Kohler · REOZ Series (Diesel Commercial Standby)

Kohler 30REOZK

30 kW standby / 28 kW prime · Diesel · Liquid-cooled

30 kW diesel commercial standby generator. Kohler-powered diesel for commercial, healthcare, education, and government standby applications.

Kohler Kohler 30REOZK generator — specifications and details
Standby power
30 kW / 28 kW prime
Voltage options
120/208V, 277/480V, 120/240V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Kohler KDI2504TM/G18 · 2.5L

Overview#

The Kohler 30REOZK is a 30-kilowatt diesel commercial standby generator powered by a Kohler diesel engine at 1800 RPM. It is designed for commercial facilities, healthcare, education, and government applications where diesel fuel independence is required. The unit features a 4-pole rotating-field alternator with PowerBoost excitation and is available with durable enclosures rated for 186 mph wind loads.

Our service experience#

OnPoint services Kohler REOZK diesel generators throughout Northern California. The 30REOZK sits in a popular size band for small commercial buildings and branch offices, and we typically structure these accounts around an annual PM plus semi-annual fuel and filter inspection.

Engineering specifications

Physical

Length
56.6 in
Width
31.9 in
Height
40.3 in
Wet weight
1,130 lb

Fuel system & runtime

Fuel use @ full load
2.6 GPH
Fuel use @ 75% load
2.1 GPH
Fuel use @ 50% load
1.5 GPH

Photos

Kohler 30REOZK — product photo

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Kohler 30REOZK

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Kohler 30REOZK

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

99.7 hours(4.2 days)

Fuel consumption ≈ 2.01 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Kohler 30REOZK under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 2000 hours
Air filter
Every 500 hours
Fuel filter
Every 250 hours
Major overhaul
8,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationInjector fouling, hard starting, reduced power output4,380+moderate
Coolant thermostatOvercooling at light load, extended warmup time8,000+minor
Battery (starting)Slow crank, failed exercise, low voltage alarm8,760+minor

Frequently Asked Questions

What engine is in the Kohler 30REOZK?
The 30REOZK uses a Kohler diesel engine rated at 1800 RPM, EPA certified for stationary emergency standby use.
Is there a Tier 4 Final version of the 30REOZK?
Yes. The 30REOZK4 is the EPA Tier 4 Final variant of this model, certified for both stationary emergency and non-emergency applications.

Compatible equipment

More in the REOZ Series (Diesel Commercial Standby)

Kohler's diesel commercial standby series — 10 to 510 kW, John Deere and Kohler engines, built for life-safety loads.

Similar models

Kohler Kohler 30REOZK4 30 kW liquid-cooled standby generator

Kohler

Kohler 30REOZK4

Compact 30 kW diesel standby -- Kohler KDI 1903 TCR at 1800 RPM. Quiet operation with sub-3% THD for sensitive loads.

30 kW standby · Diesel · Liquid-cooled

30 kW Tier 4 Final diesel commercial standby generator. Kohler-powered diesel with EPA Tier 4 Final emissions compliance for commercial and institutional applications.

Tier 4 Final3-phasecommercialhealthcare
Kohler Kohler 35REOZT4 30 kW liquid-cooled standby generator

Kohler

Kohler 35REOZT4

30 kW mobile diesel trailer -- Tier 4 Kohler KDI 1903 TCR. Road-towable for temporary power, construction, and emergency deployment.

30 kW standby · Diesel · Liquid-cooled

35 kW Tier 4 Final diesel mobile trailer generator. Kohler-powered portable diesel for construction, events, and temporary power applications.

Tier 4 Final3-phasecommercialhealthcare
Kohler Kohler 20REOZK 20 kW liquid-cooled standby generator

Kohler

Kohler 20REOZK

Compact 20 kW diesel standby -- Kohler KDI2504ESM at 1800 RPM. Quiet operation with sub-3% THD for sensitive loads.

20 kW standby · Diesel · Liquid-cooled

20 kW diesel commercial standby generator. Kohler-powered diesel for small commercial, retail, and light institutional standby applications.

3-phasecommercialhealthcare

Need service or parts for the Kohler 30REOZK?

We service every major OEM and stock genuine parts for the most common models.