Overview#
The Cummins C250 N6 is a 250-kilowatt natural gas standby generator set built on the Cummins GTA855E — a 14-liter (854 in³) 4-cycle industrial spark-ignited engine with a cast iron block and replaceable wet cylinder liners.
The C250 N6 is rated at 250 kW (312 kVA) standby, listed to UL 2200, and certified to EPA SI NSPS Stationary Emergency standards. The PowerCommand 3.3 control supports full paralleling functionality — including Phase Lock Loop synchronization, isochronous kW/kVar load sharing, and extended paralleling for baseload or peak-shave operation — making the C250 N6 well suited for multi-unit arrays and facilities requiring N+1 redundancy on natural gas.
The generator accepts full rated load in a single step per NFPA 110 Type 10 (ten-second transfer) for Level 1 and Level 2 EPSSs.
Dimensions (L x W x H): 3,734 mm x 1,676 mm x 1,997 mm (147 x 66 x 79 in.). Weight: consult factory for configuration-specific weights.
Technical Specifications#
| Parameter | Value |
|---|---|
| Standby Rating | 250 kW (312 kVA) |
| Frequency | 60 Hz |
| Power Factor | 0.8 |
| Engine Model | GTA855E |
| Displacement | 14 L (854 in³) |
| Cylinder Block | Cast iron with replaceable wet cylinder liners |
| Starting System | 24-volt, 8D batteries (x2), 900 A cranking current at 0 °C (32 °F) |
| Battery Charging Alternator | 43 amps |
| Control | PowerCommand 3.3 |
| Dimensions (L x W x H) | 3734 x 1676 x 1997 mm (147 x 66 x 79 in.) |
Natural gas fuel consumption (SCFH):
| Load | SCFH |
|---|---|
| 25% | 950 |
| 50% | 1,951 |
| 75% | 2,692 |
| 100% | 3,440 |
Fuel inlet pressure: 381 to 508 mm WC (15 to 20 in. WC) at the generator set connection.
Available voltage configurations (three-phase): 120/208V, 127/220V, 139/240V, 220/380V, 240/416V, 254/440V, 277/480V, 347/600V
Our Service Experience#
The C250 N6 handles demanding commercial standby loads where gaseous fuel is the preferred choice. Its 15 to 20 in. WC fuel inlet pressure requirement makes gas supply system sizing critical — underpressure conditions will cause performance degradation that may not be immediately obvious until full-load testing.
The PowerCommand 3.3 control's InPower service tool compatibility allows detailed diagnostics and fault history review at every service visit.
Frequently Asked Questions#
What engine does the C250 N6 use? The Cummins GTA855E — a 14-liter (854 in³) 4-cycle spark-ignited engine with a cast iron block and replaceable wet cylinder liners, 24-volt starting, and a 43-amp battery charging alternator. Overspeed limit is 2100 rpm.
What is the fuel consumption of the C250 N6 at full load on natural gas? At 100% standby load: 3,440 SCFH. At 75%: 2,692 SCFH. At 50%: 1,951 SCFH. At 25%: 950 SCFH. Fuel inlet pressure at the generator connection must be 381 to 508 mm WC (15 to 20 in. WC).
What control system does the C250 N6 use? The PowerCommand 3.3 — providing full three-phase sensing, AmpSentry protection, paralleling capability (Phase Lock Loop synchronizer, isochronous kW/kVar load sharing), PCCNet and Modbus interface, and InPower service tool compatibility.
Can C250 N6 units be paralleled? Yes. The PowerCommand 3.3 control supports parallel operation, which is useful for facilities needing capacity beyond a single unit or requiring N+1 redundancy on natural gas.
What fuel supply pressure does the C250 N6 require? Fuel inlet pressure at the generator set connection: 381 to 508 mm WC (15 to 20 in. WC). It must be verified with the site gas system before installation.