500 kW standby / 450 kW prime · Natural Gas / LPG · Liquid-cooled

450 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

Standby power
500 kW / 450 kW prime
Voltage options
120/208V, 240V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 3-phase
Engine
PSI 32L · 31.8L
EPA / Emissions
EPA Stationary Spark Ignition
Alternator
Stamford HCI534D
large-commercialdata-centerhospital-non-criticalschool-campusmulti-family-largelight-industrial

Overview#

The Blue Star NG500-01P is the prime-rated variant of the NG500-01, delivering 450 kWe continuously on natural gas (350 kWe on LP). It uses the identical PSI 32L V12 platform and physical enclosure as the standby NG500-01. Three-phase only — no single-phase option. The NG500-01P carries a 1-year / 1,500-hour prime warranty.

Standby vs. prime on the NG500 platform#

NG500-01 (Standby)NG500-01P (Prime)
Output NG500 kWe450 kWe
Output LP400 kWe350 kWe
Warranty2 yr / 2,000 hr1 yr / 1,500 hr
NG fuel @ 100%5,878 ft³/hr5,444 ft³/hr
Deration base temp97°F102°F
Deration base altitude4,200 ft5,000 ft
Temp rise125°C standby105°C prime

Both share the same OPU footprint (210×96×103 in, 15,500 lbs) and DSE DCP7310 controller.

Note on deration: The NG500-01P prime variant has better deration tolerance than the standby NG500-01 (102°F / 5,000 ft vs. 97°F / 4,200 ft). This is an unusual reversal of the typical pattern where standby units outperform prime variants on deration.

Alternator configurations#

VoltagePhaseAlternatorConnection
120/208V3Stamford HCI534E12-lead WYE
240V3Stamford HCI534E12-lead DELTA
277/480V3Stamford HCI534D12-lead WYE
347/600V3Stamford HCI534D4-lead WYE

All carry 105°C prime temperature rise and ±0.5% voltage regulation.

When to spec the NG500-01P#

Our service experience#

Service procedures are identical to the NG500-01 standby. Prime-duty use accumulates hours faster — budget accordingly for 12-cylinder spark plug and ignition coil service. Confirm oil and coolant change intervals against PSI's prime-duty maintenance schedule.

Engineering specifications

Physical

Length
210 in
Width
96 in
Height
103 in
Dry weight
15,500 lb

Acoustic

Sound @ 7m, full load
89 dBA
Enclosure
Open

Fuel system & runtime

NG required pressure
11 in WC

Thermal & ventilation

Heat to coolant
1,463,100 BTU/hr
Heat radiated
540,300 BTU/hr
Exhaust flow
2,786 CFM
Exhaust temp
1084 °F
Combustion air
890 CFM
Ventilation air
41,200 CFM

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Blue Star NG500-01P

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Blue Star NG500-01P

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

5,250,000 BTU/hr5250.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Service intervals

Manufacturer-recommended intervals for the Blue Star NG500-01P under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 4000 hours
Air filter
Every 1000 hours
Spark plugs
Every 1500 hours
Major overhaul
15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Turbocharger(s)Significant power loss, heavy exhaust smoke12,000+severe
Ignition system (multi-cylinder)Multiple misfires, output derating1,500+moderate
Charge air coolerReduced output, elevated intake temperatures10,000+moderate

Frequently Asked Questions

What is the prime rating of the NG500-01P?
The Blue Star NG500-01P is rated 450 kWe prime on natural gas and 350 kWe prime on LP at 60 Hz / 1800 RPM, backed by a 1-year / 1,500-hour prime warranty. The paired standby unit is the NG500-01 at 500 kWe.
What are the deration thresholds for the NG500-01P?
The NG500-01P has exceptionally extended deration thresholds: 3% per 10°F above 102°F inlet air temperature and 7% per 1,000 ft above 5,000 ft altitude — the most tolerant deration spec in the Blue Star gaseous lineup. This reflects the PSI 32L engine's thermal headroom even under continuous prime-duty loading.
How does fuel consumption compare between NG500-01 and NG500-01P?
At 100% load: the NG500-01 standby consumes 5,878 ft³/hr NG (500 kW); the NG500-01P prime consumes 5,444 ft³/hr NG (450 kW). The lower consumption at the prime rating reflects the reduced output level, not a more efficient engine — the same 32L V12 is used in both.
Is single-phase output available on the NG500-01P?
No. The NG500-01P is three-phase only, in 208V, 240V, 480V, and 600V configurations — identical to the standby NG500-01.

Compatible equipment

Similar models

Blue Star Power Systems

New

Blue Star NG500-01

500 kW standby · Natural Gas / LPG · Liquid-cooled

500 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG450-01

450 kW standby · Natural Gas / LPG · Liquid-cooled

450 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG500-02

500 kW standby · Natural Gas · Liquid-cooled

500 kW natural-gas-only standby generator from Blue Star Power Systems. PSI 21.9LHO high-output V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V. LP not available.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG600-01

600 kW standby · Natural Gas / LPG · Liquid-cooled

600 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG600-01P

600 kW standby · Natural Gas / LPG · Liquid-cooled

540 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Blue Star Power Systems

New

Blue Star NG650-01

650 kW standby · Natural Gas / LPG · Liquid-cooled

650 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 32L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Need service or parts for the Blue Star NG500-01P?

We service every major OEM and stock genuine parts for the most common models.