3512 V-12 engine, rated 1000 to 1400 kVA at 50 Hz.
1 MW standby · Diesel · Liquid-cooled
Diesel power for data centers, large hospitals, and industrial campuses with CAT fleet.
1000-1400 kVA (50 Hz) diesel generator with Cat 3512 V-12 engine. 51.8L displacement, Woodward governor, continuous/prime/standby duty cycles.
3-phasecommercial-standbyindustrial
Caterpillar
Cat 3512B
Diesel generator set with the Cat 3512B V-12 engine, rated up to 1500 ekW mission critical standby at 60 Hz.
1.5 MW standby · Diesel · Liquid-cooled
1500 ekW mission critical standby for data centers, large hospitals, and critical infrastructure.
1230-1500 kW diesel generator with Cat 3512B V-12 engine. EUI fuel system, EMCP 4.2B controller, mission-critical and standby ratings.
3-phasecommercial-standbymission-critical
Caterpillar
Cat 3516
Diesel with CAT 3516 V-16 engine and EMCP 4.2 controller.
Standby: see spec sheet · Diesel · Liquid-cooled
Diesel standby for large data centers, hospitals, and industrial campuses with CAT fleet standardization.
Diesel generator with Cat 3516 turbocharged V-16 engine. Mission-critical platform for data centers, hospitals, and large industrial standby and prime power.
3-phasedata-centerhospital
Caterpillar
Cat 3516B
2000 kW standby diesel with CAT 3516B V-16 engine and EMCP 4.2B controller.
2 MW standby · Diesel · Liquid-cooled
2000 kW diesel standby for data centers, large hospitals, and campus-scale critical infrastructure.
2500 kW diesel with CAT 3516C V-16. EPA Tier 4 Final. Paralleling for multi-MW arrays.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW diesel standby for hyperscale data centers, campus microgrids, and emission-regulated industrial.
2500 kW diesel standby generator with Cat 3516C V-16 engine. The largest Cat genset platform for mission-critical data centers and industrial power.
Tier 23-phasedata-centerhospital-large
Caterpillar
Cat 3516E
Diesel with CAT 3516E V-16 engine and EMCP 4.2B controller.
Standby: see spec sheet · Diesel · Liquid-cooled
Diesel standby for data centers, campus microgrids, and utility peak shaving.
Diesel generator with Cat 3516E V-16 engine. 78.1L displacement, Tier 2 equivalent, ATAAC aspiration for standby power.
Tier 23-phasecommercial-standbymission-critical
Caterpillar
Cat C175-16
Up to 3100 kW diesel with CAT C175-16 V-16. Voltages from 220 to 13,800 volts.
3 MW standby · Diesel · Liquid-cooled
Diesel generator rated up to 3100 kW for data centers, campus microgrids, and mission-critical infrastructure.
2500-3100 kW diesel generator with Cat C175-16 SCAC V-16 engine. 84.7L displacement, Tier 2, mission-critical and standby power for data centers and large industrial facilities.
Tier 23-phasecommercial-standbymission-critical
Caterpillar
Cat C175-20
Diesel with CAT C175-20 V-20 engine and EMCP 4.2 controller. Medium-voltage capable.
Standby: see spec sheet · Diesel · Liquid-cooled
Diesel standby for data centers, utility-scale backup, and campus microgrids.
Diesel generator with Cat C175-20 SCAC V-20 engine. 105.8L displacement, standby, mission-critical, prime, and continuous duty cycles for large industrial and utility applications.
3-phasecommercial-standbymission-critical
Caterpillar
Cat C27
800 kW diesel with CAT C27 V-12.
800 kW standby · Diesel · Liquid-cooled
800 kW diesel generator for mission-critical data centers, large hospitals, and industrial campuses.
680-800 kW diesel generator set with Cat C27 ACERT V-12 engine. Tier 2, MEUI fuel system, EMCP 4 controller.
Tier 23-phasecommercial-standbyindustrial
Caterpillar
Cat C32
1000 kW diesel with CAT C32 V-12. ~200 US dealers. Paralleling for multi-MW.
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for Tier III data centers, large hospitals, and industrial campuses with CAT fleet.
1000 kW diesel standby generator with Cat C32 ACERT V-12 engine. Mission-critical platform for data centers, hospitals, and large campus power.
Tier 23-phasedata-centerhospital
Caterpillar
Cat C32B
1500 kW diesel with CAT C32B. EPA Tier 2.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier III+ data centers, hospitals, and mission-critical campus infrastructure.
1500 kW diesel standby generator with Cat C32B engine. Tier 2, EUI fuel system, Cat ECS/GCCP controller. The D1500 platform.
Tier 23-phasedata-centermission-critical
Caterpillar
Cat D1500
1.5 MW Cat diesel with C32B V-12. Cat's newest flagship. Maximum power density for data centers.
1.5 MW standby · Diesel · Liquid-cooled
1.5 MW standby for Tier III+ data centers and large hospitals needing maximum single-unit density.
1500 kW standby diesel generator with Cat C32B V12 engine, 32.1L displacement. Cat's newest 1.5 MW platform — maximum power density for space-constrained data centers.
Tier 23-phasedata-centerhospital
Caterpillar
Cat G3516H
1982 kW natural gas with CAT G3516H. 43.5% electrical efficiency. Cogeneration-ready.
2.0 MW standby · Natural Gas · Liquid-cooled
1982 kW natural gas continuous/CHP for industrial cogeneration, distributed generation, and utility power.
1982 kW continuous natural gas generator with Cat G3516H engine. High-efficiency combined heat and power for industrial, utility, and distributed generation.
3-phasecogenerationdistributed-generation
Caterpillar
Cat G3516H
Natural gas with CAT G3516H. Medium-voltage capable. Cogeneration-ready.
2.0 MW standby · Natural Gas · Liquid-cooled
Natural gas continuous/cogeneration for industrial CHP, distributed generation, and campus power.
Continuous-duty natural gas generator with Cat G3516H engine. Low-emission gas power for cogeneration, distributed generation, and industrial applications.
3-phasecontinuous-dutycogeneration
Caterpillar
Cat G3520E
2022 kW natural gas with CAT G3520E. 41.5% electrical efficiency. Cogeneration-ready.
2.0 MW standby · Natural Gas · Liquid-cooled
2022 kW natural gas continuous/CHP for industrial cogeneration, distributed generation, and baseload power.
2022 kW continuous natural gas generator with Cat G3520E engine. High-efficiency CHP platform for industrial, utility, and distributed generation.
3-phasecogenerationdistributed-generation
Caterpillar
Cat G3520H
2500 kW natural gas with CAT G3520H. Medium-voltage capable. Hydrogen capability on certain configurations.
2.5 MW standby · Natural Gas · Liquid-cooled
2500 kW natural gas continuous/cogeneration for industrial CHP, distributed generation, and campus power.
Up to 2500 ekW continuous natural gas generator at 50 Hz with Cat G3520H engine. 97.5L displacement, up to 25% hydrogen by volume capability on certain configurations, for cogeneration and distributed generation.
3-phasecontinuous-dutycogeneration
Caterpillar
Caterpillar 3512C
Diesel standby generator set with the Cat 3512C V-12 engine, rated 1500 ekW standby at 60 Hz. EPA Tier 2 for stationary emergency use.
1.5 MW standby · Diesel · Liquid-cooled
1500 ekW diesel standby for data centers, hospitals, and industrial sites.
The Caterpillar 3512C is a 1500 kW standby diesel generator. 51.8L V12 ATAAC, 14.7:1 compression, EPA Tier 2. Fuel: 104.6 gal/hr at full load. Medium-voltage outputs to 13,800V for mission-critical applications.
Tier 23-phasedata-centerhospital-large
Cummins
Cummins C1000 D6
1 MW standby diesel with the Cummins QST30 30.5-liter V-12 engine, EPA Tier 2.
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for Tier III+ data centers, large hospitals, and mission-critical infrastructure requiring megawatt-class power.
1000 kW diesel standby generator with QST30 30.5L V-12 engine, liquid-cooled, for data center, hospital, and mission-critical standby applications requiring megawatt-class power.
Tier 23-phasedata-centerhospital
Cummins
Cummins C1000 N6
1000 kW standby natural gas generator set with the Cummins QSK60G engine.
1 MW standby · Natural Gas · Liquid-cooled
1000 kW natural gas standby for data centers, large campuses, and utility peak shaving on gas.
1000 kW standby natural gas generator with QSK60G V16 engine. EPA NSPS certified, 36.4% electrical efficiency at 100% rated load (ISO 3046/1), pipeline natural gas.
3-phasecommercial-standbyindustrial
Cummins
Cummins C1100 D6
1100 kW diesel with QSK38 V-12 engine. MCRS fuel injection. Full Cummins vertical integration. Paralleling for multi-MW.
1.1 MW standby · Diesel · Liquid-cooled
1100 kW diesel standby for Tier III+ data centers, large hospitals, and critical infrastructure requiring above-megawatt power.
1100 kW diesel standby generator with QSK38 37.7L V-12 engine and MCRS fuel injection. EPA Tier 2 compliant, PowerCommand control, liquid-cooled, for data center, hospital, and mission-critical standby applications.
Tier 23-phasedata-centerhospital
Cummins
Cummins C1250 D6
1250 kW / 1563 kVA standby diesel with the Cummins QSK38-G17 engine, EPA Tier 2, with PC 3.3 as the standard controller.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW diesel standby for Tier III+ data centers, large hospitals, and mission-critical infrastructure.
1250 kW diesel standby generator with the Cummins QSK38-G17 engine, EPA Tier 2, with PC 3.3 as the standard controller, for data center, hospital, and mission-critical standby applications.
Tier 23-phasedata-centerhospital
Cummins
Cummins C1250 D6e
1.25 MW standby with the Cummins QSK38-G17 engine, PC 3.3 standard control and EPA Tier 2 emissions certification.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW diesel standby for data centers, hospitals, and mission-critical facilities.
1250 kW standby / 1136 kW prime 60 Hz diesel generator set with the Cummins QSK38-G17 engine, EPA Tier 2 emissions certification and PC 3.3 as the standard controller.
Tier 23-phasedata-centerhospital
Cummins
Cummins C1500 D6
1500 kW standby / 1365 kW prime at 60 Hz from the Cummins QSK50 V-16 engine with MCRS fuel injection.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for Tier IV data centers, university campuses, and major industrial plants.
1500 kW diesel standby generator with QSK50 50.3L V-16 engine and MCRS fuel injection. EPA Tier 2 compliant engine with 2P2L cooling, for data center, hospital, and mission-critical standby applications.
Tier 23-phasedata-centerhospital
Cummins
Cummins C1500 D6e
1.5 MW standby with the Cummins QSK38-G18 engine, PC 3.3 standard control and EPA Tier 2 emissions certification.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for data centers, hospitals, and mission-critical facilities.
1500 kW standby / 1364 kW prime 60 Hz diesel generator set with the Cummins QSK38-G18 engine, EPA Tier 2 emissions certification and PC 3.3 as the standard controller.
Tier 23-phasedata-centerhospital
Cummins
Cummins C1750 D6e
1.75 MW standby Centum Series generator set with QSK50-G24 engine and PC 3.3 standard controller.
1.8 MW standby · Diesel · Liquid-cooled
1750 kW Centum diesel standby for data centers and mission-critical facilities.
1750 kW Centum Series diesel standby generator with QSK50-G24 engine, S7L1D-F4 standard alternator, PC 3.3 standard controller and EPA Tier 2 certification, for data center applications.
Tier 23-phasedata-centermission-critical
Cummins
Cummins C2000 D6
2 MW diesel with QSK60 V-16 engine. Full Cummins vertical integration. Paralleling for multi-MW arrays. Proven mega-diesel platform.
2 MW standby · Diesel · Liquid-cooled
2000 kW diesel standby for Tier III/IV data centers, large industrial facilities, and mission-critical infrastructure requiring multi-megawatt power.
2000 kW diesel standby generator with QSK60 60L V-16 engine. PowerCommand control, liquid-cooled, for data center, industrial, and mission-critical standby applications requiring multi-megawatt power.
Tier 23-phasedata-centerindustrial
Cummins
Cummins C2000 D6e
2 MW standby and 1825 kW prime at 60 Hz from the Cummins QSK50-G24/G25 engine, with the PC 3.3 controller as standard.
2 MW standby · Diesel · Liquid-cooled
2000 kW Centum diesel standby for data centers and mission-critical facilities.
2000 kW standby / 1825 kW prime Centum Series diesel generator set at 60 Hz with the Cummins QSK50-G24/G25 engine, S7L1D-G4 alternator and PC 3.3 controller as standard, EPA Tier 2, for data center applications.
Tier 23-phasedata-centermission-critical
Cummins
Cummins C2250 D6
2.25 MW diesel with QSK60 V-16 engine. Mid-range of the QSK60 platform. Full Cummins vertical integration. Paralleling for multi-MW arrays.
2.3 MW standby · Diesel · Liquid-cooled
2250 kW diesel standby for Tier III/IV data centers, large industrial facilities, and mission-critical infrastructure.
2250 kW diesel standby generator with QSK60 60L V-16 engine. PowerCommand control, liquid-cooled, for data center, industrial, and mission-critical standby applications.
Tier 23-phasedata-centerindustrial
Cummins
Cummins C2500 D6
2.5 MW diesel with QSK60 V-16 engine at peak output. Full Cummins vertical integration. Maximum QSK60 platform capacity in a single genset.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW diesel standby for Tier III/IV data centers, large industrial plants, and mission-critical infrastructure requiring maximum QSK60 output.
2500 kW diesel standby generator with QSK60 60L V-16 engine. PowerCommand control, liquid-cooled, top of the QSK60 platform for data center and mission-critical standby applications.
Tier 23-phasedata-centerindustrial
Cummins
Cummins C2750 D6e
2.75 MW standby Centum Series generator set with QSK78-G36 engine and PC 3.3 standard controller.
2.8 MW standby · Diesel · Liquid-cooled
2750 kW Centum diesel standby for hyperscale data centers and mission-critical facilities requiring near-3 MW premium standby power.
2750 kW Centum Series diesel standby generator with QSK78-G36 engine, S9L1D-E4 standard alternator and PC 3.3 standard controller, for data center and mission-critical standby.
3-phasedata-centermission-critical
Cummins
Cummins C3000 D6
3 MW standby diesel generator set with the Cummins QSK95-G2 engine. PC 3.3 controller standard.
3 MW standby · Diesel · Liquid-cooled
3000 kW diesel standby for hyperscale data centers, large industrial complexes, and utility-scale mission-critical infrastructure.
3000 kW standby (2750 kW prime) 60 Hz diesel generator set with the Cummins QSK95-G2 engine and the PC 3.3 standard controller, for data center, utility, and mission-critical standby applications requiring 3 MW of power.
3-phasedata-centerindustrial
Cummins
Cummins C3000 D6eb
3 MW standby diesel with the Cummins QSK78-G37 engine, S9L1D-E4 standard alternator and PC 3.3 standard controller.
3 MW standby · Diesel · Liquid-cooled
3000 kW Centum diesel standby for hyperscale data centers and mission-critical facilities requiring 3 MW of standby power.
3000 kW Centum Series diesel standby generator with QSK78-G37 engine, PC 3.3 standard controller and EPA Tier 2 emissions certification, for hyperscale data center applications.
Tier 23-phasedata-centermission-critical
Cummins
Cummins C3250 D6
3.25 MW standby diesel with the Cummins QSK95-G2 engine, LVSI804W standard alternator and PC 3.3 standard controller.
3.3 MW standby · Diesel · Liquid-cooled
3250 kW diesel standby for hyperscale data centers, large industrial complexes, and mission-critical infrastructure.
3250 kW diesel standby generator with Cummins QSK95-G2 engine and PC 3.3 standard controller, for hyperscale data center and mission-critical standby applications.
3-phasedata-centerindustrial
Cummins
Cummins C3500 D6
3.5 MW standby and 3000 kW prime at 60 Hz from the Cummins QSK95-G2 diesel engine, for hyperscale standby arrays.
3.5 MW standby · Diesel · Liquid-cooled
3500 kW diesel standby for hyperscale data centers, utility-scale standby, and mission-critical applications.
3500 kW standby / 3000 kW prime diesel generator set at 60 Hz with the Cummins QSK95-G2 engine and PC 3.3 controller, for hyperscale data center and utility standby applications.
3-phasedata-centerindustrial
Cummins
Cummins C750 D6
750 kW standby diesel generator set with a Cummins QSK23-G3 engine and the HPI-PT full authority electronic fuel system.
750 kW standby · Diesel · Liquid-cooled
750 kW diesel standby for mission-critical data centers, large hospitals, and industrial campuses.
750 kW standby diesel generator set at 60 Hz with a Cummins QSK23-G3 23.1L inline-6 engine and HPI-PT fuel injection, for data center, hospital, and mission-critical standby applications.
3-phasecommercial-standbylarge-commercial
Cummins
Cummins C800 D6
800 kW standby diesel generator set with a Cummins QSK23-G3 engine and the HPI-PT full authority electronic fuel system.
800 kW standby · Diesel · Liquid-cooled
800 kW diesel standby for mission-critical data centers, large hospitals, and industrial campuses requiring N+1 redundancy.
800 kW standby, 727 kW prime diesel generator set at 60 Hz with a Cummins QSK23-G3 23.1L inline-6 engine and HPI-PT fuel injection, liquid-cooled, for data center, hospital, and mission-critical standby applications.
3-phasecommercial-standbylarge-commercial
Cummins
Cummins C900 D6
900 kW standby diesel at 60 Hz on the Cummins QST30-G3, a 30.5-liter V12 Quantum series engine.
900 kW standby · Diesel · Liquid-cooled
900 kW diesel standby for Tier III+ data centers, large hospitals, and mission-critical infrastructure.
900 kW diesel standby generator at 60 Hz with Cummins QST30-G3 30.5L V-12 engine, liquid-cooled, for data center, hospital, and mission-critical standby applications.
3-phasecommercial-standbylarge-commercial
Cummins
Cummins KTA38
887 kW standby diesel generator at 50 Hz on the Cummins KTA38-G5 37.8-liter V12 engine.
887 kW standby · Diesel · Liquid-cooled
887 kW diesel standby for large industrial plants, hospitals, and mission-critical infrastructure.
887 kW standby / 811 kW prime diesel generator at 50 Hz. Cummins KTA38-G5 37.8L V12 with Cummins PT direct injection, for industrial, hospital, campus, and mining standby applications.
3-phaseindustrialhospital-large
Cummins
Cummins KTA50
1340 kW diesel with legendary KTA50 engine. Full Cummins vertical integration.
1.3 MW standby · Diesel · Liquid-cooled
1340 kW diesel standby for Tier III+ data centers, large hospitals, and heavy industrial plants.
1340 kW standby / 1200 kW prime diesel generator at 50 Hz. KTA50-GS8 50.3L V16 PT fuel injection, 2-pump 2-loop cooling. Legacy Cummins platform for data center, industrial, hospital, and mining standby applications.
3-phasedata-centerhospital-large
Cummins
Cummins QSK23
800 kW standby diesel generator rating on the Cummins QSK23-G3: a 23.1-liter inline-6 with the HPI-PT full authority electronic fuel system.
800 kW standby · Diesel · Liquid-cooled
800 kW diesel standby for mission-critical data centers, large hospitals, and industrial campuses.
1160 kW standby diesel generator at 60 Hz on the Cummins QSK38-G5 37.7-liter V12 engine with Modular Common Rail fuel system.
1.2 MW standby · Diesel · Liquid-cooled
1160 kW diesel standby for Tier III+ data centers, large hospitals, and critical infrastructure.
1160 kW standby / 965 kW prime diesel generator at 60 Hz with the Cummins QSK38-G5 37.7L V12 MCRS engine. EPA Tier 2, 2P2L cooling, 24V starting.
Tier 23-phasedata-centerhospital-large
Cummins
Cummins QSK50
1500 kW standby diesel generator set with the Cummins QSK50-G4 engine, MCRS fuel system and 2P2L cooling.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel standby for data centers, university campuses, and major industrial plants.
1500 kW standby / 1365 kW prime diesel generator with QSK50-G4 50.3L V16 MCRS engine. EPA Tier 2 and TA Luft compliant, 2P2L cooling, 24V starting.
Tier 23-phasedata-centerhospital-large
Cummins
Cummins QSK60
2000 kW diesel with QSK60 engine. Full Cummins vertical integration. Paralleling for multi-MW.
2 MW standby · Diesel · Liquid-cooled
2000 kW diesel standby for hyperscale data centers, large hospitals, and campus microgrids.
2000 kW diesel standby generator. The data center industry standard — V-16, 60.2L, Tier 2. Cummins' flagship for mission-critical power.
Tier 23-phasedata-centerhospital
Cummins
Cummins QSK78
2750 kW diesel with QSK78 engine. Full Cummins vertical integration. Paralleling for multi-MW.
2.8 MW standby · Diesel · Liquid-cooled
2750 kW diesel standby for hyperscale data centers, critical infrastructure, and utility peaking.
2750 kW standby / 2500 kW prime diesel generator with QSK78-G14 V18 engine. EPA Tier 4 Final, 78-liter displacement for mission-critical and data center power.
Tier 4 Final3-phasedata-centerhospital
Cummins
Cummins QSK95
3010 kW standby diesel at 50 Hz with the Cummins QSK95-G10: 95.3 L V16, quad-turbocharged, capable of accepting 100% of rated load in one step.
3.0 MW standby · Diesel · Liquid-cooled
3010 kW diesel standby for hyperscale data centers, campus microgrids, and utility peak shaving.
3010 kW standby / 2690 kW prime diesel generator with QSK95-G10 V16 engine. EPA Tier 2, quad turbo, MCRS fuel injection, ISO 8528-G3 transient capability.
Tier 23-phasedata-centerhospital
Generac
Generac MD1250
1250 kW modular diesel with factory paralleling. N+1 redundancy, easier installation, and scalable power architecture for multi-megawatt systems.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW modular diesel for Tier III+ data centers, large hospitals, and mission-critical facilities requiring redundancy.
1250 kW modular diesel standby generator system. Factory-paralleled configuration with Mitsubishi 49.0L V12 engine for N+1 redundancy.
Tier 23-phasecommercial-standbyindustrial
Generac
Generac MD1500
1500 kW modular diesel with factory paralleling. N+1 redundancy, easier installation, and scalable power architecture for multi-megawatt systems.
1.5 MW standby · Diesel · Liquid-cooled
1500 kW modular diesel for Tier IV data centers, university campuses, and mission-critical facilities requiring redundancy.
1500 kW modular diesel standby generator system. Factory-paralleled configuration with Mitsubishi 65.4L engine for N+1 redundancy.
Tier 23-phasecommercial-standbyindustrial
Generac
Generac MD300
300 kW modular diesel with factory paralleling. N+1 redundancy, easier installation, and scalable power architecture.
300 kW standby · Diesel · Liquid-cooled
300 kW modular diesel for data centers, hospitals, and mission-critical facilities requiring redundancy and serviceability.
300 kW modular diesel standby generator system. Factory-paralleled configuration with Iveco/FPT 10.3L inline-6 engine for N+1 redundancy.
3-phasecommercial-standbyindustrial
Generac
Generac MD400
400 kW modular diesel with factory paralleling. N+1 redundancy, easier installation, and scalable power architecture.
400 kW standby · Diesel · Liquid-cooled
400 kW modular diesel for data centers, hospitals, and mission-critical facilities requiring redundancy and serviceability.
400 kW modular diesel standby generator system. Factory-paralleled configuration with Perkins 12.5L inline-6 engine for N+1 redundancy.
3-phasecommercial-standbyindustrial
Generac
Generac MD500
500 kW modular diesel with factory paralleling. N+1 redundancy, easier installation, and scalable power architecture.
500 kW standby · Diesel · Liquid-cooled
500 kW modular diesel for data centers, hospitals, and mission-critical facilities requiring redundancy and serviceability.
500 kW modular diesel standby generator system. Factory-paralleled configuration with Perkins 15.2L inline-6 engine for N+1 redundancy.
3-phasecommercial-standbyindustrial
Generac
Generac MD500-T4
500 kW Tier 4 Final modular diesel with factory paralleling. N+1 redundancy, lower emissions, and scalable power architecture.
500 kW standby · Diesel · Liquid-cooled
500 kW Tier 4 Final modular diesel for data centers, hospitals, and mission-critical facilities in emissions-sensitive areas requiring redundancy.
500 kW modular diesel standby generator system, Tier 4 Final emissions. Factory-paralleled configuration with Perkins 18.1L inline-6 engine for N+1 redundancy.
Tier 4 Final3-phasecommercial-standbyindustrial
Generac
Generac MD600
600 kW modular diesel with factory paralleling. N+1 redundancy, easier installation, and scalable power architecture.
600 kW standby · Diesel · Liquid-cooled
600 kW modular diesel for data centers, hospitals, and mission-critical facilities requiring redundancy and serviceability.
600 kW modular diesel standby generator system. Factory-paralleled configuration with Perkins 18.1L inline-6 engine for N+1 redundancy.
3-phasecommercial-standbyindustrial
Generac
Generac MD750
750 kW modular diesel with factory paralleling. N+1 redundancy, easier installation, and scalable power architecture.
750 kW standby · Diesel · Liquid-cooled
750 kW modular diesel for data centers, hospitals, and mission-critical facilities requiring redundancy and serviceability.
750 kW modular diesel standby generator system. Factory-paralleled configuration with Mitsubishi S12A2-Y2PTAW-2 33.9L engine for N+1 redundancy.
Tier 23-phasecommercial-standbyindustrial
Generac
Generac SD1000/MD1000
1000 kW mission-critical diesel on the same Perkins 30.6L platform as the SD900 at higher output. Competitive alternative to CAT and Cummins.
1 MW standby · Diesel · Liquid-cooled
1000 kW diesel standby for data centers, hospitals, and large commercial or industrial facilities requiring reliable backup power.
1.1 MW standby · Natural Gas / LPG · Liquid-cooled
1,050 kW (1 MW) natural gas standby for data centers, hospitals, industrial campuses, and utility-scale backup.
1,050 kW natural gas stationary standby generator. PSI 52.3L V16 turbocharged engine, Stamford AVK alternator, DSE 7420 MKII. Made in USA.
3-phasedata-centerhospital
Gillette
Gillette SP-8000
Factory-direct. PSI 39.2L V12 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
800 kW standby · Natural Gas · Liquid-cooled
800 kW natural gas standby for data centers, hospitals, industrial campuses, and large municipal facilities.
800 kW natural gas stationary standby generator. PSI 39.2L V12 turbocharged engine, Stamford HCI634 alternator, DSE 7420 MKII. Standby rating published for natural gas. Made in USA.
3-phasedata-centerhospital
Gillette
Gillette SPHD-9000
Factory-direct. Hyundai 21.9L V12 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
900 kW standby · Diesel · Liquid-cooled
900 kW diesel standby for data centers, hospitals, industrial campuses, and large-scale critical infrastructure.
900 kW stationary diesel standby generator with Hyundai DP222CCS V12 engine. Made-in-USA with Stamford S6DD311 alternator, shunt excitation, and DSE 7420 MKII controller.
1,000 kW (1 MW) diesel standby for data centers, hospitals, industrial campuses, and utility-scale backup.
1,000 kW stationary diesel standby generator with Mitsubishi S12H engine. USA factory built with Stamford AVK alternator, PMG excitation, and DSE 7420 MKII controller.
Tier 23-phasedata-centerhospital
Gillette
Gillette SPMI-2M
Factory-direct 2 MW diesel. Mitsubishi S16R V16. No proprietary lock-in.
2 MW standby · Diesel · Liquid-cooled
2,000 kW (2 MW) diesel standby for hyperscale data centers, hospitals, industrial campuses, and utility-grade backup.
Factory-direct. Mitsubishi S12A2 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
800 kW standby · Diesel · Liquid-cooled
800 kW diesel standby for data centers, hospitals, industrial campuses, and large-scale critical infrastructure.
800 kW stationary diesel standby generator with Mitsubishi S12A2 engine. USA factory built with Stamford AVK HCI634H alternator, PMG excitation, and DSE 7420 MKII controller.
Tier 23-phasedata-centerhospital
Kohler
Kohler 1000REOZMD
1020 kW diesel standby -- Mitsubishi S12H-Y2PTAW-1, sub-3% THD. Decision-Maker controller for load management and paralleling.
1.0 MW standby · Diesel · Liquid-cooled
1 MW industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
1020 kW diesel industrial standby generator powered by Mitsubishi. Large-frame REOZ for data centers, hospitals, and mission-critical facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 1250REOZDD
Standby: see spec sheet · Diesel · Liquid-cooled
Diesel industrial standby generator. Mission-critical standby for data centers, hospitals, and large facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 1250REOZMD
1280 kW diesel standby -- Mitsubishi S12R-Y2PTAW-1, sub-3% THD. Decision-Maker controller for load management and paralleling.
1.3 MW standby · Diesel · Liquid-cooled
1280 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
1280 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 1250ROZMC
1280 kW diesel standby -- Mitsubishi S12R V12 turbo, sub-3% THD. Decision-Maker controller for load management and paralleling.
1.3 MW standby · Diesel · Liquid-cooled
1280 kW commercial/industrial standby for hospitals, data centers, and large campuses requiring NFPA 110 Level 1.
1280 kW diesel 1800 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 1500REOZDD
Standby: see spec sheet · Diesel · Liquid-cooled
Diesel industrial standby generator. Mission-critical standby for data centers, hospitals, and large facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 1600REOZMD
1600 kW industrial diesel -- Mitsubishi S16R-Y2PTAW-1, offered with the APM603 or Decision-Maker 6000 paralleling controller. Sub-3% THD, UL 2200, NFPA 110 Level 1.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1600 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 1600ROZMC
1600 kW industrial diesel -- Mitsubishi S16R V16 turbo, offered with the APM603 or Decision-Maker 6000 paralleling controller. Sub-3% THD, UL 2200, NFPA 110 Level 1.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
1600 kW diesel 1800 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 1750REOZMD
1.8 MW standby · Diesel · Liquid-cooled
1780 kW diesel industrial generator powered by Mitsubishi.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 2000REOZDD
Standby: see spec sheet · Diesel · Liquid-cooled
Diesel industrial standby generator.
3-phasedata-centerhealthcare
Kohler
Kohler 2000REOZMD
2000 kW industrial diesel -- Mitsubishi S16R-Y2PTAW2-1 with Decision-Maker 6000 paralleling. UL 2200, NFPA 110 Level 1.
2 MW standby · Diesel · Liquid-cooled
2000 kW industrial standby for data centers, hospitals, and utility-scale facilities.
2000 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
2000 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
2000 kW diesel 1800 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 2250REOZDD
Standby: see spec sheet · Diesel · Liquid-cooled
Industrial standby for data centers and mission-critical campuses.
Diesel industrial standby generator. Mission-critical standby for data centers and large industrial facilities.
3-phasedata-centerhealthcare
Kohler
Kohler 2500REOZDB
Standby: see spec sheet · Diesel · Liquid-cooled
Diesel industrial standby generator.
3-phasedata-centerhealthcare
Kohler
Kohler 2500REOZDC
2500 kW industrial diesel -- Detroit Diesel/MTU 16V4000G83L with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW industrial standby for data centers, hospitals, and utility-scale facilities. Parallel-ready for N+1 mission-critical redundancy.
2500 kW diesel industrial generator powered by Detroit Diesel/MTU. Mission-critical standby for data centers, hospitals, and large commercial facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler 3250REOZD
Standby: see spec sheet · Diesel · Liquid-cooled
Industrial standby for large data centers and mission-critical campuses.
Diesel industrial standby generator.
3-phasedata-centerindustrial-heavy
Kohler
Kohler 900REOZMD
Standby: see spec sheet · Diesel · Liquid-cooled
diesel industrial standby generator.
3-phasedata-centerhealthcare
Kohler
Kohler KD1000
Megawatt-class KD at 1000 kW -- Kohler KD27V12, APM603 or APM802 controller.
1 MW standby · Diesel · Liquid-cooled
1000 kW industrial standby for data centers, hospitals, and large commercial campuses. NFPA 110 Level 1, UL 2200 listed.
1000 kW diesel industrial standby generator. Megawatt-class KD Series unit for data centers, hospitals, and mission-critical infrastructure.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD1250-4
Megawatt-class KD at 1250 kW -- Kohler KD36V16, APM603 controller.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW industrial standby for data centers, hospitals, and large commercial campuses. NFPA 110 Level 1, UL 2200 listed.
Megawatt-class KD at 1250 kW -- Kohler KD36V16, APM603 or APM802 controller.
1.3 MW standby · Diesel · Liquid-cooled
1250 kW industrial standby for data centers, hospitals, and large commercial campuses. NFPA 110 Level 1, UL 2200 listed.
1250 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and large commercial facilities.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD1350
1.4 MW standby · Diesel · Liquid-cooled
1350 kW diesel industrial standby generator. KD Series platform.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD1500
1.5 MW standby · Diesel · Liquid-cooled
1500 kW diesel industrial standby generator. KD Series platform.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD1600
Megawatt-class KD at 1600 kW -- Kohler KD45V20, APM603 or APM802 controller.
1.6 MW standby · Diesel · Liquid-cooled
1600 kW industrial standby for data centers, hospitals, and large commercial campuses. NFPA 110 Level 1, UL 2200 listed.
1600 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and heavy industrial applications.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD1750
Megawatt-class KD at 1750 kW -- Kohler KD45V20, APM603 or APM802 controller.
1.8 MW standby · Diesel · Liquid-cooled
1750 kW industrial standby for data centers, hospitals, and large commercial campuses. NFPA 110 Level 1, UL 2200 listed.
1750 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and mission-critical infrastructure.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD2000
2000 kW KD Series -- Kohler KD62V12 with PM pilot exciter.
2 MW standby · Diesel · Liquid-cooled
2000 kW industrial standby for data centers, hospitals, and critical infrastructure requiring multi-MW backup with NFPA 110 Level 1.
2000 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and mission-critical infrastructure requiring multi-megawatt backup.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD2250
2.3 MW standby · Diesel · Liquid-cooled
2250 kW diesel industrial standby generator. KD Series platform.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD2500
2500 kW KD Series -- Kohler KD62V12 with PM pilot exciter.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW industrial standby for data centers, hospitals, and critical infrastructure requiring multi-MW backup with NFPA 110 Level 1.
2500 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and heavy industrial facilities requiring 2+ MW backup.
Tier 23-phasedata-centerhealthcare
Kohler
Kohler KD2500-4
2500 kW KD Series -- Kohler KD62V12 with PM pilot exciter.
2.5 MW standby · Diesel · Liquid-cooled
2500 kW industrial standby for data centers, hospitals, and critical infrastructure requiring multi-MW backup with NFPA 110 Level 1.
800 kW diesel standby — MTU 2000-series V12, 23.9L. Medium-voltage 4,160V option, EUP injection, separate intercooler circuit, 59 gph.
800 kW standby · Diesel · Liquid-cooled
Industrial/hospital standby at 800 kW.
800 kW diesel standby generator with MTU 12V2000G85TB 23.9L V12 engine, EPA Tier 2, 208–4160V including medium voltage, electronic unit pump injection, ADEC governor. 4675 x 2292 x 2341 mm, 17,379 lb.
Tier 23-phasecommercial-standbyindustrial-standby
MTU
MTU 12V4000 DS1250
1,250 kW standby. MTU 57.2L V12, 380-13,800V, HVO and GtL fuels meeting EN15940.
1.3 MW standby · Diesel · Liquid-cooled
Standby power at 1,250 kW. Diesel at 90 gph at full load, 9 voltage configs to 13.8kV, SCAQMD + Tier 2.
1,250 kW standby diesel generator from MTU (Rolls-Royce). 57.2L V12 engine, EPA Tier 2 + SCAQMD, 380-13,800V.
Tier 23-phasedata-centerhospital-large
MTU
MTU 12V4000 DS1500
1,500 kW standby. MTU 57.2L V12, 380-13,800V, HVO and GtL fuels meeting EN15940.
1.5 MW standby · Diesel · Liquid-cooled
Standby power at 1,500 kW. Diesel at 111 gph at full load, 9 voltages to 13.8kV, HVO compatible.
1,500 kW standby diesel generator from MTU (Rolls-Royce). 57.2L V12 engine, EPA Tier 2 + SCAQMD, 380-13,800V.
Standby power at 2.5 MW. Diesel at 183 gph at full load, standby-only rating.
2,500 kW standby diesel generator from MTU (Rolls-Royce). 76.3L V16 engine, EPA Tier 2 + SCAQMD, 380-13,800V. 16-cylinder Series 4000.
Tier 23-phasedata-centerhospital-large
MTU
MTU 20V4000 DS2800
2,800 kW diesel standby — MTU 20V4000 95.4L V20.
2.8 MW standby · Diesel · Liquid-cooled
Utility-scale standby at 2.8 MW. Diesel at 186 gph, 480V-13.8kV direct MV connection, 62,000 lb installation.
2800 kW diesel standby generator with MTU 20V4000G83 95.4L 20-cylinder V common-rail engine, EPA Tier 2, 380V–13.8kV including medium voltage, ADEC governor, 7626 x 3099 x 3569 mm, 62,056 lb.
Tier 23-phasecommercial-standbyindustrial-standby
MTU
MTU 20V4000 DS3250
3,250 kW diesel standby — top of the MTU product line. 95.4L V20 at 3,490 kWm, 480V-13.8kV, standby-only, 223 gph.
3.3 MW standby · Diesel · Liquid-cooled
Maximum single-unit standby at 3.25 MW. Diesel at 223 gph, 480V-13.8kV medium-voltage, 65,000+ lb power plant.
3250 kW diesel standby generator with MTU 20V4000G83L 95.4L 20-cylinder V common-rail engine, EPA Tier 2, 480V–13.8kV medium and high voltage, ADEC governor. 7766 x 3099 x 3569 mm, 65,369 lb.
Tier 23-phasecommercial-standbyindustrial-standby
Need service for the Russelectric RTS-03 Bypass-Isolation ATS?
Our technicians work on every major component OEM. We stock common parts and source rare ones.