Blue Star Power Systems · PSI Industrial Gaseous (500-1250 kW)

Blue Star NG1050-01

1050 kW standby / 900 kW prime · Natural Gas / LPG · Liquid-cooled

1050 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 53L V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V.

Blue Star Power Systems Blue Star NG1050-01 generator — specifications and details
Standby power
1050 kW / 900 kW prime
Voltage options
277/480V, 347/600V, 4160V
Frequency / Phase
60 Hz · 3-phase
Engine
PSI 53L · 52.3L
EPA / Emissions
EPA Stationary Spark Ignition
Alternator
Stamford S6L1D-F

Overview#

The Blue Star NG1050-01 is a 1,050-kilowatt natural gas / LP standby generator built on the PSI 53-liter V16 platform. It is rated 1,050 kWe standby on natural gas and 700 kWe on LP at 60 Hz / 1800 RPM. Available in 480V, 600V, and 4160V three-phase configurations only — no 208V or 240V options. UL 2200 listing applies through 600VAC; the 4160V configuration is not UL-listed.

The PSI 53L V16#

The PSI 53L is a 52.3-liter (3,192 cu in) V16 turbocharged-aftercooled spark-ignition engine:

  • 1,589 bHp (1,185 kWm) at 1800 RPM standby
  • 16-cylinder Vee — four more cylinders than the 40L V12, using the same bore (5.91 in) and stroke (7.28 in)
  • 601 GPM water pump — highest flow in the Blue Star gaseous lineup
  • Large fluid systems: 45.2 gal oil, 65.4 gal system coolant
  • 67,300 CFM ventilation requirement — size the mechanical room accordingly
  • EPA Stationary Spark Ignition certified under 40 CFR 60 Subpart JJJJ

Voltage configurations#

VoltagePhaseAlternatorConnection
277/480V3Stamford S6L1D-F4-lead WYE
347/600V3Stamford S6L1D-F4-lead WYE
4160V3Stamford MVWI734F6-lead WYE

All configurations carry 125°C standby temperature rise and ±0.5% voltage regulation. UL 2200, cUL, and CSA certifications apply through 600VAC only. The 4160V configuration is not UL-listed.

Infrastructure requirements#

At 1,050 kW, infrastructure demands are substantially larger than sub-megawatt units:

  • Fuel pressure: 30 in. WC sustained under full standby load (vs 11 in. WC for most smaller Blue Star gaseous models)
  • Ventilation: 67,300 CFM — verify mechanical room design with this value
  • Cooling: 3,095,580 BTU/hr coolant heat rejection; 1,277,400 BTU/hr radiated

When to spec the NG1050-01#

  • 850 kW–1,050 kW standby loads on natural gas or LP (three-phase 480V, 600V, or 4160V)
  • Data centers, campuses, or large hospital non-critical loads requiring megawatt-class gaseous standby
  • Sites with 4160V distribution where UL-listing at 4160V is not required by the AHJ

Our service experience#

The PSI 53L V16 is a large and specialized platform. At 16 cylinders, scheduled maintenance (spark plugs, ignition coils) involves significantly more labor than smaller engines. The 45.2 gal oil system requires a planned drain and capture strategy. Parts lead time from PSI is the primary service risk for this low-volume platform in most territories.

Engineering specifications

Physical

Length
252 in
Width
106 in
Height
117 in
Dry weight
25,860 lb

Acoustic

Sound @ 7m, full load
92 dBA
Enclosure
Open

Fuel system & runtime

NG required pressure
30 in WC

Thermal & ventilation

Heat to coolant
3,095,580 BTU/hr
Heat radiated
1,277,400 BTU/hr
Exhaust flow
6,855 CFM
Exhaust temp
1212 °F
Combustion air
2,205 CFM
Ventilation air
67,300 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Blue Star NG1050-01

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Blue Star NG1050-01

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

11,025,000 BTU/hr≈ 11025.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Service intervals

Manufacturer-recommended intervals for the Blue Star NG1050-01 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 4000 hours
Air filter
Every 1000 hours
Spark plugs
Every 1500 hours
Major overhaul
≈ 15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Turbocharger(s)Significant power loss, heavy exhaust smoke12,000+severe
Ignition system (multi-cylinder)Multiple misfires, output derating1,500+moderate
Charge air coolerReduced output, elevated intake temperatures10,000+moderate

Frequently Asked Questions

What is the standby rating of the NG1050-01?
The Blue Star NG1050-01 is rated 1,050 kWe standby on natural gas and 700 kWe standby on LP at 60 Hz / 1800 RPM. Deration is 0.8% per 5°F above 77°F inlet air temperature and 2.5% per 1,000 ft above 1,200 ft altitude — a lower per-degree rate than smaller models, reflecting the engine's thermal mass. Fuel pressure requirement is 30 in. water column.
What engine is in the NG1050-01?
The PSI 53L — a 52.3-liter (3,192 cu in) V16 turbocharged-aftercooled spark-ignition engine producing 1,589 bHp (1,185 kWm) at 1800 RPM standby. The 53L uses the same 5.91-in bore and 7.28-in stroke as the 40L V12 but adds four cylinders for 16 total, increasing displacement proportionally. Oil capacity is 45.2 gal and system coolant is 65.4 gal.
Is the NG1050-01 available at 208V or 240V?
No. The NG1050-01 is offered in 480V, 600V, and 4160V three-phase configurations only. UL 2200, cUL, and CSA certifications apply through 600VAC — the 4160V configuration (Stamford MVWI734F alternator) is not UL-listed.
How does the NG1050-01 LP rating compare to NG output?
The NG1050-01 delivers 700 kWe on LP standby — 67% of the 1,050 kWe NG rating. This is a lower LP-to-NG ratio than smaller models, reflecting the increased thermal loading at megawatt-class output. LP fuel consumption at 100% standby load is 3,867 ft³/hr.

Compatible equipment

More in the PSI Industrial Gaseous (500-1250 kW)

500–1250 kW natural gas and LP standby power on PSI V12 and V16 spark-ignition platforms.

Similar models

Blue Star Power Systems Blue Star NG1050-01P 1.1 MW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG1050-01P

Open Basler controller + PSI V16 engine + Stamford alternator — prime-rated, no proprietary lock-in. Serviceable by any qualified tech.

1.1 MW standby · Natural Gas / LPG · Liquid-cooled

900 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 53L V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center
Blue Star Power Systems Blue Star NG1250-01 1.3 MW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG1250-01

Open Basler controller + PSI high-output V16 engine + Stamford alternator — no proprietary lock-in. 1.25 MW gas class without OEM dealer dependency.

1.3 MW standby · Natural Gas · Liquid-cooled

1250 kW natural-gas-only standby generator from Blue Star Power Systems. PSI 53LHO high-output V16 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 480-4160V. LP not available.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center
Blue Star Power Systems Blue Star NG800-01 800 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG800-01

Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. 800 kW gas class without OEM dealer dependency.

800 kW standby · Natural Gas / LPG · Liquid-cooled

800 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 40L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-4160V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Services for the Blue Star NG1050-01

Need service or parts for the Blue Star NG1050-01?

We service every major OEM and stock genuine parts for the most common models.

Last reviewed: