REOZ Series (Diesel Industrial Large)

Kohler REOZ large industrial diesel gensets from 515 to 2500 kW with Mitsubishi, MTU, and Volvo engines.

5152500 kW12 modelsdiesel

Series Overview#

The Kohler REOZ Series (Diesel Industrial Large) covers 12 models from 515 to 2500 kW standby, filling the power range between Kohler's commercial REOZ line and the proprietary-engine KD Series. Where the KD Series uses Kohler-built engines throughout, the large REOZ Series draws on three industry-leading engine OEMs depending on power class: Volvo, Mitsubishi, and Detroit Diesel/MTU. All 12 models are EPA Tier 2 certified for stationary emergency standby applications.

The series organizes into three distinct engine families. At the lower end — 515 to 600 kW standby — the REOZVB designation indicates Volvo TAD-series turbocharged inline-6 engines. The Volvo TAD1641GE-B, TAD1642GE-B, and TWD1643GE (or TWD1644GE) are purpose-built industrial genset engines widely supported in North America. Moving up from 750 kW through 2000 kW, the REOZMD designation indicates Mitsubishi heavy-duty multi-cylinder engines: the S12A2-Y2PTAW-2 at 750 kW and the S12R and S16R families (65.4 L, 16-cylinder V-configuration) at 1250 kW through 2000 kW. At 2500 kW, the REOZDC stands alone — powered by a Detroit Diesel/MTU 16V4000G83L, a 76.3-liter V16 producing up to 2,740 kW maximum shaft power.

Voltage flexibility is a distinguishing capability of this series. While the Volvo-powered 500–600 kW models support 277/480V and 120/208V, the Mitsubishi-powered models from 750 kW upward add medium-voltage options: 4160V, 12470V, 13200V, and 13800V. This allows large facilities to receive generator output at distribution voltage, eliminating the step-up transformer that would otherwise be required between a low-voltage generator and a medium-voltage switchgear bus. The 2500REOZDC supports the same medium-voltage range at the 2.5 MW level.

The ROZMC variants (1250ROZMC, 1600ROZMC, 2000ROZMC) are non-EPA-certified models intended for export or non-regulated markets, available in both 50 Hz (1500 RPM) and 60 Hz (1800 RPM) configurations. Buyers specifying domestic US installations should confirm the REOZMD designation, which carries the EPA Tier 2 certification required for permitted standby applications.

How to Choose#

500–600 kW: REOZVB platform (Volvo). Choose between the 500REOZVC (515 kW standby), 550REOZVB (550 kW standby), and 600REOZVB (600 kW standby). All three use Volvo inline-6 engines and support 277/480V and 120/208V. If your facility load calculation lands in this range after demand factor analysis, the 550REOZVB provides a practical mid-step before transitioning to the Mitsubishi platform at 750 kW.

750 kW: 750REOZMD (Mitsubishi S12A2). This is the entry point for medium-voltage output capability and the Mitsubishi platform. If your facility distribution is at 4160V or above, the 750REOZMD is the lowest-output option that can deliver at medium voltage.

1250–2000 kW: REOZMD platform (Mitsubishi S12R and S16R). This range covers the most common single-unit configurations for large data centers and hospital campuses. The 1250REOZMD (1280 kW standby), 1600REOZMD (1600 kW standby), 1750REOZMD (1780 kW standby), and 2000REOZMD (2000 kW standby) all use Mitsubishi S-series engines with full medium-voltage support. The 2000REOZMD represents the practical upper limit of the Mitsubishi S16R platform as a single-unit installation.

Export variants: ROZMC. The 1250ROZMC, 1600ROZMC, and 2000ROZMC are rated for 50 Hz or 60 Hz operation and are not EPA-certified. Specify these only for international or non-regulated applications.

2500 kW: 2500REOZDC (Detroit Diesel/MTU 16V4000). For applications requiring a single 2.5 MW unit — hyperscale data centers, major hospital campuses, large wastewater treatment plants — the REOZDC uses a fundamentally different engine architecture from the rest of the series. Parts and service support for the MTU 16V4000 requires MTU-trained technicians; factor this into your service contract planning.

Common Applications#

Service & Maintenance#

All 12 models in the large REOZ Series share consistent service intervals: oil and fuel filter changes every 500 hours or 12 months, air filter service every 1,000 hours, and coolant changes at 6,000 hours. These intervals apply across the Volvo, Mitsubishi, and MTU engine platforms.

Starting battery failure is the most widely observed failure mode across this fleet, present on all 12 models. For large industrial generators that cycle only during monthly exercises and actual outages, battery state-of-health checks should be included in every semi-annual inspection. A battery that passes a visual check can still fail to deliver sufficient cold-cranking current when the unit has been sitting.

Fuel injection system issues are the next most significant failure category. The Mitsubishi-powered REOZMD models (8 of the 12 total) show fuel injection pump and injector faults as a common failure mode at approximately 10,000 hours — symptoms include hard starting, black smoke, and uneven cylinder loading. Turbocharger wear typically appears around 12,000 hours in the Mitsubishi platform and 15,000 hours in the MTU 16V4000.

For the 2500REOZDC (MTU-powered), charge air cooling system inspections are important — reduced output and intake temperature alarms are common failure indicators around 12,000 hours. The MTU 16V4000 requires MTU-certified service personnel for major maintenance events; plan service contracts accordingly before commissioning.

All REOZ Series (Diesel Industrial Large) Models

ModelStandby kWPrime kWVoltageEngineEmissionsFuel
Kohler 500REOZVC515460277/480V, 120/208VVolvo TAD1641GE-BTier 2diesel
Kohler 550REOZVB550500277/480V, 120/208VVolvo TAD1642GE-BTier 2diesel
Kohler 600REOZVB600555277/480V, 120/208VVolvo TWD1643GETier 2diesel
Kohler 750REOZMD760690277/480V, 4160V, 12470VMitsubishi S12A2-Y2PTAW-2Tier 2diesel
Kohler 1250ROZMC11201016277/480V, 4160V, 12470VMitsubishi See spec sheetdiesel
Kohler 1250REOZMD12801160277/480V, 4160V, 12470VMitsubishi S12R-Y2PTAW-1Tier 2diesel
Kohler 1600ROZMC15601416277/480V, 4160V, 12470VMitsubishi See spec sheetdiesel
Kohler 1600REOZMD16001450277/480V, 4160V, 12470VMitsubishi S16R-Y2PTAW-1Tier 2diesel
Kohler 2000ROZMC17601600277/480V, 4160V, 12470VMitsubishi See spec sheetdiesel
Kohler 1750REOZMD17801650277/480V, 4160V, 12470VMitsubishi S16R-Y2PTAW2-1Tier 2diesel
Kohler 2000REOZMD20001820277/480V, 4160V, 12470VMitsubishi S16R-Y2PTAW2-1Tier 2diesel
Kohler 2500REOZDC2500277/480V, 4160V, 12470VDetroit Diesel/MTU 16V4000G83LTier 2diesel

Frequently Asked Questions

What is the difference between a REOZMD and a ROZMC model?
The REOZMD designation indicates EPA Tier 2 certification for stationary emergency use in the US domestic market. The ROZMC designation is a non-EPA-certified variant designed for export and non-regulated markets, available in both 50 Hz (1500 RPM) and 60 Hz (1800 RPM) configurations. For domestic US installations, specify REOZMD.
What engine platforms does the large REOZ Series use?
The series uses three engine OEMs depending on power class. The 500–600 kW range (REOZVB) uses Volvo TAD-series inline-6 engines. The 750 kW through 2000 kW range (REOZMD) uses Mitsubishi heavy-duty engines — S12A2 at 750 kW, S12R at 1250 kW, and S16R at 1600–2000 kW. The 2500 kW flagship (REOZDC) uses a Detroit Diesel/MTU 16V4000G83L V16.
Does this series support medium voltage output?
Yes. Models from the 750REOZMD upward support medium-voltage configurations including 4160V, 12470V, 13200V, and 13800V in addition to 277/480V. This is critical for large facility installations that distribute power at medium voltage without an additional step-up transformer.
What are the service intervals for the REOZ large industrial series?
All 12 models share consistent intervals: oil and fuel filter changes at 500 hours or 12 months, air filter at 1,000 hours, and coolant at 6,000 hours. Units in this power class require medium-voltage-qualified service personnel and large-capacity load bank testing equipment.
Can REOZ large industrial units be paralleled?
Yes. These units are designed for large-scale paralleling arrays. The 1750REOZMD and 2000REOZMD are commonly deployed in data center campuses where multiple 2 MW units operate in parallel with N+1 redundancy.