Overview#
The Hipower HGM-65 is a 60 kW (77.5 kVA) natural gas standby generator set at 277/480V three-phase. It pairs a General Motors Vortec 5.7L engine with a Marathon Electric 361PSL1602 alternator. The datasheet states the generator set can accept rated load in one step.
Standby ratings at 60 Hz, as printed on the datasheet:
- 120/240V single-phase: not available (N.A.).
- 120/208V three-phase: standby rating natural gas 60 kW (77.5 kVA); LPG 60 kW (77.5 kVA).
- 120/240V Delta three-phase: standby rating natural gas 60 kW (77.5 kVA); LPG 60 kW (77.5 kVA).
- 277/480V three-phase: standby rating natural gas 60 kW (77.5 kVA); LPG 60 kW (77.5 kVA).
- 347/600V three-phase: standby rating natural gas 60 kW (77.5 kVA); LPG 60 kW (77.5 kVA).
The 347/600V configuration is not available as a UL2200 certified generator set.
Engine Platform#
The HGM-65 uses a General Motors Vortec 5.7L: 8 cylinders, cylinder arrangement vee, 350 cu in (5.7 liters) displacement, aspiration Natural, liquid cooled, 4-stroke, running at a crankshaft speed of 1,800 rpm. The datasheet lists a nominal power of 100 hp on natural gas and 108 hp on LPG. The alternator is a Marathon Electric 361PSL1602: four-pole, rotating field, with Class H insulation and an SE350 AVR. The datasheet lists alternator model 361PSL1634 for the 600 volt configuration.
Standards#
The datasheet states the generator set is UL2200 and meets ISO 8528-5. It states that the base set meets NFPA 110, when accessorized with the required equipment and installed per NFPA standards. The engine is listed as EPA certified. The 600 volt configuration is not available as a UL2200 certified generator set.
Our Service Experience#
OnPoint Generators maintains natural gas standby generators throughout Northern California.