The Kohler 10REOZDC is a 10-kilowatt diesel commercial standby generator powered by a Yanmar engine at 1800 RPM. It is the smallest unit in the REOZ diesel lineup, designed for small commercial facilities, retail locations, and light institutional applications where diesel fuel independence is required. The unit features a brushless wound-field alternator with PowerBoost excitation and sustained short-circuit capability up to 300% of rated current.
OnPoint services small diesel standby generators across Northern California for commercial customers who need fuel-independent backup power. The compact Yanmar platform in the 10REOZDC is reliable and straightforward to maintain, with standard annual PM covering oil, filters, and coolant inspection.
Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.
Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.
Estimate runtime on this tank
Estimated runtime
235.7 hours(9.8 days)
Fuel consumption ≈ 0.85 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.
Service intervals
Manufacturer-recommended intervals for the Kohler 10REOZDC under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.
Oil & filter
Every 200 hours or 12 months
Coolant change
Every 2000 hours
Air filter
Every 500 hours
Fuel filter
Every 200 hours
Major overhaul
≈ 8,000 hours
Load bank test
Every 12 months
Common failure modes
What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.
Component
Symptom
Typical hours
Severity
Fuel quality / degradation
Injector fouling, hard starting, filter clogging
4,380+
moderate
Coolant thermostat
Overcooling, extended warmup, high fuel consumption
6,000+
minor
Battery (starting)
Slow crank, failed exercise
8,760+
minor
Frequently Asked Questions
What engine is in the Kohler 10REOZDC?
The 10REOZDC uses a Yanmar diesel engine rated at 1800 RPM, EPA certified for stationary emergency standby use.
Is the 10REOZDC available in three-phase?
Yes. The 10REOZDC is offered in both single-phase (120/240 V) and three-phase (120/208 V) configurations.