Overview#
The Cat DG200 is a 200 kW natural gas generator set designed for emergency standby, demand response, and prime power applications. Built on a 10.3-liter V8 turbocharged-aftercooled engine with an electronic regulator and spark ignition, the DG200 carries a U.S. EPA Certified for Non-Emergency Application emissions strategy and is rated for demand response (participating in a demand response or economic dispatch program) in addition to backup power.
The DG200 also accepts propane vapor fuel, though at reduced power ratings (144 ekW emergency standby / 117 ekW prime). Propane gives a fuel option for sites without natural gas service.
Power ratings#
The DG200 offers three operating modes on natural gas at 60 Hz:
- Emergency Standby: 200 ekW -- average power output is 70% of the standby rated ekW
- Demand Response: 200 ekW -- average power output is 70% of the standby rated ekW
- Prime: 157 ekW -- output available with varying load for an unlimited time; average power output is 70% of the prime rated ekW
Engine and alternator#
The 10.3L V8 uses an electronic regulator with spark ignition and an electronic governor that is G2 Class capable per ISO 8528-5 (consult your Cat dealer for site-specific classification). The compression ratio is 9.6:1.
The M2736L4 alternator frame is available in seven voltage configurations (208/120V, 240/120V, 240/139V, 277/480V, 346/600V, 380/220V and 220/127V), all with 105C temperature rise. PMG excitation is listed on all but the 346/600V configuration, which uses AREP excitation.
Physical specifications#
The DG200 measures 117.5 inches long, 63 inches wide, and 72 inches high, with a dry weight of 3924 lb (1780 kg).
Our service experience#
The DG200 is a straightforward gas generator to maintain. The electronic spark ignition system is the primary service item -- spark plugs require regular inspection and replacement. Natural gas fuel quality is critical: ensure gas supply meets minimum pressure requirements at the rail connector and maintain clean fuel filters. The EPA non-emergency certification is what allows this unit to be used in demand response programs.