Cummins · Cummins D6 Commercial Diesel

Cummins C125 D6

125 kW standby / 112.5 kW prime · Diesel · Liquid-cooled

125 kW EPA Tier 3 diesel standby generator with Cummins QSB5-G6 engine and PowerCommand 1.1 control. Available UL 2200 listed; accepts full rated load in a single step per NFPA 110 Level 1.

Cummins Cummins C125 D6 generator — specifications and details
Standby power
125 kW / 112.5 kW prime
Voltage options
120/240V, 120/208V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Cummins QSB5-G6 · 4.5L
EPA / Emissions
Tier 3

Overview#

The Cummins C125 D6 (model designation C125D6C) is a 125 kW standby diesel generator set built on the QSB5-G6 engine -- a 4.5-liter, 4-cylinder turbocharged and charge-air-cooled industrial diesel running at 1800 rpm. Rated at 156 kVA standby and 141 kVA prime at 60 Hz, the C125D6C is the highest-rated model on the QSB5 series generator set specification sheet (50-125 kW at 60 Hz).

The standard controller is PowerCommand 1.1, and aluminum sound attenuated enclosures (Sound Level 1 or Level 2) and an aluminum weather protective enclosure are listed as options. The unit carries EPA Tier 3 emissions certification. The QSB5-G6 engine features a high pressure common rail fuel system, a Holset HX35 wastegated turbocharger, and full-authority electronic controls.

Our Service Experience#

We monitor these units closely for charge air cooler integrity and fuel injection system health. The high-pressure common rail fuel system is sensitive to fuel quality -- we recommend fuel polishing for units that sit idle for extended periods.

Frequently Asked Questions#

What fuel consumption should I expect from the C125D6C? Based on the QSB5-G6 engine specification sheet, fuel consumption at full standby load is approximately 10.3 gallons per hour (39 L/hr).

Is the C125 D6 NFPA 110 Level 1 compliant? The QSB5 series specification sheet states that the generator set accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems. Codes and standards compliance may not be available with all model configurations, so verify the specific configuration with your Cummins distributor.

Engineering specifications

Fuel system & runtime

Fuel use @ full load
10.3 GPH

Ready to order this model?

Configure your Cummins C125 D6

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Cummins C125 D6

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

25.2 hours(1.0 days)

Fuel consumption ≈ 7.95 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Before you buy this generator

Can a second qualified provider program a replacement controller for the Cummins C125 D6, using access issued to us?

Ask every supplier to answer in writing. Service access is part of what you are buying.

Open the 13-question checklist

Frequently Asked Questions

What engine does the Cummins C125 D6 use?
The C125D6C uses the Cummins QSB5-G6, a 4.5-liter, inline-4-cylinder, turbocharged and charge-air-cooled diesel rated at 1800 rpm. EPA Tier 3 certified.
What are the standby and prime ratings of the C125 D6?
Standby rating is 125 kW (156 kVA) at 60 Hz. Prime rating is 112.5 kW (141 kVA). Both at 1800 rpm.
Can OnPoint Generators service the C125 D6 in Northern California?
Yes. OnPoint Generators serves the San Francisco Bay Area, Silicon Valley, and broader Northern California with authorized Cummins service.

Compatible equipment

Similar models

Cummins Cummins C100 D6 100 kW liquid-cooled standby generator

Cummins

Cummins C100 D6

100 kW diesel from Cummins' fully integrated QSB5 series. Accepts full rated load in a single step per NFPA 110 for Level 1 systems.

100 kW standby · Diesel · Liquid-cooled

100 kW standby / 90 kW prime EPA Tier 3 diesel generator set at 60 Hz with the Cummins QSB5-G13 engine. Accepts full rated load in a single step per NFPA 110 for Level 1 systems; available listed to UL 2200.

Tier 33-phasecommercial-standbylight-industrial
Cummins Cummins C150 D6 150 kW liquid-cooled standby generator

Cummins

Cummins C150 D6

150 kW standby diesel generator set with the Cummins QSB7-G5 engine and EPA Tier 3 emissions certification.

150 kW standby · Diesel · Liquid-cooled

150 kW standby, 135 kW prime 60 Hz diesel generator set with the Cummins QSB7-G5 engine, EPA Tier 3 emissions certification and PC 1.1 as the standard controller.

Tier 33-phasecommercial-standbylight-industrial
Cummins Cummins C125 N6 125 kW liquid-cooled standby generator

Cummins

Cummins C125 N6

125 kW natural gas with full Cummins vertical integration. 100% load in 10 seconds. Single-source warranty.

125 kW standby · Natural Gas · Liquid-cooled

125 kW natural gas standby generator with QSJ8.9G engine. 125 kW standby, PowerCommand 2.3 controls, UL 2200, IBC Seismic, NFPA 110 capable. Quiet Connect RS125 series, weight 3915 lbs.

3-phasecommercial-standbyindustrial-standby

Services for the Cummins C125 D6

Need service or parts for the Cummins C125 D6?

We service every major OEM and stock genuine parts for the most common models.