Overview#
The Cat G3516H is a high-performance natural gas generator set delivering continuous power for cogeneration, distributed generation, and baseload industrial applications. The engine features a Separate Circuit Aftercooled (SCAC) air system, ADEM4 electronic controls (listed as ADEM4 W/ IM), and an air-fuel ratio control system designed for low-emission operation at 1.0 g/bhp-hr NOx.
Available in voltages from 480V through 13,800V medium voltage, the G3516H is designed for continuous duty with high electrical efficiency. The engine supports fuel methane numbers down to 50 (with derating) and operates with a low-pressure fuel system (1.5-5.0 psig).
Key specifications#
- Continuous power: 1,982 ekW (2,477 kVA) at 0.8 power factor (continuous rating) at 1,500 rpm (50 Hz), per the cited sheet
- Engine: Cat G3516H
- Compression ratio: 12.1:1
- Aspiration: Turbocharged with SCAC (Separate Circuit Aftercooling)
- Fuel: Natural gas, low pressure with air-fuel ratio control
- NOx emissions: 1.0 g/bhp-hr
- Generator efficiency: 96.3% at full load
- Genset efficiency: 44.7% at full load (ISO 3046/1)
- Total efficiency (electrical + thermal): 86.4% at full load
Fuel consumption#
At continuous rated load (1,982 ekW continuous) at 1,500 rpm (50 Hz), per the cited sheet:
- 100% load: 292 scfm, 7,725 Btu/ekW-hr (ISO)
- 75% load: 223 scfm, 7,889 Btu/ekW-hr
- 50% load: 157 scfm, 8,300 Btu/ekW-hr
Acoustic data#
Sound power levels at full load (1,982 ekW) at 1,500 rpm (50 Hz), per the cited sheet:
- Mechanical: 122.8 dB(A) overall
- Exhaust: 125.5 dB(A) overall
Sound data measured per ISO 3747 (mechanical) and ISO 6798 (exhaust). Actual installed levels will vary based on enclosure, site acoustics, and cooling system configuration.
Cogeneration capability#
The G3516H achieves 86.4% total efficiency when heat recovery is included, making it a candidate platform for combined heat and power (CHP) installations. Recoverable heat sources include jacket water, lube oil, first-stage aftercooler, and exhaust (to 248 deg F).
Our service experience#
The G3516H is a sophisticated gas engine requiring precise fuel system management and aftercooler temperature control. The SCAC inlet temperature must be maintained within tight tolerances to prevent detonation. Air-fuel ratio control requires up to 180 seconds to stabilize after load steps. Regular spark plug inspection, valve adjustment, and ignition timing verification are critical to maintaining performance and emissions compliance.
At 1,982 ekW of continuous output (at 1,500 rpm / 50 Hz, per the cited sheet), this is a project-grade installation. The engine requires shop-level tooling for valve train, fuel system, and turbocharger service — field service van work is not appropriate at this scale.
For CHP applications, heat recovery system integration must be commissioned concurrently with the generator. The exhaust heat exchanger, jacket water heat exchanger, and lube oil cooler all carry meaningful heat recovery potential — engage a mechanical engineer to size the heat recovery loop before finalizing the site design.
Frequently Asked Questions#
What is the continuous power rating of the Cat G3516H? The Cat G3516H is rated 1,982 ekW (2,477 kVA) at 0.8 power factor for continuous duty at 1,500 rpm (50 Hz), per the cited sheet. The unit is designed for continuous-duty applications including cogeneration and baseload distributed generation — not emergency standby-only service.
What voltages are available on the Cat G3516H? The data sheet gives a voltage range of 480 V to 13,800 V. The medium- and high-voltage end of that range suits CHP and industrial paralleling array installations.
What NOx emissions level does the G3516H achieve? 1.0 g/bhp-hr NOx at the engine exhaust flange, prior to any aftertreatment. The engine is listed with ADEM4 controls, air-fuel ratio control and SCAC aftercooling. An oxidation catalyst may be required to meet CO or HC requirements.
Is the Cat G3516H suitable for cogeneration? Yes. The G3516H achieves 86.4% total efficiency when heat recovery is included. Recoverable heat sources include jacket water, lube oil, first-stage aftercooler, and exhaust to 248 degrees F, making it a candidate platform for combined heat and power (CHP) installations at hospitals, campuses, and industrial plants.
What fuel supply does the G3516H require? Natural gas at low pressure (1.5–5.0 psig). The engine supports fuel methane numbers down to 50 (with derating). At 100% continuous load at 1,500 rpm (50 Hz) the sheet lists a fuel flow of 292 scfm (60F, 14.7 psia) — a utility gas service engineering review is required before installation.
Confirm exact intervals with the OEM service manual — the G3516H operating profile (load factor, fuel quality) affects actual interval recommendations.