Series Overview#
The MTU Series 4000 Diesel from Rolls-Royce spans six models from 1,250 to 2,500 kilowatts of standby capacity: a 57.2-liter V12 for the three lower-output models and a 76.3-liter V16 for the three higher-output models.
The six models divide into two sublines: the 12V4000 platform (DS1250, DS1500, DS1750) rated 1,250–1,750 kW standby, and the 16V4000 platform (DS2000, DS2250, DS2500) rated 2,000–2,500 kW standby.
All six cited data sheets list three-phase output at 60 Hz, EPA Tier 2 certification and SCAQMD approval, with voltages from 380V through 13,800V. The medium-voltage options are 4,160V, 12,470V, 13,200V and 13,800V.
How to Choose#
The Series 4000 selection is organized around the engine platform boundary:
12V4000 subline (V12, 57.2L):
- DS1250 (1,250 kW standby): the lowest rating in the Series 4000.
- DS1500 (1,500 kW standby): standby rating with a 50 °C radiator ambient capacity.
- DS1750 (1,750 kW standby): the highest rating of the three V12 sheets.
16V4000 subline (V16, 76.3L):
- DS2000 (2,000 kW standby): the 16V4000G74S engine, 2,280 kWm.
- DS2250 (2,250 kW standby): the 16V4000G84S engine, 2,500 kWm on the 40 °C sheet.
- DS2500 (2,500 kW standby): the 16V4000G94S engine, 2,740 kWm, the highest rating of the six sheets.
For voltage configuration, medium-voltage options (4,160V and above) require coordination with the electrical engineer.
Common Applications#
- Large hospitals: NFPA 110 compatible controls; the data sheets state that rated load is accepted in one step per NFPA 110.
- High-rise and large campuses: Buildings and campuses with central plant electrical distribution where a single generator position must carry the full facility standby load.
Service & Maintenance#
The cited data sheets list a 24 VDC starting system with group 8D batteries and a system coolant capacity of 154 gallons (583 L) on the 12V4000 models.
Application Guidance#
The MTU Series 4000 covers single-unit standby at 1,250–2,500 kW. This series is not appropriate when the standby requirement is below 1,250 kW — the MTU Series 2000 DS1000 covers 1,000 kW standby and the MTU 12V1600 Series covers 750–900 kW. Where Tier 4 Final compliance is required, the Series 4000's Tier 2 certification will not meet that standard; confirm with the AHJ whether emergency standby use is exempt.