Overview#
The Blue Star NG500-02 is a 500-kilowatt natural-gas-only standby generator built on the PSI 21.9LHO V12 platform. It is rated 500 kWe standby on natural gas at 60 Hz / 1800 RPM. LP fuel is not available on this model. Three-phase only (208V, 240V, 480V, 600V).
The PSI 21.9LHO#
The PSI 21.9LHO is a 21.9-liter V12:
- 764 bHp (570 kWm) at 1800 RPM standby
- 21.9L displacement (1,336 cu in)
- Natural gas only — LP operation not supported
- Standard deration: 1.5% per 10°F above 77°F inlet air temperature; 2.5% per 1,000 ft above 1,200 ft altitude
Alternator configurations#
| Voltage | Phase | Alternator | Connection |
|---|---|---|---|
| 120/208V | 3 | HCI534E | 12-lead WYE |
| 240V | 3 | HCI534E | 12-lead DELTA |
| 277/480V | 3 | HCI534D | 12-lead WYE |
| 347/600V | 3 | HCI534D | 4-lead WYE |
All configurations carry 125°C standby temperature rise and ±0.5% voltage regulation.
When to spec the NG500-02#
- Sites constrained to the 156×86×98 in OPU footprint
- Applications where the standard deration thresholds (77°F / 1,200 ft) are acceptable and LP is not needed
Our service experience#
The PSI 21.9LHO parts cross-reference to the same PSI catalog.