Blue Star Power Systems · Volvo Penta Diesel Standby

Blue Star VD550-01

550 kW standby · Diesel · Liquid-cooled

550 kW Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1642GE-B 16.1L inline-six with DSE DCP7310 controller, 208-600V output.

Blue Star Power Systems Blue Star VD550-01 generator — specifications and details
Standby power
550 kW
Voltage options
120/208V, 120/240V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Volvo Penta TAD1642GE-B · 16.1L
EPA / Emissions
Tier 2
Alternator
Stamford HCI534E

Overview#

The Blue Star VD550-01 is a 550-kilowatt EPA Tier 2 diesel standby generator built around the Volvo Penta TAD1642GE-B — the highest-output variant of the TAD1640/1641/1642GE-B engine family. At 821 HP, it extracts the maximum from the 16.1L platform. This is a current-production active model.

The VD550-01 shares its physical footprint with the VD500-01 (140 x 72 x 98 in), making it a drop-in upgrade when 500 kW is marginal for the load study.

The Volvo Penta TAD1642GE-B platform#

The TAD1642GE-B tops the updated 16.1L engine family:

Variant selection guide#

The VD550-01 is the top of the TAD1640/1641/1642GE-B range:

When to spec the VD550-01#

Our service experience#

The TAD1642GE-B shares all service procedures, fluid capacities (12.7 gal oil, 15.9 gal coolant), and filter cross-references with the TAD1641GE-B (VD500-01). The self de-aerating fuel system and fuel shut-off valve are service advantages shared across the TAD164xGE-B family. The 94 dBA open-skid sound level requires enclosed installation for all but the most remote sites. The DSE DCP7310 controller and Stamford HCI534 alternator maintain parts commonality across the Blue Star lineup.#

Engineering specifications

Physical

Length
140 in
Width
72 in
Height
98 in
Dry weight
10,225 lb

Acoustic

Sound @ 7m, full load
94 dBA
Enclosure
Open

Fuel system & runtime

Fuel use @ full load
37.4 GPH
Fuel use @ 75% load
28.1 GPH
Fuel use @ 50% load
18.8 GPH

Thermal & ventilation

Heat to coolant
846,240 BTU/hr
Heat radiated
643,440 BTU/hr
Exhaust flow
4,153 CFM
Exhaust temp
954 °F
Combustion air
1,603 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Blue Star VD550-01

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Blue Star VD550-01

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

6.9 hours(0.3 days)

Fuel consumption ≈ 28.85 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Blue Star VD550-01 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Turbocharger(s)Major power loss, heavy exhaust smoke12,000+severe
Fuel quality / degradationInjector fouling, hard starting4,380+moderate
Battery bank (24V)Failed start, slow cranking8,760+minor

Frequently Asked Questions

What engine is in the VD550-01?
The Volvo Penta TAD1642GE-B — a 16.1-liter inline-six turbocharged-aftercooled diesel rated 821 HP (612 kWm) at 1800 RPM. It is the highest-output variant of the TAD1640/1641/1642GE-B engine family, sharing the same block (5.67 in bore, 6.50 in stroke, 16.8:1 compression) as the TAD1641GE-B used in the VD500-01. EPA Tier 2 certified with Volvo Penta EMS 2.4 electronic management.
How does the VD550-01 compare to the VD500-01?
Both use the same 16.1L Volvo Penta block and share the same physical dimensions (140 x 72 x 98 in). The TAD1642GE-B (VD550-01) produces 821 HP versus 768 HP for the TAD1641GE-B (VD500-01). The VD550-01 is 350 lbs heavier (10,225 vs 9,875 lbs) and has a lower altitude deration: 4,920 ft (1,500 m) versus 6,562 ft (2,000 m) for the VD500-01. Both are rated at 94 dBA at full load.
What controller does the VD550-01 use?
The DSE DCP7310 — the same controller used across Blue Star's current diesel lineup. It features CAN bus J1939 communications, RS-485 interface, IP 65 front panel rating, and remote communications via DSE2548 annunciator. cULus Listed and NFPA 110 Level 1 compatible.
What is the altitude deration for the VD550-01?
Rated power is available up to 4,920 ft (1,500 m) at ambient temperatures to 122F (50C). This is lower than the VD500-01's 6,562 ft ceiling because the TAD1642GE-B is tuned closer to the 16.1L block's peak output. For sites above 4,920 ft, the VD500-01 with its 6,562 ft ceiling is the safer specification if 500 kW is sufficient.

Compatible equipment

More in the Volvo Penta Diesel Standby

100–700 kW Volvo Penta diesel standby across Tier 4 Final, Tier 3, and Tier 2 — 22 models, one and three-phase.

Similar models

Blue Star Power Systems Blue Star VD550-04FT4 550 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star VD550-04FT4

Open Basler controller + Volvo Penta engine + Stamford alternator — Tier 4 Final compliant, no proprietary lock-in. Serviceable by any qualified tech.

550 kW standby · Diesel · Liquid-cooled

550 kW standby / 500 kW prime Tier 4 Final diesel generator from Blue Star Power Systems. Volvo Penta TWD1682GE 16.12L inline-six with SCR/DPF/DOC, DSE DCP7310 controller, three-phase 208-600V.

Tier 4 Final3-phaselarge-commercialhospital-non-critical
Blue Star Power Systems Blue Star VD550-04FT4MP 550 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star VD550-04FT4MP

Open Basler controller + Volvo Penta engine + Leroy-Somer alternator — trailer-mounted, no proprietary lock-in. Serviceable by any qualified tech.

550 kW standby · Diesel · Liquid-cooled

550 kW standby / 500 kW prime Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TWD1682GE six-cylinder engine, 572RSL6429 alternator, DSE DCP7310 controller, 550-gallon integrated fuel tank.

Tier 4 Final3-phaseconstructiontemporary-power
Blue Star Power Systems Blue Star VD500-01 500 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star VD500-01

Open Basler controller + Volvo Penta engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech, not just the dealer.

500 kW standby · Diesel · Liquid-cooled

500 kW Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TAD1641GE-B 16.1L inline-six with DSE DCP7310 controller, 208-600V output.

Tier 23-phasecommerciallarge-commercial

Need service or parts for the Blue Star VD550-01?

We service every major OEM and stock genuine parts for the most common models.