Overview#
The Cat C175-16 is a large-format diesel generator set rated from 2,500 to 3,100 ekW for standby and mission-critical applications. Built around Caterpillar's 84.7-liter V-16 SCAC engine with common rail fuel injection and ADEM A4 electronic controls, this platform serves data centers, large industrial facilities, and campus-scale power systems where multi-megawatt capacity is required.
The C175-16 is available in voltages from 220 to 13,800 volts. The EMCP 4.2 control panel provides programmable protective relaying, Modbus RTU communications, and programmable digital inputs and outputs.
Key specifications#
- Rating range: 2500 to 3100 ekW at 60 Hz / 1800 rpm
- Engine: Cat C175-16 SCAC, V-16, 4-stroke, 84.7L displacement
- Bore x stroke: 175 mm x 220 mm (6.89 in x 8.66 in)
- Compression ratio: 16.07:1
- Fuel system: Common rail with ADEM A4 governor
- Fuel consumption (3000 ekW mission critical standby, 60 Hz, 1800 rpm, 480 V): 212.9 gal/hr at 100% load, 154.6 gal/hr at 75%, 109.7 gal/hr at 50%
- Genset dimensions (sheet Dimensions table; Technical Spec Sheet rating 3000 ekW mission critical standby, 60 Hz, 480 V): 312.9 in x 113.7 in x 134.3 in (L x W x H)
- Emissions: U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent)
Our service experience#
Site planning must account for adequate structural support and rigging access for equipment of this size. At this size class, proper load banking, fuel quality management, and turbocharger health monitoring are critical to reliability. The V-16 configuration requires balanced attention to both banks during service. The EMCP 4.2 controller provides metering and protective relaying.
FAQ#
What is the power output of the Cat C175-16?#
The sheet lists a rating range of 2500 to 3100 ekW at 60 Hz / 1800 rpm. The technical spec sheet shows a 3000 ekW (3750 kVA) mission critical standby rating at 480V, 0.8 power factor.
What engine does the Cat C175-16 generator use?#
The C175-16 SCAC -- an 84.7-liter V-16, four-stroke turbocharged-aftercooled diesel with a 175 mm bore, 220 mm stroke, 16.07:1 compression ratio, and common rail fuel injection governed by the ADEM A4 electronic governor. Certified to U.S. EPA Tier 2 Nonroad Equivalent for stationary emergency use.
Is the Cat C175-16 EPA compliant?#
The sheet lists the emissions strategy as U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards). Its applicable codes and standards list includes UL 2200, IBC, NFPA 110, and ISO 8528; the sheet notes codes may not be available in all model configurations.
Who services Cat C175-16 generators in Northern California?#
OnPoint Generators provides installation, maintenance, load bank testing, and emergency service for Caterpillar generators throughout Northern California and the Central Valley. As an authorized dealer network partner, we stock common Cat parts and have factory-trained technicians. Call us for service within a 150-mile radius of Sacramento.
What voltage options are available on the Cat C175-16?#
The sheet lists a voltage range of 220 to 13,800 volts, covering low-, medium-, and high-voltage distribution.
What controller does the Cat C175-16 use?#
The Cat C175-16 uses the EMCP 4.2 controller, which provides programmable protective relaying, Modbus RTU communications, and programmable digital inputs and outputs.