Generac · MD Series (Modular Diesel)

Generac MD1500

1500 kW standby / 1350 kW prime · Diesel · Liquid-cooled

1500 kW modular diesel standby generator system. Factory-paralleled configuration with Mitsubishi 65.4L V16 engine for N+1 redundancy.

Standby power
1500 kW / 1350 kW prime
Voltage options
277/480V, 346/600V
Frequency / Phase
60 Hz · 3-phase
Engine
Mitsubishi S16R-Y2PTAW-1 · 65.4L
EPA / Emissions
Tier 2
Alternator
Generac K1500064N22

Overview#

The Generac MD1500 is a 1,500 kW modular diesel standby generator system powered by a Mitsubishi S16R-Y2PTAW-1 65.4-liter turbocharged and aftercooled V16 engine. As the largest model in Generac's MD Series lineup, the MD1500 is factory-configured with integrated paralleling controls and the InteliGen NT controller for automatic load sharing and synchronization across multiple modules.

Two MD1500 modules provide 3,000 kW of total capacity with full N+1 redundancy, serving the largest data center and critical infrastructure applications. The modular approach eliminates the single point of failure inherent in standalone megawatt-class gensets and simplifies transportation logistics -- individual 1,500 kW modules are substantially easier to rig than a single 3 MW unit. The system supports mixed configurations with other MD Series units for maximum design flexibility.

The Mitsubishi S16R is EPA Tier 2 certified for stationary emergency applications. The engine features dual-circuit cooling, a 212-quart oil capacity, and the Proact2 isochronous governor for precise frequency regulation during parallel operation.

Our Service Experience#

The MD1500 shares the proven Mitsubishi S16R platform with the SD1500. The 16-cylinder configuration across multiple modules creates substantial maintenance scope that requires methodical planning. We recommend staggering major service intervals (injector service, valve adjustments) across modules to maintain continuous N+1 redundancy throughout the maintenance cycle. At 133 gph per module at full load, fuel delivery and storage infrastructure is a critical design element for multi-unit installations. The dual-circuit cooling system on each module requires independent coolant sampling and maintenance.

Engineering specifications

Physical

Length
230.1 in
Width
106.8 in
Height
116.4 in
Dry weight
35,078 lb

Fuel system & runtime

Fuel use @ full load
133 GPH
Fuel use @ 75% load
97.3 GPH
Fuel use @ 50% load
66 GPH

Thermal & ventilation

Heat to coolant
2,122,320 BTU/hr
Exhaust flow
14,665 CFM
Exhaust temp
932 °F
Combustion air
5,932 CFM
Ventilation air
83,500 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Generac MD1500

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Generac MD1500

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

1.9 hours(0.1 days)

Fuel consumption ≈ 102.60 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Generac MD1500 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 4000 hours
Air filter
Every 500 hours
Fuel filter
Every 500 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationHard starting, filter clogging, reduced power output4,380+moderate
Paralleling controller synchronizationFailed sync, load sharing imbalance, hunting20,000+moderate
Coolant systemOverheating from coolant degradation in high-volume dual-circuit system4,000+moderate
TurbochargerReduced boost pressure, oil consumption from turbo seal wear12,000+severe
Starting batteriesFailure to crank the V16 from degraded batteries2,000+moderate

Frequently Asked Questions

What is the difference between the MD1500 and the SD1500?
The MD1500 is a modular (factory-paralleled) system designed for scalable, redundant power architectures. It uses the same Mitsubishi S16R 65.4L V16 engine as the SD1500 but comes factory-configured with integrated paralleling controls, enabling plug-and-play expansion with additional MD units. The SD1500 is a single-unit standalone generator at the same power rating. The modular approach provides N+1 redundancy, easier installation logistics, and the ability to service one unit while another continues operating.
What is the fuel consumption of the MD1500?
The MD1500 uses the same Mitsubishi S16R engine as the SD1500. At standby rating, fuel consumption is approximately 133.0 gallons per hour at full load, 97.3 gph at 75% load, and 66.0 gph at 50% load per module.
What voltages are available?
The MD1500 is available in three-phase configurations at 277/480V and 346/600V, both at 60 Hz.

Compatible equipment

Similar models

Generac Generac SD1500 1.5 MW liquid-cooled standby generator

Generac

Generac SD1500

1500 kW industrial diesel with Mitsubishi engine. Cost-effective alternative to CAT 3512 class. Multi-MW paralleling.

1.5 MW standby · Diesel · Liquid-cooled

1,500 kW standby diesel generator with Mitsubishi S16R-Y2PTAW-1 65.4L V16 engine. EPA Tier 2 certified. Three-phase 277/480V and 346/600V. UL2200 listed.

Tier 23-phasecommercial-standbyindustrial-standby

Generac

Generac MD1250

1250 kW modular diesel with factory paralleling. N+1 redundancy, easier installation, and scalable power architecture for multi-megawatt systems.

1.3 MW standby · Diesel · Liquid-cooled

1250 kW modular diesel standby generator system. Factory-paralleled configuration with Mitsubishi 49.0L V12 engine for N+1 redundancy.

Tier 23-phasecommercial-standbyindustrial
Generac Generac SD2500/MD2500 2.5 MW liquid-cooled standby generator

Generac

Generac SD2500/MD2500

2500 kW diesel in SD/MD platform with Baudouin engine. Cost-competitive with CAT 3516B at lower acquisition cost.

2.5 MW standby · Diesel · Liquid-cooled

2500 kW diesel industrial standby generator. Baudouin 65.6L V12 turbocharged/aftercooled, EPA Tier 2 Certified Stationary Emergency. Data Center Ready.

Tier 23-phasecommercial-standbyindustrial