Gillette · SPD Series (Industrial Diesel - Perkins)

New

Gillette SPD-2000

200 kW standby · Diesel · Liquid-cooled

200 kW stationary diesel standby generator with Perkins 1106D-E70TAG5 engine. Made-in-USA with Stamford UCID274J alternator and DSE 7420 MKII controller.

Standby power
200 kW
Voltage options
120/240V, 120/208V, 277/480V, 346/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Perkins 1106D-E70TAG5 · 7.01L
EPA / Emissions
Tier 3
Alternator
Stamford UCID274J-311
commercialhospitalhoteldata-centermunicipalindustrialcampus

Overview#

The Gillette SPD-2000 is a 200-kilowatt stationary diesel standby generator — the largest unit in the SPD Perkins series and the output ceiling of the Perkins 1106D platform. The TAG5 high-output variant produces 314 bhp from the same 7.01L inline-6 as the 150 kW SPD-1500, sharing identical physical dimensions and enclosure options.

At 200 kW, this is the highest-output Perkins diesel Gillette offers. Above 200 kW, the lineup transitions to Volvo engines (SPVD-2500 at 250 kW).

SPD-1500 vs. SPD-2000: same box, 50 kW more#

Like the gas SP series, the diesel SPD series offers paired models from the same engine platform at different output tiers:

SpecSPD-1500SPD-2000
Engine1106D-E70TAG41106D-E70TAG5
Standby kW150200
Mechanical bhp281314
Fuel (100%)13.8 gal/hr15.6 gal/hr
Open dimensions110 x 48 x 55 in110 x 48 x 55 in
Open weight3,404 lbs3,404 lbs

If load growth is anticipated, specifying the SPD-2000 on the same foundation as the SPD-1500 costs little incremental and provides 50 kW of headroom.

The Perkins-to-Volvo transition at 200 kW#

200 kW is the practical ceiling for the Perkins 1106D in standby generator duty. Above this output, the next step is the SPVD-2500 (Volvo TAD series, 250 kW) — a different engine architecture, larger physical footprint, and different service paradigm. If the facility will need more than 200 kW in the future, consider whether the Volvo platform (available from 250 kW to 700 kW) is the better long-term investment.

Our service experience#

The Perkins 1106D at 200 kW (TAG5) runs at the upper end of its thermal envelope. We pay particular attention to turbocharger condition and charge air cooler performance at this output level — the higher boost pressures mean these components are working harder than on the 150 kW variant. Fuel filter service and fuel quality testing remain critical. The Stanadyne rotary fuel system is mechanically straightforward compared to common rail systems at this power class.

Engineering specifications

Physical

Length
110 in
Width
48 in
Height
55 in
Wet weight
3,404 lb

Acoustic

Sound @ 7m, full load
78 dBA
Enclosure
Sound-attenuated

Fuel system & runtime

Fuel use @ full load
15.6 GPH

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Gillette SPD-2000

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Gillette SPD-2000

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

16.6 hours(0.7 days)

Fuel consumption ≈ 12.03 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Gillette SPD-2000 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationHard starting, filter clogging, reduced power4,380+moderate
TurbochargerPower loss, excessive smoke under load12,000+moderate
Charge air coolerReduced output, elevated intake temperatures10,000+moderate
BatteryFailed to start, slow crank8,760+minor

Frequently Asked Questions

How does the SPD-2000 achieve 200 kW from the same 7.0L as the 150 kW SPD-1500?
The SPD-2000 uses the Perkins 1106D-E70TAG5 — the 'TAG5' is a higher-output calibration of the same 7.01L inline-6 used in the SPD-1500 (TAG4). Higher turbo boost pressure and optimized fuel delivery produce 314 bhp (vs 281 bhp on the SPD-1500) from the same displacement. Physical dimensions and enclosure are identical.
Is the SPD-2000 the largest Perkins model Gillette offers?
Yes — the SPD-2000 at 200 kW is the top of the Perkins diesel lineup. Above 200 kW, Gillette transitions to Volvo engines (SPVD series starting at 250 kW). The Perkins 1106D platform reaches its practical output ceiling at 200 kW standby.
How does the SPD-2000 compare to the SPJD-2100?
The SPD-2000 (Perkins 1106D, 7.0L I6, 200 kW) and SPJD-2100 (John Deere 6068HF485, 6.8L I6, 210 kW) are very close competitors. The John Deere has 10 kW more output from slightly less displacement but with a lower compression ratio (17.0 vs 16.8). Both share the same enclosure dimensions and weight.
What fuel consumption at 200 kW full load?
15.6 gal/hr at full load. At 75%: 12.5 gal/hr. At 50%: 8.6 gal/hr. With a 300-gallon sub-base tank at 75% load, expect approximately 24 hours of runtime. For extended outages, plan for fuel delivery logistics.

Compatible equipment

Similar models

Gillette

New

Gillette SPD-1500

150 kW standby · Diesel · Liquid-cooled

150 kW stationary diesel standby generator with Perkins 1106D-E70TAG4 engine. Made-in-USA with Stamford UCI274G alternator and DSE 7420 MKII controller.

Tier 33-phasecommercialhospital

Gillette

New

Gillette SPJD-2100

210 kW standby · Diesel · Liquid-cooled

210 kW stationary diesel standby generator with John Deere 6068HF485 engine. Made-in-USA with Stamford UCID274J alternator and DSE 7420 MKII controller.

Tier 33-phasecommercialhospital

Gillette

New

Gillette SPVD-2500

250 kW standby · Diesel · Liquid-cooled

250 kW stationary diesel standby generator with Volvo Penta TAD852GE 7.7L engine. Stamford S4L1D alternator, Basler DGC-2020 controller. Made in USA.

Tier 33-phasecommercialhospital

Gillette

New

Gillette T4D-2000

200 kW standby · Diesel · Liquid-cooled

200 kW Tier 4 Final / Stage 5 diesel generator with Volvo Penta TAD1180VE 10.8L engine. SCR aftertreatment, DEF, Basler DGC-2020 controller. Made in USA.

Tier 4 Final3-phasecommercialhospital

Gillette

New

Gillette SPJD-1550

155 kW standby · Diesel · Liquid-cooled

155 kW stationary diesel standby generator with John Deere 6068HF285 engine. Made-in-USA with Stamford UCI274G alternator and DSE 7420 MKII controller.

Tier 33-phasecommercialhospital

Gillette

New

Gillette T4D-1500

150 kW standby · Diesel · Liquid-cooled

150 kW Tier 4 Final / Stage 5 diesel generator with Volvo Penta TAD881VE 7.7L engine. SCR aftertreatment, DEF system, Basler DGC-2020 controller. Made in USA.

Tier 4 Final3-phasecommercialhospital

Need service or parts for the Gillette SPD-2000?

We service every major OEM and stock genuine parts for the most common models.