Blue Star Power Systems · Diesel Product Line (Volvo Penta, 150 kW, Tier 4 Final)

New

Blue Star VD150-04FT4

150 kW standby · Diesel · Liquid-cooled

150 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD881VE 7.7L inline-six with SCR/DPF/DOC, DSE DCP7310 controller, 208-600V.

Standby power
150 kW / 150 kW prime
Voltage options
120/240V, 120/208V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Volvo Penta TAD881VE · 7.7L
EPA / Emissions
Tier 4 Final
Alternator
Stamford UCI274F
commerciallarge-commercialschoolschool-campusmunicipalhospital-non-criticallight-industrial

Overview#

The Blue Star VD150-04FT4 is a 150-kilowatt EPA Tier 4 Final / EU Stage 5 diesel standby/prime generator built around the Volvo Penta TAD881VE — the Tier 4 Final version of the 7.7L inline-six block used in the Tier 3 VD230/250/275 models. This is a current-production active model.

The transition from the 5.13L TAD58xVE four-cylinder to the 7.7L TAD881VE six-cylinder reflects the step up in kW class — the additional two cylinders provide the displacement needed for 150 kWe with Tier 4 Final aftertreatment.

The Volvo Penta TAD881VE platform#

The TAD881VE is the Tier 4 Final version of the 7.7L engine family:

Variant selection guide#

When to spec the VD150-04FT4#

Our service experience#

The TAD881VE shares its bore and stroke dimensions with the Tier 3 TAD851-853GE family, but the aftertreatment system adds meaningful service complexity. The DPF requires periodic ash cleaning, the SCR system requires DEF replenishment, and the DOC catalyst has its own inspection requirements. The 6.4% DEF ratio means roughly 0.69 gph DEF at full load — plan for DEF checks at every service visit. The 18.5-gallon tank provides adequate runtime for emergency standby, but prime power applications will need more frequent attention. The DSE DCP7310 controller monitors DEF level, aftertreatment temperatures, and regeneration status.#

Engineering specifications

Physical

Length
110 in
Width
60 in
Height
78 in
Dry weight
4,900 lb

Acoustic

Sound @ 7m, full load
82 dBA
Enclosure
Open

Fuel system & runtime

Fuel use @ full load
10.7 GPH
Fuel use @ 75% load
8.44 GPH
Fuel use @ 50% load
6.03 GPH
DEF tank
18.5 gal

Thermal & ventilation

Heat to coolant
324,840 BTU/hr
Heat radiated
192,120 BTU/hr
Exhaust flow
1,049 CFM
Exhaust temp
856 °F
Combustion air
487 CFM

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Blue Star VD150-04FT4

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Blue Star VD150-04FT4

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

24.2 hours(1.0 days)

Fuel consumption ≈ 8.25 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Blue Star VD150-04FT4 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
DEF system (SCR catalyst)Derate warning, NOx fault, DEF quality alert4,380+moderate
Fuel qualityInjector fouling, hard starting4,380+moderate
BatteryFailed to start, slow crank8,760+minor

Frequently Asked Questions

What engine is in the VD150-04FT4?
The Volvo Penta TAD881VE — a 7.7-liter inline-six turbocharged-aftercooled diesel rated 252 HP (185 kWm) at 1800 RPM. This is the Tier 4 Final version of the 7.7L block used in the Tier 3 TAD851-853GE family (VD230-275 models), sharing the same bore (4.33 in) and stroke (5.31 in). EPA Tier 4 Final and EU Stage 5 certified with SCR/DPF/DOC triple aftertreatment.
How does the VD150-04FT4 relate to the Tier 3 VD230-01?
Both use the same 7.7L Volvo Penta inline-six block. The TAD881VE (VD150-04FT4) is the Tier 4 Final version of that same six-cylinder architecture, producing 252 HP with SCR/DPF/DOC aftertreatment, while the Tier 3 TAD851GE (VD230-01) produces 364 HP without aftertreatment. The VD150-04FT4 is rated at 150 kWe — lower than the Tier 3 model because the aftertreatment system and emissions controls reduce net available power.
Does the VD150-04FT4 require DEF?
Yes. DEF consumption is approximately 6.4% of fuel consumption — the highest DEF ratio in the Blue Star T4F lineup at this point. The 18.5-gallon tank provides roughly 27 hours of full-load operation.
What is the altitude deration for the VD150-04FT4?
Rated power is available up to 4,921 ft (1,500 m) at ambient temperatures to 122F (50C). Consistent with other Volvo Penta Tier 4 Final models in the Blue Star lineup.

Compatible equipment

Similar models

Blue Star Power Systems

New

Blue Star VD125-04FT4

125 kW standby · Diesel · Liquid-cooled

125 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD582VE 5.13L inline-four with SCR/DPF/DOC, DSE DCP7310 controller, 208-600V.

Tier 4 Final3-phasecommercialsmall-commercial

Blue Star Power Systems

New

Blue Star VD200-04FT4

200 kW standby · Diesel · Liquid-cooled

200 kW Tier 4 Final diesel standby/prime generator from Blue Star Power Systems. Volvo Penta TAD1180VE 10.8L inline-six with SCR/DPF/DOC, DSE DCP7310 controller, 208-600V.

Tier 4 Final3-phasecommerciallarge-commercial

Blue Star Power Systems

New

Blue Star JD150-01

150 kW standby · Diesel · Liquid-cooled

150 kW Tier 3 diesel standby generator built by Blue Star Power Systems. John Deere 6068HF285 6-cylinder engine, Stamford UCI274/UCDI274 alternator, DSE DCP7310 controller.

Tier 33-phaselight-commercialcommercial

Blue Star Power Systems

New

Blue Star PD150-01

150 kW standby · Diesel · Liquid-cooled

150 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1106D-E70TAG2 six-cylinder engine with charge air cooling, Stamford UCI274F alternator, DSE DCP7310 controller.

Tier 33-phaselight-commercialcommercial

Blue Star Power Systems

New

Blue Star VD150-04FT4MP

150 kW standby · Diesel · Liquid-cooled

150 kW Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TAD881VE six-cylinder engine, Stamford UCI274F alternator, DSE DCP7310 controller, 250-gallon integrated fuel tank.

Tier 4 Final3-phaseconstructiontemporary-power

Blue Star Power Systems

New

Blue Star PD125-01

125 kW standby · Diesel · Liquid-cooled

125 kW Tier 3 diesel standby generator built by Blue Star Power Systems. Perkins 1106D-E70TAG2 six-cylinder engine with charge air cooling, Stamford UCI274E alternator, DSE DCP7310 controller.

Tier 33-phaselight-commercialcommercial

Need service or parts for the Blue Star VD150-04FT4?

We service every major OEM and stock genuine parts for the most common models.