Kohler · REOZ Series (Diesel Industrial Large)

Kohler 1600REOZMD

1600 kW standby / 1450 kW prime · Diesel · Liquid-cooled

1600 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.

Kohler Kohler 1600REOZMD generator — specifications and details
Standby power
1600 kW / 1450 kW prime
Voltage options
277/480V, 4160V, 12470V, 13200V, 13800V
Frequency / Phase
60 Hz · 3-phase
Engine
Mitsubishi S16R-Y2PTAW-1 · 65.4L
EPA / Emissions
Tier 2
Alternator
Kohler 7M4050

Overview#

The Kohler 1600REOZMD is a 1600-kilowatt standby (2000 kW prime) diesel generator powered by a Mitsubishi engine at 1800 RPM. This industrial-class unit serves mission-critical standby applications including data centers, hospitals, and large commercial facilities.

Our service experience#

OnPoint Generators services Kohler REOZ diesel generators throughout Northern California. Units in this class require specialized service capabilities including medium-voltage expertise and large-capacity load bank testing.

Engineering specifications

Physical

Length
271.5 in
Width
87.9 in
Height
102 in
Wet weight
31,600 lb

Fuel system & runtime

Fuel use @ full load
128.6 GPH
Fuel use @ 75% load
93.9 GPH

Photos

Kohler 1600REOZMD — product photo

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Kohler 1600REOZMD

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Kohler 1600REOZMD

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

2.0 hours(0.1 days)

Fuel consumption ≈ 99.21 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Kohler 1600REOZMD under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel injection pump / injectorsHard starting, black smoke, uneven cylinder loading10,000+moderate
TurbochargerPower loss, excessive exhaust smoke, oil carryover12,000+moderate
Cooling system (hoses / thermostat)Overtemperature fault, coolant loss10,000+minor
Battery (starting)Slow crank, failed exercise8,760+minor

Frequently Asked Questions

What engine powers the Kohler 1600REOZMD?
The 1600REOZMD uses a Mitsubishi diesel engine running at 1800 RPM (model S16R-Y2PTAW-1).
What is the standby power rating of the 1600REOZMD?
The 1600REOZMD is rated at 1600 kW standby and 2000 kW prime per Kohler published specifications.
Does OnPoint service the Kohler 1600REOZMD?
Yes. OnPoint Generators provides maintenance, repair, and load bank testing for Kohler REOZ diesel generators throughout Northern California, including the 1600 kW class.

Compatible equipment

More in the REOZ Series (Diesel Industrial Large)

Kohler REOZ large industrial diesel gensets from 515 to 2500 kW with Mitsubishi, MTU, and Volvo engines.

Similar models

Kohler Kohler 1600ROZMC 1.6 MW liquid-cooled standby generator

Kohler

Kohler 1600ROZMC

1560 kW industrial diesel -- Mitsubishi S16R V16 turbo with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.

1.6 MW standby · Diesel · Liquid-cooled

1560 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.

3-phasedata-centerhealthcare
Kohler Kohler 2000ROZMC 1.8 MW liquid-cooled standby generator

Kohler

Kohler 2000ROZMC

1760 kW industrial diesel -- Mitsubishi S16R V16 turbo with Decision-Maker 6000 paralleling. Sub-3% THD, UL 2200, NFPA 110 Level 1.

1.8 MW standby · Diesel · Liquid-cooled

1760 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.

3-phasedata-centerhealthcare
Kohler Kohler KD1600 1.6 MW liquid-cooled standby generator

Kohler

Kohler KD1600

Megawatt-class KD at 1600 kW -- Kohler KD45V20, sub-3% THD, Decision-Maker 6000 paralleling controller.

1.6 MW standby · Diesel · Liquid-cooled

1600 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and heavy industrial applications.

Tier 23-phasedata-centerhealthcare

Need service or parts for the Kohler 1600REOZMD?

We service every major OEM and stock genuine parts for the most common models.