Kohler · REOZ Series (Diesel Commercial Standby)

Kohler 500REOZJB

510 kW standby · Diesel · Liquid-cooled

510 kW diesel commercial/industrial standby generator powered by John Deere. Suitable for hospitals, data centers, and large commercial complexes.

Kohler Kohler 500REOZJB generator — specifications and details
Standby power
510 kW
Voltage options
277/480V, 120/208V
Frequency / Phase
60 Hz · 3-phase
Engine
John Deere 6135HFG75 · 13.5L
EPA / Emissions
Tier 2
Alternator
Kohler 5M4024

Overview#

The Kohler 500REOZJB is a 510-kilowatt diesel generator powered by a John Deere engine at 1800 RPM. This unit serves large commercial and industrial standby applications including hospitals, data centers, and manufacturing facilities.

Our service experience#

OnPoint Generators services Kohler REOZ diesel generators throughout Northern California. We service units in this class with annual NFPA 110 maintenance, semi-annual inspections, and load bank testing up to full rated capacity.

Engineering specifications

Physical

Length
142.9 in
Width
56.1 in
Height
78.5 in
Wet weight
8,560 lb

Fuel system & runtime

Fuel use @ full load
35.5 GPH
Fuel use @ 75% load
27.6 GPH

Photos

Kohler 500REOZJB — product photo

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Kohler 500REOZJB

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Kohler 500REOZJB

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

7.3 hours(0.3 days)

Fuel consumption ≈ 27.39 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Kohler 500REOZJB under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 3000 hours
Air filter
Every 500 hours
Fuel filter
Every 500 hours
Major overhaul
15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationInjector fouling, hard starting, filter clogging4,380+moderate
TurbochargerPower loss, excessive smoke under load12,000+moderate
Battery (starting)Failed to start, slow crank8,760+minor

Frequently Asked Questions

What engine powers the Kohler 500REOZJB?
The 500REOZJB uses a John Deere diesel engine running at 1800 RPM (model 6135HFG75).
What is the standby power rating of the 500REOZJB?
The 500REOZJB is rated at 510 kW standby per Kohler published specifications.
Does OnPoint service the Kohler 500REOZJB?
Yes. OnPoint Generators provides maintenance, repair, and load bank testing for Kohler REOZ diesel generators throughout Northern California, including the 510 kW class.

Compatible equipment

More in the REOZ Series (Diesel Commercial Standby)

Kohler's diesel commercial standby series — 10 to 510 kW, John Deere and Kohler engines, built for life-safety loads.

Similar models

Kohler Kohler 500REOZJ 500 kW liquid-cooled standby generator

Kohler

Kohler 500REOZJ

500 kW diesel standby -- John Deere 6135HFG75, sub-3% THD. Decision-Maker controller for load management and paralleling.

500 kW standby · Diesel · Liquid-cooled

500 kW diesel commercial/industrial standby generator powered by John Deere. Suitable for hospitals, data centers, and large commercial complexes.

Tier 23-phasecommercialhealthcare
Kohler Kohler 500REOZVC 515 kW liquid-cooled standby generator

Kohler

Kohler 500REOZVC

515 kW diesel standby -- Volvo TAD1641GE-B, sub-3% THD. Decision-Maker controller for load management and paralleling.

515 kW standby · Diesel · Liquid-cooled

515 kW diesel commercial/industrial standby generator powered by Volvo. Suitable for hospitals, data centers, and large commercial complexes.

Tier 23-phasecommercialhealthcare
Kohler Kohler 500REZXD 500 kW liquid-cooled standby generator

Kohler

Kohler 500REZXD

500 kW industrial gaseous -- PSI/Doosan D219L with PM alternator, sub-3% THD. No fuel tank, no SPCC, lower emissions than diesel.

500 kW standby · LPG · Liquid-cooled

500 kW LPG industrial standby generator. Enclosed gaseous standby with PSI/Doosan engine and pilot-excited permanent-magnet alternator.

3-phasecommercialhealthcare