Generac · SD Series (Industrial Diesel)

Generac SD100

100 kW standby / 90 kW prime · Diesel · Liquid-cooled

100 kW diesel standby generator. Iveco/FPT 6.7L turbocharged-aftercooled inline-6, EPA Certified Stationary Emergency.

Generac Generac SD100 generator — specifications and details
Standby power
100 kW / 90 kW prime
Voltage options
120/240V, 120/208V, 277/480V, 346/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Iveco/FPT 6.7L · 6.7L
Alternator
Generac 390

Overview#

The Generac SD100 is a 100-kilowatt diesel standby generator powered by an Iveco/FPT 6.7-liter turbocharged and aftercooled inline-six engine. Rated at 100 kW standby and 90 kW prime, it occupies the entry point of Generac's mid-range industrial diesel lineup and is EPA Certified for Stationary Emergency applications.

Generac pairs the 6.7L Iveco with their own Model 390 alternator featuring Class H insulation, permanent magnet excitation, and synchronous brushless design. The Digital H control panel provides full system monitoring with NFPA 110 Level I and II programmability, Modbus communications, and predictive maintenance algorithms.

The Iveco/FPT 6.7L platform#

The 6.7-liter inline-six in the SD100 features mechanical Stanadyne fuel injection, a 16.5:1 compression ratio, and runs at 1800 RPM producing 152 horsepower at rated kW. Piston speed is 1,559 ft/min with BMEP of 165 psi -- moderate figures that indicate a conservatively rated engine platform well suited for standby duty cycles. The 12 VDC electrical system uses a standard battery charging alternator and solenoid-activated starter.

Our service experience#

In Northern California commercial installations, the SD100 is commonly deployed at medical offices, retail centers, and small data rooms. At 7.3 gph full load, fuel consumption is economical for the power class. We recommend maintaining the 50/50 ethylene glycol coolant mix and exercising the unit weekly via the built-in 7-day programmable exerciser. The 120/240 VAC coolant heater should be verified at each service visit, particularly before winter months, as failed heaters are the most common cause of slow-start alarms in standby applications.

Engineering specifications

Physical

Length
128 in
Width
54 in
Height
58 in
Dry weight
4,465 lb

Fuel system & runtime

Fuel use @ full load
7.3 GPH
Fuel use @ 75% load
5.9 GPH
Fuel use @ 50% load
4.2 GPH

Thermal & ventilation

Heat to coolant
269,130 BTU/hr
Exhaust flow
1,022 CFM
Exhaust temp
885 °F
Combustion air
325 CFM
Ventilation air
6,360 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Generac SD100

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Generac SD100

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

35.5 hours(1.5 days)

Fuel consumption ≈ 5.63 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Generac SD100 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationHard starting, filter clogging, reduced power output4,380+moderate
TurbochargerPower loss, excessive smoke under load, oil consumption15,000+moderate
BatteryFailed to start, slow cranking8,760+minor
Coolant heaterLow coolant temperature alarm, slow start in cold weather20,000+minor

Frequently Asked Questions

What engine does the Generac SD100 use?
The Generac SD100 uses an Iveco/FPT 6.7-liter, six-cylinder in-line turbocharged and aftercooled diesel engine running at 1800 RPM. The engine has a bore of 104 mm and stroke of 128 mm with a 16.5:1 compression ratio. It uses mechanical fuel injection (Stanadyne) and is EPA Certified for Stationary Emergency applications.
What is the fuel consumption of the Generac SD100?
At standby rating, the SD100 consumes 7.3 gallons per hour at full load (100%), 5.9 gph at 75% load, 4.2 gph at 50% load, and 2.2 gph at 25% load. Total fuel pump flow (combustion plus return) is 29.1 gph. The fuel pump lift is rated at 3 feet.
What voltages are available for the SD100?
The SD100 is available in single-phase 120/240 VAC (417 amps at 1.0 pf) and three-phase configurations: 120/208 VAC (347 amps), 120/240 VAC (301 amps), 277/480 VAC (150 amps), and 346/600 VAC (120 amps), all at 0.8 power factor. The alternator is a 12-lead design with 2/3 pitch.
What are the dimensions and weight of the SD100?
The open-set SD100 (no base tank) measures 128 x 54 x 58 inches and weighs approximately 4,465 lbs. Various sub-base fuel tank options are available with runtimes from 10 to 90 hours, increasing the height and weight accordingly. Standard and acoustic enclosure options are also available in steel or aluminum.

Compatible equipment

More in the SD Series (Industrial Diesel)

Generac's broadest diesel standby lineup — 10 to 1500 kW across four engine families for commercial and industrial applications.

Similar models

Generac Generac SD080 80 kW liquid-cooled standby generator

Generac

Generac SD080

80 kW industrial diesel with Iveco/FPT 4.5L engine. 10-15% below Kohler at comparable kW. NFPA 110 compliant.

80 kW standby · Diesel · Liquid-cooled

80 kW industrial diesel standby generator. Iveco/FPT 4.5L turbocharged-aftercooled inline-4, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.

3-phasecommercial-standbylight-industrial
Generac Generac SD130 130 kW liquid-cooled standby generator

Generac

Generac SD130

130 kW industrial diesel with Iveco/FPT engine. 10-15% below Kohler pricing. Digital controller with paralleling capability.

130 kW standby · Diesel · Liquid-cooled

130 kW industrial diesel standby generator. Iveco/FPT 6.7L turbocharged-aftercooled inline-6, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.

3-phasecommercial-standbylight-industrial
Generac Generac SG100 100 kW liquid-cooled standby generator

Generac

Generac SG100

100 kW natural gas industrial standby. No on-site diesel storage. 10-15% below Kohler at comparable kW.

100 kW standby · Natural Gas / LPG · Liquid-cooled

100 kW industrial gaseous standby generator. Generac's commercial natural gas/LP platform competing with Kohler KG100 and Cummins C100 N6.

EPA Stationary Spark Ignition3-phasecommercialretail