Kohler · KG Series (Industrial Gaseous)

Kohler KG60

60 kW standby · Natural Gas / LPG / Dual Fuel (NG/LPG) · Liquid-cooled

60 kW gaseous-fueled commercial standby generator with Kohler 6.2L engine, EPA Subpart JJJJ certified for stationary emergency. Specs and compatible transfer switches.

Kohler Kohler KG60 generator — specifications and details
Standby power
60 kW
Voltage options
120/240V, 208V, 240V, 480V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Kohler KG6208 · 6.2L
Alternator
Kohler

Overview#

The Kohler KG60 is a 60-kilowatt commercial standby generator built on Kohler's 6.2-liter naturally-aspirated V8 spark-ignition platform, certified to EPA 40 CFR Part 60 Subpart JJJJ for stationary emergency duty. It runs on either natural gas or LP propane with field-selectable fuel switching, and is sized for the light commercial sweet spot: full-service restaurants, multi-tenant retail, small data closets, multi-family residential common loads, telecom huts, and refrigerated storage.

It sits in the lower-middle of Kohler's industrial gaseous lineup. Below it: KG40, KG48. Above: KG80, KG100, KG125, and the larger KG200 / KG300 / KG400 platforms. The KG line is the gaseous-fueled counterpart to Kohler's diesel KD line — same engineering philosophy, different fuel system and emissions architecture.

Why we see this unit a lot#

Three reasons drive KG60 deployments:

  1. For sites where utility gas is reliable, this is a major operational simplification.
  2. Lower visible emissions. Subpart JJJJ-certified spark-ignition engines produce no visible smoke and significantly lower particulate matter than even Tier 4 Final diesel. Important for sound-and-air sensitive sites (hotels, hospitals, schools, urban infill).
  3. Footprint. At 60 kW with a sound-attenuated enclosure, the KG60 fits in spaces that won't accommodate a 100+ kW diesel skid with day tank. Useful for retrofits.

The tradeoff: gaseous fuel pressure delivery becomes the single point of failure. Earthquake gas-shutoff valves, pipeline integrity, and utility uptime all matter more than they would for a diesel unit with on-site storage.

Sizing guidance#

A bare 60 kW nameplate is misleading without context. Real sizing considerations:

  • Motor starting: large compressors and elevators draw 4-6× full-load current at startup. A 60 kW genset will start a single 7.5 HP motor without issue but may struggle with simultaneous starts.
  • Power factor: the KG60's 75 kVA rating at 0.8 PF assumes mixed inductive load. Heavily reactive loads (lots of fluorescent ballasts, large motors without VFDs) will shave usable kW.
  • Altitude / temperature derate: above 1000 ft elevation or 25°C ambient, output derates per Kohler's curve. Coastal California sites usually clear without derate; foothill / Sierra sites may need to size up.
  • Future load growth: if your facility expects 15-20% load growth in the next 5 years, the KG80 or KG100 is often the better long-term spec.

Engine and drivetrain#

Always source parts through authorized Kohler/Rehlko channels and reference TP-7098 / TP-7118 for the part numbers that apply to your specific build — the Kohler service catalog supersedes any third-party cross-reference.

The alternator is a brushless, 4-pole, Class H rotating-field unit with rare-earth permanent magnet (PMG) excitation, using Kohler's Fast-Response excitation system. The PMG sustains short-circuit current up to 300% of rated for up to 10 seconds, which keeps voltage regulation stable into nonlinear loads (UPS rectifiers, VFDs) and lets downstream breakers trip without collapsing the alternator field.

The standard controller is the Kohler APM402, with the APM603 available for paralleling and advanced load management. Both speak Modbus and integrate with most BMS / SCADA platforms via the optional gateway accessory.

NFPA 110 considerations#

For Level 1 (life-safety) emergency systems, the KG60 is acceptable when configured with the NFPA 110 option package, which adds:

  • Battery charger output monitoring with low-voltage alarm
  • Run-fail / not-in-auto remote contacts
  • Audible/visual local alarm panel
  • Fuel pressure / supply integrity monitoring
  • On-site engine diagnostics maintained for at least 5 years

The gaseous-fuel question for NFPA 110 is local-AHJ-dependent. NFPA 110 §5.1.3 permits gaseous on-site fuel supplies where the fuel source is reliable and protected, but some California AHJs interpret this conservatively for hospital and life-safety occupancies. Always confirm with the AHJ before specifying gaseous for Level 1 service — for some occupancies, only diesel will pass review.

How it compares#

Comparable units in the 60-80 kW commercial gaseous bracket include the Generac SG080 and the Cummins C60 N6. The KG60 vs SG080 vs C60 N6 decision typically comes down to (a) which dealer is local with parts and service, (b) which controller integrates with your existing BMS, and (c) install-cost differences driven by enclosure size and local trades. Confirm current OEM specs against each manufacturer's spec sheet before locking a decision.

When NOT to spec the KG60#

Honest reasons to choose a different unit:

  • Mission-critical IT load: if you're protecting a tier III+ data center, plan around diesel. Gaseous units are excellent for tier I/II and edge sites; for tier III+, the regulatory and AHJ pressure typically favors diesel.
  • Heavy motor starting on day one: for a single-genset site that needs to cold-start a 25+ HP motor, look at the KG100 or KG125. Doable on the KG60 with a soft-start, but cleaner with more headroom.
  • Sites with unreliable gas service: historic gas-supply outages or seismic-shutoff exposure (Bay Area especially) make a diesel + gas hybrid attractive. The KG60 has a bi-fuel option but the diesel pilot fuel adds storage requirements that erase part of the gaseous advantage.
  • Locations needing CARB Level 0 marks: for the most stringent Air District filings, current diesel Tier 4 Final units are sometimes a better paper match than Subpart JJJJ gaseous, depending on jurisdiction.

Our service experience#

We service KG-series units across coastal California — Monterey, Santa Cruz, San Benito, and inland Santa Clara / San Jose. The KG60 is one of the most-deployed gaseous standby gensets in our service territory, particularly in restaurant chains, urban hotels, and Class B office buildings where on-site diesel storage is impractical.

Engineering specifications

Physical

Length
86.6 in
Width
34 in
Height
46.1 in
Wet weight
1,900 lb

Acoustic

Enclosure
Sound-attenuated

Documents & downloads

Ready to order this model?

Configure your Kohler KG60

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Kohler KG60

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

630,000 BTU/hr≈ 630.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Parts cross-reference

starting Battery
Group 31 (recommended)

Frequently Asked Questions

What is the standby power rating of the Kohler KG60?
The KG60 is rated 60 kW standby at 60 Hz. The standby rating applies to emergency backup applications where utility power is unavailable; prime power is the rating for indefinite-duration runtime with variable load. Kohler also offers selectable voltage configurations from 120/240V single-phase up to 480V three-phase.
Does the KG60 run on natural gas or propane?
Both. The KG60 is a dual-fuel design that operates on either natural gas (NG) or liquid propane (LPG) with field-selectable fuel switching. Propane delivers slightly higher kW output than natural gas due to BTU density. There is no diesel variant — the KG line is gaseous-only.
What engine is in the Kohler KG60?
The KG60 uses the Kohler KG6208, a 6.2L naturally-aspirated V8 (101.6 mm bore × 95.25 mm stroke, 9.8:1 compression) running at 1800 RPM. It is EPA-certified to 40 CFR Part 60 Subpart JJJJ for stationary emergency spark-ignition engines.
Is the KG60 EPA Tier 4 Final compliant?
EPA Tier ratings (Tier 2/3/4) apply to non-road diesel engines. The KG60 is a stationary spark-ignition engine and is regulated under 40 CFR Part 60 Subpart JJJJ, not the Tier system. The KG60 is certified to current Subpart JJJJ standards for stationary emergency engines.
What automatic transfer switches are compatible with the KG60?
The KG60 will pair with any 2-pole or 3-pole ATS rated for the unit's amperage at the selected voltage. Common pairings include the Kohler KCS Series, ASCO 300 Series, and Eaton ATC-300+. For 60 kW at 480V three-phase, an 100-150A switch is typical; at 208V three-phase, plan for 200-225A.
Can the KG60 be paralleled with a second unit?
Yes — with the appropriate paralleling controller (Kohler APM603 or upgrade) and switchgear, multiple KG60 units can be paralleled for capacity expansion or N+1 redundancy. The base KG60 controller does not include paralleling firmware out of the box.
Is the KG60 NFPA 110 compliant?
Yes, when configured with appropriate options. NFPA 110 Level 1 (life-safety) and Level 2 applications require specific controller features, monitoring, alarm contacts, and on-site fuel storage / supply guarantees. Spec the unit with the NFPA 110 option package and confirm your local AHJ accepts the gaseous fuel arrangement.

Checklist

  1. Verify NG/LPG supply pressure and BTU content match Kohler spec (5-14 inches WC for NG)
  2. Confirm fuel piping is sized for full-load demand without pressure drop
  3. Check engine oil level and quality (color, smell, consistency)
  4. Inspect coolant level and condition; test pH and freeze point
  5. Inspect ignition wires, coil packs, and spark plugs for wear
  6. Test exercise cycle runs and load transfer (if ATS-connected)
  7. Check exhaust system for leaks, especially at manifold and mufflers
  8. Verify controller alarm contacts and remote monitoring connectivity
  9. Confirm enclosure ventilation, drainage, and animal/pest exclusion

Key Terms

EPA Subpart JJJJ
40 CFR Part 60 Subpart JJJJ — federal emissions standard for new stationary spark-ignition internal combustion engines, including natural gas and propane gensets like the KG60.
Standby vs. Prime rating
Standby rating is for emergency backup with utility outages; prime is for continuous-duty primary power with variable load.
Dual-fuel (NG/LPG)
Engine configured to operate on either natural gas or liquid propane, with field-selectable fuel switching. Output varies slightly by fuel due to BTU differences.
Subbase fuel tank
Not applicable to gaseous units — natural gas relies on utility supply, propane requires a separate ASME-rated propane tank with appropriate vaporization.

Compatible equipment

More in the KG Series (Industrial Gaseous)

Kohler KG Series: 40–200 kW gaseous gensets with Kohler-built engines for commercial and light industrial standby.

Why we recommend Kohler

Kohler is our primary recommendation for commercial standby power. We sell and service the full Kohler line — RCA residential, RCL light commercial, KG industrial diesel, and REOZ large-frame — and our technicians are factory-trained on every product family.

We are an authorized Kohler dealer with factory-trained technicians. Kohler is the majority of our new generator sales today, spanning residential through large industrial. Our parts inventory is stocked for same-day Kohler service.

See all Kohler generators →

Similar models

Kohler Kohler KG50 53 kW liquid-cooled standby generator

Kohler

Kohler KG50

53 kW gaseous standby -- Kohler KG6208 NA V8 at 1800 RPM with rare-earth PM alternator.

53 kW standby · Natural Gas / LPG / Dual Fuel (NG/LPG) · Liquid-cooled

53 kW gaseous-fueled commercial standby generator with Brushless Rare-Earth Permanent-Magnet alternator. Industrial gaseous unit for commercial backup on natural gas or propane.

3-phasecommercialhealthcare
Kohler Kohler KG80 80 kW liquid-cooled standby generator

Kohler

Kohler KG80

80 kW industrial gaseous -- Kohler KG6208 6.2L turbo.

80 kW standby · Natural Gas / LPG / Dual Fuel (NG/LPG) · Liquid-cooled

80 kW gaseous-fueled commercial standby generator. Industrial gaseous unit for medium commercial backup on natural gas or propane.

3-phasemedium-commercialmulti-tenant-retail
Kohler Kohler 60REOZK 60 kW liquid-cooled standby generator

Kohler

Kohler 60REOZK

60 kW compact diesel standby -- Kohler KDI 3404TM turbo at 1800 RPM.

60 kW standby · Diesel · Liquid-cooled

60 kW diesel commercial standby generator. Kohler-powered diesel for commercial, healthcare, education, and government standby applications.

3-phasecommercialhealthcare