Kohler · REOZ Series (Diesel Commercial Standby)

Kohler 250REOZJE

255 kW standby / 230 kW prime · Diesel · Liquid-cooled

255 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.

Kohler Kohler 250REOZJE generator — specifications and details
Standby power
255 kW / 230 kW prime
Voltage options
277/480V, 120/208V, 120/240V
Frequency / Phase
60 Hz · 1/3-phase
Engine
John Deere 6090HF484B · 9L
EPA / Emissions
Tier 3
Alternator
Kohler 4UA10

Overview#

The Kohler 250REOZJE is a 255-kilowatt standby (230 kW prime) diesel generator powered by a John Deere engine at 1800 RPM. Typical applications include commercial buildings, healthcare facilities, and institutional campuses.

Our service experience#

OnPoint Generators services Kohler REOZ diesel generators throughout Northern California. We typically structure accounts for mid-range diesel units around annual NFPA 110 service plus semi-annual fuel and filter inspections.

Engineering specifications

Physical

Length
118.1 in
Width
51.2 in
Height
74.4 in
Wet weight
5,400 lb

Fuel system & runtime

Fuel use @ full load
17.6 GPH
Fuel use @ 75% load
13.3 GPH

Photos

Kohler 250REOZJE — product photo

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Kohler 250REOZJE

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Kohler 250REOZJE

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

14.7 hours(0.6 days)

Fuel consumption ≈ 13.58 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Kohler 250REOZJE under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 3000 hours
Air filter
Every 500 hours
Fuel filter
Every 500 hours
Major overhaul
15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationInjector fouling, hard starting, filter clogging4,380+moderate
TurbochargerPower loss, excessive smoke under load12,000+moderate
Battery (starting)Failed to start, slow crank8,760+minor

Frequently Asked Questions

What engine powers the Kohler 250REOZJE?
The 250REOZJE uses a John Deere diesel engine running at 1800 RPM (model 6090HF484B).
What is the standby power rating of the 250REOZJE?
The 250REOZJE is rated at 255 kW standby and 230 kW prime per Kohler published specifications.
Does OnPoint service the Kohler 250REOZJE?
Yes. OnPoint Generators provides maintenance, repair, and load bank testing for Kohler REOZ diesel generators throughout Northern California, including the 255 kW class.

Compatible equipment

More in the REOZ Series (Diesel Commercial Standby)

Kohler's diesel commercial standby series — 10 to 510 kW, John Deere and Kohler engines, built for life-safety loads.

Similar models

Kohler Kohler 230REOZJE 230 kW liquid-cooled standby generator

Kohler

Kohler 230REOZJE

230 kW diesel standby with sub-3% THD -- John Deere 6090HF484C. Healthcare and data center default in this power class.

230 kW standby · Diesel · Liquid-cooled

230 kW diesel commercial standby generator powered by John Deere. Reliable standby power for commercial and institutional facilities.

Tier 33-phasecommercialhealthcare
Kohler Kohler 275REOZJE 280 kW liquid-cooled standby generator

Kohler

Kohler 275REOZJE

280 kW diesel standby with sub-3% THD -- John Deere 6090HF484A. Healthcare and data center default in this power class.

280 kW standby · Diesel · Liquid-cooled

280 kW diesel commercial standby generator powered by John Deere. Mid-range diesel workhorse for commercial, healthcare, and institutional applications.

Tier 33-phasecommercialhealthcare
Kohler Kohler 250REZXB 260 kW liquid-cooled standby generator

Kohler

Kohler 250REZXB

260 kW industrial gaseous -- Doosan D146L with PM alternator. No fuel storage, no SPCC plan, lower emissions than diesel.

260 kW standby · LPG · Liquid-cooled

260 kW LPG industrial standby generator. Enclosed gaseous standby with Doosan engine for large commercial and institutional applications.

3-phasecommercialhealthcare

Need service or parts for the Kohler 250REOZJE?

We service every major OEM and stock genuine parts for the most common models.