Cummins · Cummins D6 Commercial Diesel

Cummins C110 D6

112 kW standby / 102 kW prime · Diesel · Liquid-cooled

112 kW diesel standby generator with Cummins 6BT5.9-G6 engine and PowerCommand control. Liquid-cooled, for commercial standby applications.

Cummins Cummins C110 D6 generator — specifications and details
Standby power
112 kW / 102 kW prime
Voltage options
120/240V, 120/208V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Cummins 6BT5.9-G6 · 5.9L
EPA / Emissions
Tier 3

Overview#

The Cummins C110 D6 is a 112 kW / 140 kVA standby diesel generator set in the Cummins commercial lineup. It uses the 6BT5.9-G6 engine — a 5.9-liter, 6-cylinder inline, turbocharged and charge-air-cooled diesel running at 1800 rpm (60 Hz). Prime rating is 102 kW / 128 kVA.

Our Service Experience#

The 6BT5.9 platform is one of the most common engine blocks we service in the Cummins commercial diesel lineup. Parts availability is excellent, and the engine is well-documented. The 5.9-liter inline-6 is a proven workhorse across the 80-150 kW range of Cummins generator sets.

Engineering specifications

Physical

Length
119 in
Width
40 in
Height
58 in
Dry weight
2,500 lb

Fuel system & runtime

Fuel use @ full load
9.5 GPH
Fuel use @ 50% load
5.2 GPH

Documents & downloads

Ready to order this model?

Configure your Cummins C110 D6

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Cummins C110 D6

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

27.3 hours(1.1 days)

Fuel consumption ≈ 7.33 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Cummins C110 D6 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Air filter
Every 500 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
6BT5.9 charge air coolerCoolant in intake, white smoke at startup, loss of powersevere
PowerCommand battery monitoringWeak battery warning, slow crank, failed auto-startmoderate
Spin-on lube oil filter sealOil seepage at filter base, low oil pressure warningminor

Frequently Asked Questions

What are the power ratings of the Cummins C110 D6?
The C110 D6 is rated for 112 kW / 140 kVA standby and 102 kW / 128 kVA prime at 60 Hz (1800 rpm). It uses the Cummins 6BT5.9-G6 engine.
What engine does the Cummins C110 D6 use?
The C110 D6 uses the Cummins 6BT5.9-G6 engine -- a 5.9-liter, 6-cylinder inline, turbocharged and charge-air-cooled diesel running at 1800 rpm.
Can OnPoint Generators service Cummins diesel generators in this power range?
Yes. OnPoint Generators serves the San Francisco Bay Area, Silicon Valley, and broader Northern California with authorized Cummins service. We carry 6BT5.9 parts and provide annual maintenance, load bank testing, and emergency response for the entire 80-125 kW Cummins diesel range.

Compatible equipment

Similar models

Cummins Cummins C100 D6 100 kW liquid-cooled standby generator

Cummins

Cummins C100 D6

100 kW diesel with full Cummins vertical integration. 100% load acceptance in 10 seconds. Single-source warranty.

100 kW standby · Diesel · Liquid-cooled

100 kW EPA Tier 3 diesel standby generator with QSB5-G13 engine and PowerCommand 2.3 control. Sound-attenuated aluminum enclosure, UL 2200 listed, NFPA 110 Level 1 capable.

Tier 33-phasecommercial-standbylight-industrial
Cummins Cummins C125 D6 125 kW liquid-cooled standby generator

Cummins

Cummins C125 D6

125 kW diesel with Cummins QSB5-G6 engine. Top of the QSB5 4-cylinder range. 100% load acceptance in 10 seconds. Single-source warranty.

125 kW standby · Diesel · Liquid-cooled

125 kW EPA Tier 3 diesel standby generator with Cummins QSB5-G6 engine and PowerCommand 1.1 control. Sound-attenuated aluminum enclosure, UL 2200 listed, NFPA 110 Level 1 capable.

Tier 33-phasecommercial-standbylight-industrial
Cummins Cummins C100 N6 100 kW liquid-cooled standby generator

Cummins

Cummins C100 N6

100 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. No diesel logistics.

100 kW standby · Natural Gas / LPG · Liquid-cooled

100 kW natural gas standby generator with QSJ5.9G-G3 engine. 100 kW / 125 kVA standby, PowerCommand controls, AmpSentry protection, UL 2200, EPA certified. Dry weight 2812 lbs.

3-phasecommercial-standbyindustrial-standby

Need service or parts for the Cummins C110 D6?