Overview#
The Kohler 550REOZVB is a 550-kilowatt standby (500 kW prime) diesel generator powered by a Volvo TAD1642GE-B — a 16.12 L turbocharged charge-air-cooled inline-6 at 1800 RPM.
At 550/500 kW standby/prime, this unit targets large commercial and industrial standby applications including regional hospitals, Tier II/III data centers, large manufacturing plants, and campus distribution systems. The REOZVB series carries EPA Tier 2 certification for stationary emergency applications and meets NFPA 110 Level 1 when equipped with the appropriate accessories.
The 550REOZVB is approved for Hydrotreated Vegetable Oil (HVO) / Renewable Diesel compliant with EN15940/ASTM D975, making it an option for organizations with sustainability mandates that require lower-carbon standby power.
Specifications#
| Spec | Value |
|---|---|
| Standby Power | 550 kW |
| Prime Power | 500 kW |
| Voltage (primary) | 277/480V three-phase |
| Frequency | 60 Hz |
| Engine | Volvo TAD1642GE-B |
| Engine type | 4-cycle turbocharged, charge air-cooled |
| Cylinders | 6 inline |
| Displacement | 16.12 L (984 cu. in.) |
| Compression ratio | 17:1 |
| Rated RPM | 1800 |
| Alternator | Kohler 5M4028 |
| Fuel | Diesel (#2 / HVO / RD) |
| Cooling | Liquid (radiator) |
| Emissions tier | EPA Tier 2 stationary emergency |
| Fuel consumption (100% standby load) | 39.9 gph |
| Fuel consumption (75% standby load) | 28.8 gph |
| Overall dimensions | 166.5" x 72" x 77.2" |
Service & Maintenance#
The Volvo TAD1642GE-B has an oil pan capacity of 42.0 L (44.4 qt) dry and 48.1 L (50.8 qt) with filter. It uses three cartridge oil filters and a water-cooled oil cooling system.
Common Failure Modes#
Fuel quality and degradation is the primary service concern for standby generators in this class. Fuel polishing and biocide treatment are standard for NFPA 110 Level 1 facilities.
The Volvo TAD1642GE-B is highly turbocharged (compression ratio 17:1), making turbocharger condition a critical service point. Symptoms include power loss, elevated exhaust temperature, and oil carryover into the intake. Volvo's commercial service network provides strong parts support in Northern California.
The charge air cooler on the Volvo platform is accessible for cleaning and inspection as part of extended service intervals.
The 550REOZVB uses two 925 CCA (12V) batteries in 24V configuration with an 80A charging alternator.
Our service experience#
OnPoint Generators provides installation, maintenance, load bank testing, and emergency service for Kohler industrial generators throughout Northern California and the Central Valley. The Volvo TAD1642 platform is well-supported through Volvo's regional distribution network.
FAQ#
Q: What engine powers the Kohler 550REOZVB? A: The 550REOZVB uses a Volvo TAD1642GE-B — a 16.12 L, 6-cylinder turbocharged charge-air-cooled diesel at 1800 RPM, EPA Tier 2 certified for stationary emergency standby.
Q: What is the standby power rating of the 550REOZVB? A: 550 kW standby and 500 kW prime at 0.8 power factor per Kohler spec sheet G5-395.
Q: How does the 550REOZVB compare to the 500REOZJC? It targets heavier-duty and higher-runtime installations.
Q: Does OnPoint service the Kohler 550REOZVB? A: Yes. OnPoint Generators provides maintenance, repair, and load bank testing for Kohler REOZVB diesel generators throughout Northern California, including the 550 kW class.