Kohler · REOZ Series (Diesel Commercial Standby)

Kohler 180REOZJG

180 kW standby / 165 kW prime · Diesel · Liquid-cooled

180 kW diesel commercial standby generator powered by John Deere. Reliable standby power for commercial and institutional facilities.

Kohler Kohler 180REOZJG generator — specifications and details
Standby power
180 kW / 165 kW prime
Voltage options
277/480V, 120/208V, 120/240V
Frequency / Phase
60 Hz · 1/3-phase
Engine
John Deere 6068HFG82E · 6.8L
EPA / Emissions
Tier 3
Alternator
Kohler 4S12X

Overview#

The Kohler 180REOZJG is a 180-kilowatt standby (165 kW prime) diesel generator powered by a John Deere engine at 1800 RPM. Typical applications include commercial buildings, healthcare, and institutional facilities.

Our service experience#

OnPoint Generators services Kohler REOZ diesel generators throughout Northern California. We typically structure service for this class around annual NFPA 110 maintenance plus semi-annual fuel quality and filter inspections.

Engineering specifications

Physical

Length
118.1 in
Width
51.2 in
Height
65.7 in
Wet weight
3,295 lb

Fuel system & runtime

Fuel use @ full load
13.7 GPH
Fuel use @ 75% load
11.3 GPH

Photos

Kohler 180REOZJG — product photo

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Kohler 180REOZJG

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Kohler 180REOZJG

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

18.9 hours(0.8 days)

Fuel consumption ≈ 10.57 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Kohler 180REOZJG under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 3000 hours
Air filter
Every 500 hours
Fuel filter
Every 500 hours
Major overhaul
15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationInjector fouling, hard starting, filter clogging4,380+moderate
TurbochargerPower loss, excessive smoke under load12,000+moderate
Battery (starting)Failed to start, slow crank8,760+minor

Frequently Asked Questions

What engine powers the Kohler 180REOZJG?
The 180REOZJG uses a John Deere diesel engine running at 1800 RPM (model 6068HFG82E).
What is the standby power rating of the 180REOZJG?
The 180REOZJG is rated at 180 kW standby and 165 kW prime per Kohler published specifications.
Does OnPoint service the Kohler 180REOZJG?
Yes. OnPoint Generators provides maintenance, repair, and load bank testing for Kohler REOZ diesel generators throughout Northern California, including the 180 kW class.

Compatible equipment

More in the REOZ Series (Diesel Commercial Standby)

Kohler's diesel commercial standby series — 10 to 510 kW, John Deere and Kohler engines, built for life-safety loads.

Similar models

Kohler Kohler 200REOZJF 200 kW liquid-cooled standby generator

Kohler

Kohler 200REOZJF

200 kW diesel standby with sub-3% THD -- John Deere 6068HFG85. Healthcare and data center default in this power class.

200 kW standby · Diesel · Liquid-cooled

200 kW diesel commercial standby generator. Large commercial diesel for hospitals, data centers, and institutional facilities.

Tier 33-phasehospitaldata-center
Kohler Kohler 150REOZJF 154 kW liquid-cooled standby generator

Kohler

Kohler 150REOZJF

THD below 3% at 154 kW -- the healthcare and commercial default. John Deere 6068HF285K with Decision-Maker controller.

154 kW standby · Diesel · Liquid-cooled

154 kW diesel commercial standby generator powered by John Deere. Reliable standby power for commercial and institutional facilities.

Tier 33-phasecommercialhealthcare
Kohler Kohler 180REZXB 190 kW liquid-cooled standby generator

Kohler

Kohler 180REZXB

190 kW industrial gaseous -- Doosan D111TIC with PM alternator, sub-3% THD. No on-site fuel storage required.

190 kW standby · LPG · Liquid-cooled

190 kW LPG industrial standby generator. Enclosed gaseous standby with Doosan engine for commercial, healthcare, and institutional applications.

3-phasecommercialhealthcare