Blue Star Power Systems · Gaseous Product Line (PSI 40L)

New

Blue Star NG800-01

800 kW standby / 660 kW prime · Natural Gas / LPG · Liquid-cooled

800 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 40L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-4160V.

Standby power
800 kW / 660 kW prime
Voltage options
120/208V, 240V, 277/480V, 347/600V, 4160V
Frequency / Phase
60 Hz · 3-phase
Engine
PSI 40L · 39.2L
EPA / Emissions
EPA Stationary Spark Ignition
Alternator
Stamford S6L1D-C
large-commercialdata-centerhospital-non-criticalschool-campusmulti-family-largelight-industrial

Overview#

The Blue Star NG800-01 is an 800-kilowatt natural gas / LP standby generator built on the PSI 40-liter V12 platform — the largest engine in Blue Star's current gaseous lineup below the PSI 52L-based models. It is rated 800 kWe standby on natural gas and 475 kWe on LP at 60 Hz / 1800 RPM. Three-phase only (208V, 240V, 480V, 600V, and 4160V). UL 2200 listing applies through 600VAC only — the 4160V configuration is not UL-listed.

The PSI 40L V12#

The PSI 40L is a 39.2-liter (2,392 cu in) V12 turbocharged-aftercooled spark-ignition engine:

Fuel pressure requirement#

Important: The NG800-01 requires 30 in. water column inlet fuel pressure — nearly 3× the 11 in. WC required by smaller Blue Star gaseous units. Site gas infrastructure, meter sets, and regulators must be sized to deliver 30 in. WC under sustained full-load conditions. This is a critical specification check before installation.

4160V option and UL listing#

The NG800-01 is the first model in Blue Star's gaseous lineup to offer 4160V three-phase output:

VoltagePhaseAlternatorConnection
120/208V3Stamford S6L1D-D12-lead WYE
240V3Stamford S6L1D-D12-lead DELTA
277/480V3Stamford S6L1D-C12-lead WYE
347/600V3Stamford S6L1D-C4-lead WYE
4160V3Stamford MVWI734E6-lead WYE

All configurations carry 125°C standby temperature rise and ±0.5% voltage regulation.

UL listing: UL 2200, cUL, and CSA certifications apply through 600VAC only. The 4160V configuration is not UL-listed. Confirm AHJ requirements before specifying 4160V output.

LP output note#

The NG800-01's LP standby rating of 475 kWe is 59% of the 800 kWe NG rating — lower LP-to-NG parity than smaller PSI 32L-based models. For sites where LP fuel must carry substantial load, verify the 475 kWe LP rating against the load profile.

When to spec the NG800-01#

Our service experience#

The PSI 40L V12 is a large and specialized platform. Service intervals on a 12-cylinder engine with 38.6 gal of oil are significant — plan for proportionally larger fluid changes and a full 12-cylinder spark plug and ignition coil schedule. Fuel delivery infrastructure (30 in. WC sustained under load) must be verified before commissioning.

Engineering specifications

Physical

Length
210 in
Width
96 in
Height
103 in
Dry weight
16,975 lb

Acoustic

Sound @ 7m, full load
90 dBA
Enclosure
Open

Fuel system & runtime

NG required pressure
30 in WC

Thermal & ventilation

Heat to coolant
2,621,040 BTU/hr
Heat radiated
961,620 BTU/hr
Exhaust flow
5,420 CFM
Exhaust temp
1238 °F
Combustion air
1,676 CFM
Ventilation air
52,000 CFM

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Blue Star NG800-01

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Blue Star NG800-01

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

8,400,000 BTU/hr8400.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Service intervals

Manufacturer-recommended intervals for the Blue Star NG800-01 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 4000 hours
Air filter
Every 1000 hours
Spark plugs
Every 1500 hours
Major overhaul
15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Turbocharger(s)Significant power loss, heavy exhaust smoke12,000+severe
Ignition system (multi-cylinder)Multiple misfires, output derating1,500+moderate
Charge air coolerReduced output, elevated intake temperatures10,000+moderate

Frequently Asked Questions

What is the standby rating of the NG800-01?
The Blue Star NG800-01 is rated 800 kWe standby on natural gas and 475 kWe standby on LP at 60 Hz / 1800 RPM. The LP-to-NG ratio at standby is 59% — notably lower than smaller models in the gaseous lineup. Deration is: 1.5% per 5°F above 77°F inlet air temperature and 4.5% per 1,000 ft above 1,200 ft altitude.
What engine is in the NG800-01?
The PSI 40L — a 39.2-liter (2,392 cu in) V12 turbocharged-aftercooled spark-ignition engine producing 1,234 bHp (921 kWm) at 1800 RPM standby. The 40L uses a longer stroke (7.28 in) than the 32L's square bore-stroke profile (5.91×5.91 in), with the same bore (5.91 in). The oil system is 38.6 gal and the cooling system holds 45.0 gal system coolant.
Is the 4160V configuration UL-listed?
No. The NG800-01 carries UL 2200 listing, cUL listing, and CSA certification through 600VAC only. The 4160V configuration (Stamford MVWI734E alternator) is not UL-listed. Specify accordingly for projects with UL listing requirements — confirm with the AHJ whether 4160V distribution requires a listed unit.
What is the fuel inlet pressure requirement for the NG800-01?
The NG800-01 requires 30 in. water column fuel inlet pressure — significantly higher than smaller Blue Star gaseous units (11 in. WC). Verify the site gas infrastructure can sustain 30 in. WC under full-load demand conditions before specifying.
Is the NG800-01 available in single-phase?
No. The NG800-01 is three-phase only in 208V, 240V, 480V, 600V, and 4160V configurations.

Compatible equipment

Similar models

Blue Star Power Systems

New

Blue Star NG650-01

650 kW standby · Natural Gas / LPG · Liquid-cooled

650 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG800-01P

800 kW standby · Natural Gas / LPG · Liquid-cooled

660 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 40L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-4160V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG650-01P

650 kW standby · Natural Gas / LPG · Liquid-cooled

550 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG600-01

600 kW standby · Natural Gas / LPG · Liquid-cooled

600 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG600-01P

600 kW standby · Natural Gas / LPG · Liquid-cooled

540 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG500-01

500 kW standby · Natural Gas / LPG · Liquid-cooled

500 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center