Hipower Systems · HGM Series (Stationary Natural Gas)

Hipower HGM-65

60 kW standby · Natural Gas / LPG · Liquid-cooled

60 kW stationary natural gas generator. CARB certified. Built in Olathe, Kansas.

Hipower Systems Hipower HGM-65 generator — specifications and details
Standby power
60 kW
Voltage options
120/240V, 120/208V, 277/480V
Frequency / Phase
60 Hz · 1/3-phase
Engine
TBD TBD
EPA / Emissions
EPA Stationary Spark Ignition

Overview#

The Hipower HGM-65 is a 60 kW stationary natural gas standby generator in Hipower's HGM series — a compact natural gas lineup manufactured in Olathe, Kansas. At 60 kW, the HGM-65 provides reliable standby coverage for small-to-mid commercial facilities with existing gas service, eliminating the need for on-site diesel storage and the compliance obligations that accompany it.

CARB certification positions the HGM series for California standby projects where air district compliance is required without a source test. For California facility owners, natural gas standby under CARB certification represents the simplest path to code-compliant emergency power.

Engine Platform#

The HGM-65 engine OEM and model designation has not been confirmed from available OEM documentation and is marked for verification. The unit operates at 1800 RPM on natural gas or LP. Maintenance follows standard spark-ignited gas generator practice: spark plugs and oil changes at 1000-hour intervals, annual gas system inspection.

CARB-Certified for California#

Hipower's HGM series holds CARB certification for stationary natural gas engine applications. California permit-by-rule applies to the HGM-65, enabling standard air district approval without a source test or variance process.

Service and Maintenance#

Our Service Experience#

OnPoint Generators maintains natural gas standby generators throughout Northern California. The HGM-65 is a compact, straightforward unit for small commercial applications where natural gas is already the primary energy source.

Request a quote

Get pricing & lead time on the Hipower HGM-65

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Hipower HGM-65

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

630,000 BTU/hr630.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Service intervals

Manufacturer-recommended intervals for the Hipower HGM-65 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 1000 hours or 12 months
Air filter
Every 500 hours
Spark plugs
Every 1000 hours
Major overhaul
30,000 hours

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Spark plugsErosion from natural gas combustion — replace at 1000-hour intervals1,000+minor
Gas pressure regulatorInlet pressure drift from utility fluctuations — test regulator at each service4,380+minor
Ignition moduleMisfire under low-load conditions — check ignition coil output and spark timing8,000+moderate

Frequently Asked Questions

What is the HGM series?
The HGM is Hipower's stationary natural gas generator series for compact, fixed-installation commercial standby. The HGM-65 sits at 60 kW in the middle of the HGM lineup. Engine OEM and model are unconfirmed. <!-- NEEDS VERIFICATION: HGM-65 engine OEM and model -->
Is the HGM-65 CARB certified?
Yes. Hipower's HGM natural gas series holds CARB certification for California stationary standby applications.
What are the fuel options?
Natural gas and LP. The HGM-65 draws fuel from the building's utility gas service.
What is the difference between the HGM-55 and HGM-65?
The HGM-65 provides 60 kW vs 53 kW on the HGM-55 — a 13% increase suitable for slightly larger standby loads. Both use natural gas and hold CARB certification.
What loads does 60 kW of natural gas standby support?
60 kW covers essential building systems in a small-to-mid commercial building — HVAC, lighting, refrigerated display, POS and networking equipment. Confirm with a load analysis before sizing.
Who services HGM generators in Northern California?
OnPoint Generators services Hipower natural gas generators, including HGM series units, throughout Northern California.

Similar models

Hipower Systems Hipower HNI-60 60 kW liquid-cooled standby generator

Hipower Systems

Hipower HNI-60

Broadest CARB-certified natural gas lineup from a Tier 2 manufacturer — 30 to 1000 kW with PSI and Origin engines.

60 kW standby · Natural Gas / LPG · Liquid-cooled

60 kW standby natural gas generator with Origin 3.6L turbocharged engine. CARB certified for California natural gas standby.

EPA Stationary Spark Ignition3-phasecommercial-standbylight-commercial
Hipower Systems Hipower HRNG-85 66 kW liquid-cooled standby generator

Hipower Systems

Hipower HRNG-85

Trailer-mounted CARB-certified natural gas generator for temporary power — no diesel storage, connects to permanent gas supply on site.

66 kW standby · Natural Gas / LPG · Liquid-cooled

66 kW trailer-mounted natural gas generator. CARB certified. Rental-ready towable unit for temporary power from a permanent gas supply.

EPA Stationary Spark Ignition3-phaserental-fleetconstruction
Hipower Systems Hipower HGM-55 53 kW liquid-cooled standby generator

Hipower Systems

Hipower HGM-55

CARB-certified stationary natural gas standby from Hipower's HGM series — compact, utility-supplied fuel, no on-site storage.

53 kW standby · Natural Gas / LPG · Liquid-cooled

53 kW stationary natural gas generator. CARB certified. Built in Olathe, Kansas.

EPA Stationary Spark Ignition3-phasecommercial-standbylight-commercial

Need service or parts for the Hipower HGM-65?

We service every major OEM and stock genuine parts for the most common models.