Kohler · REOZ Series (Diesel Industrial Large)

Kohler 2000REOZMD

2000 kW standby / 1820 kW prime · Diesel · Liquid-cooled

2000 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.

Kohler Kohler 2000REOZMD generator — specifications and details
Standby power
2000 kW / 1820 kW prime
Voltage options
277/480V, 4160V, 12470V, 13200V, 13800V
Frequency / Phase
60 Hz · 3-phase
Engine
Mitsubishi S16R-Y2PTAW2-1 · 65.4L
EPA / Emissions
Tier 2
Alternator
Kohler 7M4054

Overview#

The Kohler 2000REOZMD is a 2,000-kilowatt standby (1,820 kW prime) diesel generator powered by a Mitsubishi S16R-Y2PTAW2-1 — a 65.4 L, 16-cylinder V-configuration turbocharged diesel at 1800 RPM. At 2 MW standby, this is the highest-rated single-unit generator in Kohler's standard REOZMD series, representing the practical upper limit of a single Mitsubishi S16R installation before moving to multi-unit paralleling arrays.

The 2000REOZMD is EPA Tier 2 certified for stationary emergency applications, UL 2200 listed, and meets NFPA 110 Level 1 requirements. It supports both 480V low-voltage and medium-voltage outputs (4,160V; 12,470V; 13,200V; 13,800V), making it suitable for direct medium-voltage distribution integration. Deployments include hyperscale data centers, large hospital campuses, university systems, and critical infrastructure where a single 2 MW source provides N+1 coverage for multiple sub-feeds.

The same Mitsubishi S16R-Y2PTAW2-1 engine platform is shared with the 1750REOZMD, but the 2000REOZMD uses a higher-output alternator (7M4054 vs. 7M4052) tuned for the 2 MW rating, with correspondingly higher fuel consumption (160.1 gph vs. 141.6 gph at full standby load).

Specifications#

SpecValue
Standby Power2,000 kW
Prime Power1,820 kW
Voltage options277/480V, 4,160V, 12,470V, 13,200V, 13,800V
Frequency60 Hz
EngineMitsubishi S16R-Y2PTAW2-1
Engine type4-cycle turbocharged
Cylinders16 V-configuration
Displacement65.4 L (3,989 cu. in.)
Compression ratio14.0:1
Rated RPM1,800
AlternatorKohler 7M4054
FuelDiesel (#2 / HVO / RD)
CoolingLiquid (radiator)
Emissions tierEPA Tier 2 stationary emergency
Fuel consumption (100% standby load)160.1 gph
Fuel consumption (75% standby load)116.8 gph

Service & Maintenance#

ServiceInterval
Oil changeEvery 500 hours or 12 months
Fuel filter replacementEvery 500 hours
Air filter replacementEvery 1,000 hours
Coolant flushEvery 6,000 hours or 5 years
Load bank testAnnually (NFPA 110 requirement)
Major overhaulEvery 20,000 hours

The Mitsubishi S16R-Y2PTAW2-1 uses four secondary cartridge oil filters. Oil pan capacity is 200 L (211 qt) dry, 230 L (243 qt) with filter change. Jacket water capacity is 170 L (44.9 gal); total radiator system capacity is 367 L (96.9 gal). The high-ambient radiator configuration supports operation up to 50°C (122°F). Four 1,150 CCA batteries power dual 24V starter motors.

Common Failure Modes#

Fuel injection pump and injector wear is the primary concern at high operating hours, typically around 10,000 hours on the S16R platform. At 2,000 kW, the fuel system delivers up to 660 L/hr (174 gph) maximum flow; maintaining clean fuel quality is critical to injector life. Quarterly fuel polishing and biocide treatment are standard for all NFPA 110 Level 1 accounts at this power level.

Turbocharger degradation at approximately 12,000 hours is an expected maintenance milestone. The exhaust flow at rated load is 544 m³/min (19,209 cfm) at 526°C (979°F) — high thermal cycling accelerates turbocharger bearing wear. Turbocharger oil supply and return lines should be inspected at every major service.

Cooling system components require attention given the large system volumes (367 L radiator, dual intercooler circuit). The charge cooler circuit (920 L/min flow) must be maintained separately from the jacket water circuit. Annual coolant testing and hose condition inspections are required.

Starting battery condition — four 1,150 CCA batteries power dual 24V starters. At 2,000 kW / 16 cylinders, engine cranking demands are high. Individual battery health testing at each annual inspection is non-negotiable.

Our service experience#

OnPoint Generators provides installation, maintenance, load bank testing, and emergency service for Kohler industrial generators throughout Northern California and the Central Valley. The 2000REOZMD is the largest single-unit generator we regularly service. At 2 MW, full-load testing requires 2 MW+ load banks and careful coordination with facility electrical teams. We provide factory-level Mitsubishi S16R service capabilities including fuel system calibration, turbocharger service, and major overhaul planning for accounts that need lifecycle management on these assets.

FAQ#

Q: What engine powers the Kohler 2000REOZMD? A: The 2000REOZMD uses a Mitsubishi S16R-Y2PTAW2-1 — a 65.4 L, 16-cylinder V-configuration turbocharged diesel at 1800 RPM, EPA Tier 2 certified for stationary emergency standby.

Q: What is the standby power rating of the 2000REOZMD? A: 2,000 kW standby and 1,820 kW prime at 0.8 power factor per Kohler spec sheet G5-369.

Q: How does the 2000REOZMD compare to the 1750REOZMD? A: Both use the same Mitsubishi S16R-Y2PTAW2-1 engine. The 2000REOZMD uses a higher-output alternator (7M4054 vs. 7M4052) and produces 220 kW more standby capacity, consuming approximately 18.5 more gph at full load. Physical size and service intervals are identical.

Q: Does OnPoint service the Kohler 2000REOZMD? A: Yes. OnPoint Generators provides maintenance, repair, and full-load bank testing for Kohler 2000REOZMD generators throughout Northern California.

Engineering specifications

Physical

Wet weight
34,000 lb

Fuel system & runtime

Fuel use @ full load
160.1 GPH
Fuel use @ 75% load
116.8 GPH
Fuel use @ 50% load
79 GPH

Photos

Kohler 2000REOZMD — product photo

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Kohler 2000REOZMD

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Kohler 2000REOZMD

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

1.6 hours(0.1 days)

Fuel consumption ≈ 123.51 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Kohler 2000REOZMD under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel injection pump / injectorsHard starting, black smoke, uneven cylinder loading10,000+moderate
TurbochargerPower loss, excessive exhaust smoke, oil carryover12,000+moderate
Cooling system (hoses / thermostat)Overtemperature fault, coolant loss10,000+minor
Battery (starting)Slow crank, failed exercise8,760+minor

Frequently Asked Questions

What engine powers the Kohler 2000REOZMD?
The 2000REOZMD uses a Mitsubishi diesel engine running at 1800 RPM (model S16R-Y2PTAW2-1).
What is the standby power rating of the 2000REOZMD?
The 2000REOZMD is rated at 2000 kW standby and 1820 kW prime per Kohler published specifications.
Does OnPoint service the Kohler 2000REOZMD?
Yes. OnPoint Generators provides maintenance, repair, and load bank testing for Kohler REOZ diesel generators throughout Northern California, including the 2000 kW class.

Compatible equipment

More in the REOZ Series (Diesel Industrial Large)

Kohler REOZ large industrial diesel gensets from 515 to 2500 kW with Mitsubishi, MTU, and Volvo engines.

Similar models

Kohler Kohler 1750REOZMD 1.8 MW liquid-cooled standby generator

Kohler

Kohler 1750REOZMD

1780 kW industrial diesel -- Mitsubishi S16R-Y2PTAW2-1 with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.

1.8 MW standby · Diesel · Liquid-cooled

1780 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.

Tier 23-phasedata-centerhealthcare
Kohler Kohler 2500REOZDC 2.5 MW liquid-cooled standby generator

Kohler

Kohler 2500REOZDC

2500 kW industrial diesel -- Detroit Diesel/MTU 16V4000G83L with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.

2.5 MW standby · Diesel · Liquid-cooled

2500 kW diesel industrial generator powered by Detroit Diesel/MTU. Mission-critical standby for data centers, hospitals, and large commercial facilities.

Tier 23-phasedata-centerhealthcare
Kohler Kohler KD2000 2 MW liquid-cooled standby generator

Kohler

Kohler KD2000

2000 kW KD Series -- Kohler KD62V12 with sub-3% THD and PM pilot exciter. Hurricane-rated enclosures available.

2 MW standby · Diesel · Liquid-cooled

2000 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and mission-critical infrastructure requiring multi-megawatt backup.

Tier 23-phasedata-centerhealthcare