Overview#
The Blue Star NG1050-01P is rated 900 kWe prime on natural gas (575 kWe on LP). Three-phase 480V, 600V, and 4160V only — no 208V or 240V. The NG1050-01P carries a 1-year / 1,500-hour prime warranty. UL 2200 listing applies through 600VAC; 4160V is not UL-listed.
Voltage configurations#
| Voltage | Phase | Alternator | Connection |
|---|---|---|---|
| 277/480V | 3 | S6L1D-F | 4-lead WYE |
| 347/600V | 3 | S6L1D-F | 4-lead WYE |
| 4160V | 3 | MVWI734F | 6-lead WYE |
All carry 105°C prime temperature rise and ±0.5% voltage regulation.
When to spec the NG1050-01P#
- 900 kWe prime duty on natural gas (575 kWe on LP), three-phase 480V, 600V, or 4160V
- Large commercial, data center, or hospital facilities with confirmed prime-duty load profiles at megawatt class
- Sites requiring prime-rated certification on gaseous fuel at this output level
Our service experience#
Prime-duty use on a 16-cylinder engine means substantially higher hour accumulation — budget for an aggressive spark plug and ignition coil schedule per PSI's prime-duty maintenance specification.