Blue Star Power Systems · Diesel Product Line (Volvo Penta, 100 kW, Tier 4 Final)

New

Blue Star VD100-04FT4

100 kW standby · Diesel · Liquid-cooled

100 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD581VE 5.13L inline-four with SCR/DPF/DOC, DSE DCP7310 controller, 208-600V.

Standby power
100 kW / 100 kW prime
Voltage options
120/240V, 120/208V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Volvo Penta TAD581VE · 5.13L
EPA / Emissions
Tier 4 Final
Alternator
Stamford UCI274D
commercialsmall-commercialretailschoolmunicipalhospital-non-criticalresidential-high-end

Overview#

The Blue Star VD100-04FT4 is a 100-kilowatt EPA Tier 4 Final / EU Stage 5 diesel standby/prime generator built around the Volvo Penta TAD581VE — a 5.13-liter inline-four with full SCR/DPF/DOC triple aftertreatment. This is a current-production active model and the entry point to Blue Star's Volvo Penta Tier 4 Final lineup.

The TAD581VE shares its bore and stroke dimensions with the larger 7.7L TAD851-853GE inline-six, reflecting Volvo Penta's modular engine architecture — the same combustion chamber design scaled from four to six cylinders.

The Volvo Penta TAD581VE platform#

The TAD581VE introduces Volvo Penta's Tier 4 Final engine family to the Blue Star lineup:

Variant selection guide#

The VD100-04FT4 bridges the John Deere T4F range and the larger Volvo Penta T4F models:

When to spec the VD100-04FT4#

Our service experience#

The Volvo Penta TAD581VE is serviced through Volvo Penta's industrial dealer channel. The SCR/DPF/DOC system requires periodic DPF ash cleaning (typically every 4,000-5,000 hours) and regular DEF replenishment. The 18.5-gallon DEF tank is a significant advantage over the John Deere models' 3.8-gallon tank — at typical emergency standby usage, DEF replenishment may only be needed annually rather than at each exercise visit. The DSE DCP7310 controller provides DEF level monitoring and aftertreatment status via the standard CAN J1939 interface.#

Engineering specifications

Physical

Length
110 in
Width
60 in
Height
78 in
Dry weight
4,250 lb

Acoustic

Sound @ 7m, full load
80 dBA
Enclosure
Open

Fuel system & runtime

Fuel use @ full load
6.99 GPH
Fuel use @ 75% load
5.51 GPH
Fuel use @ 50% load
4.05 GPH
DEF tank
18.5 gal

Thermal & ventilation

Heat to coolant
223,860 BTU/hr
Heat radiated
125,700 BTU/hr
Exhaust flow
742 CFM
Exhaust temp
831 °F
Combustion air
325 CFM

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Blue Star VD100-04FT4

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Blue Star VD100-04FT4

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

37.1 hours(1.5 days)

Fuel consumption ≈ 5.39 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Blue Star VD100-04FT4 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
DEF system (SCR catalyst)Derate warning, NOx fault, DEF quality alert4,380+moderate
Fuel qualityInjector fouling, hard starting4,380+moderate
BatteryFailed to start, slow crank8,760+minor

Frequently Asked Questions

What engine is in the VD100-04FT4?
The Volvo Penta TAD581VE — a 5.13-liter inline-four turbocharged-aftercooled diesel rated 175 HP (131 kWm) at 1800 RPM. The TAD58xVE family shares its bore (4.33 in) and stroke (5.31 in) with the larger 7.7L TAD851-853GE inline-six used in Tier 3 models, but with four cylinders instead of six. EPA Tier 4 Final and EU Stage 5 certified with SCR/DPF/DOC triple aftertreatment.
Does the VD100-04FT4 require DEF?
Yes. The VD100-04FT4 uses a full SCR/DPF/DOC aftertreatment system. DEF consumption is approximately 5.1% of fuel consumption, and the integrated DEF tank holds 18.5 gallons — significantly larger than the 3.8-gallon tank on the John Deere models (JD60/JD80). At full load, the 18.5-gallon tank provides over 50 hours of operation.
How does the VD100-04FT4 compare to the VD125-04FT4?
Both use the same 5.13L Volvo Penta inline-four block and share identical physical dimensions (110 x 60 x 78 in) and weight (4,250 lbs). The TAD582VE (VD125) produces 218 HP versus 175 HP for the TAD581VE (VD100). The VD125 consumes more fuel (8.61 vs 6.99 gph) and has a slightly higher DEF consumption rate (5.9% vs 5.1%). Choose the VD100 if 100 kW meets the load study — the lower fuel and DEF consumption provide meaningful operating cost savings.
What emissions certifications does the VD100-04FT4 hold?
Both EPA Tier 4 Final and EU Stage 5 — the most stringent diesel emissions standards currently in force. The dual certification makes this model suitable for global deployments and the most restrictive US jurisdictions, including California CARB requirements for non-emergency applications.

Compatible equipment

Similar models

Blue Star Power Systems

New

Blue Star VD125-04FT4

125 kW standby · Diesel · Liquid-cooled

125 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD582VE 5.13L inline-four with SCR/DPF/DOC, DSE DCP7310 controller, 208-600V.

Tier 4 Final3-phasecommercialsmall-commercial

Blue Star Power Systems

New

Blue Star JD80-03FT4

80 kW standby · Diesel · Liquid-cooled

80 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. John Deere 4045HFG04 4.5L inline-four with SCR/DOC, DSE DCP7310 controller, 208-600V.

Tier 4 Final3-phasecommercialsmall-commercial

Blue Star Power Systems

New

Blue Star JD100-01

100 kW standby · Diesel · Liquid-cooled

100 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 4045HF285 engine with charge air cooling, Stamford UCI274 alternator, DSE DCP7310 controller.

Tier 33-phaselight-commercialcommercial

Blue Star Power Systems

New

Blue Star PD100-01

100 kW standby · Diesel · Liquid-cooled

100 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1104D-E44TAG2 turbocharged intercooled engine, Stamford UCI274C alternator, DSE DCP7310 controller.

Tier 33-phaselight-commercialcommercial

Blue Star Power Systems

New

Blue Star VD100-04FT4MP

100 kW standby · Diesel · Liquid-cooled

100 kW Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TAD581VE four-cylinder engine, Stamford UCI274D alternator, DSE DCP7310 controller, 250-gallon integrated fuel tank.

Tier 4 Final3-phaseconstructiontemporary-power

Blue Star Power Systems

New

Blue Star PD125-01

125 kW standby · Diesel · Liquid-cooled

125 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1106D-E70TAG2 six-cylinder engine with charge air cooling, Stamford UCI274E alternator, DSE DCP7310 controller.

Tier 33-phaselight-commercialcommercial

Need service or parts for the Blue Star VD100-04FT4?

We service every major OEM and stock genuine parts for the most common models.