Kohler · KD Series (Industrial Diesel)

New

Kohler KD1350

1350 kW standby / 1210 kW prime · Diesel · Liquid-cooled

1350 kW diesel industrial standby generator. Mid-range KD Series platform for data centers, healthcare, and large commercial applications.

Kohler KD1350 — product photo
Standby power
1350 kW / 1210 kW prime
Voltage options
277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
Kohler KD36V16 · 36L
EPA / Emissions
Tier 2
Alternator
Kohler KH05641TO4D
data-centerhealthcareindustrial-heavycommercialgovernmentmission-critical

Overview#

The Kohler KD1350 is a 1350-kilowatt diesel industrial standby generator from Kohler's KD Series platform. It occupies the mid-range of the KD line, serving data centers, healthcare facilities, and large commercial campuses that need over a megawatt of backup power. The KD Series uses Kohler-designed engines and permanent-magnet pilot exciter alternators.

KD Series platform#

The KD Series is Kohler's large industrial diesel generator line, covering 800 to 4000 kW. Designed for mission-critical facilities, every KD Series unit carries UL 2200 listing and meets NFPA 110 Level 1 requirements when equipped with the necessary accessories. Hurricane-rated enclosures with 186 mph wind load ratings are available across the platform.

Our service experience#

OnPoint Generators provides installation, maintenance, and emergency service for Kohler KD Series generators throughout Northern California. Our technicians are experienced with large diesel platforms in the megawatt class, including load bank testing, fuel system maintenance, and cooling system service for high-capacity industrial units.

Engineering specifications

Acoustic

Sound @ 7m, full load
97 dBA
Enclosure
Open

Fuel system & runtime

Fuel use @ full load
89.3 GPH
Fuel use @ 75% load
69.7 GPH
Fuel use @ 50% load
49.1 GPH

Photos

Kohler KD1350 — product photo

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Kohler KD1350

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Kohler KD1350

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

2.9 hours(0.1 days)

Fuel consumption ≈ 68.89 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Kohler KD1350 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationInjector fouling, hard starting, black smoke under load4,380+moderate
TurbochargerPower loss, excessive exhaust smoke, oil at turbo seals15,000+moderate
Cooling system (hoses / thermostat)Overtemperature fault, coolant loss, high EGT10,000+moderate
Battery (starting)Slow crank, failed exercise, low voltage alarm8,760+minor

Frequently Asked Questions

What is the standby rating of the Kohler KD1350?
Per the Kohler spec sheet, the KD1350 is rated at 1350 kW / 1687 kVA standby and 1210 kW / 1512 kVA prime continuous at 0.8 power factor, 60 Hz, 1800 RPM.
Is the Kohler KD1350 EPA Tier 4 certified?
No. The KD1350 is EPA certified for stationary emergency use. Tier 4 Final variants are available in separate KD Series models designated with a -4 suffix.
What alternator type does the KD1350 use?
The KD1350 uses a brushless, permanent-magnet pilot exciter alternator — Kohler's standard for the KD Series large industrial diesel platform.

Similar models

Kohler 1250REOZMD backup generator

Kohler

New

Kohler 1250REOZMD

1.3 MW standby · Diesel · Liquid-cooled

1280 kW diesel industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.

Tier 23-phasedata-centerhealthcare
Kohler KD1250-4 backup generator

Kohler

New

Kohler KD1250-4

1.3 MW standby · Diesel · Liquid-cooled

1250 kW EPA Tier 4 Final diesel industrial standby generator. Dual-certified (emergency and non-emergency) for mission-critical and prime power applications.

Tier 4 Final3-phasedata-centerhealthcare
Kohler KD1250-A backup generator

Kohler

New

Kohler KD1250-A

1.3 MW standby · Diesel · Liquid-cooled

1250 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and large commercial facilities.

Tier 23-phasedata-centerhealthcare
Kohler KD1500 backup generator

Kohler

New

Kohler KD1500

1.5 MW standby · Diesel · Liquid-cooled

1500 kW diesel industrial standby generator. KD Series platform for data centers, healthcare, and mission-critical infrastructure.

Tier 23-phasedata-centerhealthcare
Kohler 1600ROZMC backup generator

Kohler

New

Kohler 1600ROZMC

1.6 MW standby · Diesel · Liquid-cooled

1560 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.

3-phasedata-centerhealthcare
Kohler 1250ROZMC backup generator

Kohler

New

Kohler 1250ROZMC

1.1 MW standby · Diesel · Liquid-cooled

1120 kW diesel 1500 RPM non-certified industrial generator powered by Mitsubishi. Mission-critical standby for data centers, hospitals, and large commercial facilities.

3-phasedata-centerhealthcare