Overview#
The Cat G3516H is a high-efficiency natural gas engine designed for continuous-duty power generation and combined heat and power (CHP) applications. Producing 1982 ekW at 1500 rpm, the G3516H is a turbocharged-aftercooled gas engine with ADEM4 electronic controls and separate-circuit aftercooling (SCAC).
At 43.5% electrical efficiency and 85.9% total CHP efficiency, the G3516H is engineered for baseload and distributed generation rather than emergency standby. The NOx emission level is 0.5 g/bhp-hr at the engine exhaust flange, prior to any aftertreatment; an oxidation catalyst may be required to meet CO or HC requirements.
Engine platform#
The G3516H data sheet lists:
- 12.1:1 compression ratio
- SCAC (separate circuit aftercooling) with stage 1 and stage 2 aftercooler inlet temperatures specified
- ADEM4 control system with air-fuel ratio control
- Dry exhaust manifold
The engine is rated without fan at ISO 3046/1 standard reference conditions (25C, 100 kPa barometric). Altitude capability is 1400 meters at 25C inlet air temperature before derating.
Efficiency and heat recovery#
The G3516H is designed for total energy utilization. At full load:
- Electrical output: 1982 ekW (43.5% efficiency)
- Jacket water heat: 485 kW recoverable
- Lube oil heat: 184 kW recoverable
- Stage 1 aftercooler heat: 407 kW recoverable
- Exhaust heat to 120C: 919 kW recoverable
- Total CHP efficiency: 85.9%
These heat recovery values make the G3516H a strong candidate for district heating, industrial process heat, and greenhouse heating applications where both electrical and thermal output are valuable.
Emissions profile#
The G3516H data sheet lists engine-out emissions at the exhaust flange, prior to any aftertreatment, at full load:
- NOx: 272 mg/Nm3 (corrected to 5% O2) at full load
- CO: 975 mg/Nm3 -- an oxidation catalyst may be required for CO/HC compliance depending on local regulations
- Formaldehyde: 117 mg/Nm3
Our service experience#
The two-stage aftercooling system demands careful attention to coolant temperature stability: the sheet states the aftercooler stage 2 inlet temperature should be controlled to the rated value with a tolerance of (+)3C, (-)0C.