Triton Power · TP-V

Triton Power TP-V625-T4F

625 kW standby / 570 kW prime · Diesel · Liquid-cooled

625 kW Tier 4 Final diesel generator with Volvo TWD1673GE engine. For commercial, industrial, and data center standby applications.

Triton Power Triton Power TP-V625-T4F generator — specifications and details
Standby power
625 kW / 570 kW prime
Voltage options
120/208V, 277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
Volvo TWD1673GE · 16.12L
EPA / Emissions
Tier 4 Final
Alternator
Leroy Somer

Overview#

The Triton Power TP-V625-T4F is a diesel generator rated 625 kW / 784 kVA standby and 570 kW / 713 kVA prime at 60 Hz, powered by the Volvo TWD1673GE turbocharged engine with 16.12 L displacement (655 kWm / 878 HP at 1800 RPM), listed as Tier 4 Final. The engine is paired with a Leroy Somer alternator, and the enclosed unit's fuel tank is listed as 1000 L.

Three-phase output is listed at 120/208 and 277/480 V, and the sheet lists a Deep Sea 7420 digital controller. Triton lists the unit as available in open, enclosed and mobile versions, with 125% full containment for fluids and a sub-base tank up to 45 hours. It is suited to construction sites, rental fleets, and mobile power applications.

Our service experience#

Before specifying the TP-V625-T4F, confirm engine parts and service support for your site, as you would for any Volvo-powered unit.

Engineering specifications

Fuel system & runtime

Fuel use @ full load
34.05 GPH
Fuel use @ 75% load
25.81 GPH
Fuel use @ 50% load
17.91 GPH

Ready to order this model?

Configure your Triton Power TP-V625-T4F

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Triton Power TP-V625-T4F

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

7.6 hours(0.3 days)

Fuel consumption ≈ 26.27 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Frequently Asked Questions

What engine powers the Triton TP-V625-T4F?
Triton's sheet lists a Volvo TWD1673GE turbocharged diesel engine with 16.12 L displacement, Tier 4 Final, at 1800 RPM, paired with a Leroy Somer alternator.
What is the fuel tank capacity of the TP-V625-T4F?
Triton's sheet lists a fuel tank of 1000 L for the enclosed unit. It also lists 125% full containment for fluids and a sub-base tank up to 45 hours.

Why we recommend Triton Power

Triton Power is our value brand for mobile and portable diesel generators, and an emerging option for industrial standby. When MQ Power's pricing is a stretch or lead times are too long, Triton delivers comparable capability at a lower price point with faster availability.

We are developing our Triton Power sales relationship and building fleet experience. Every engine platform Triton uses — Perkins, John Deere, Kubota, Scania, Volvo — is one we already service daily across other brands. Triton's open architecture means our technicians can maintain these units with standard tooling and widely available parts.

See all Triton Power generators →

Similar models

Triton Power Triton Power TP-V550-T4F 550 kW liquid-cooled standby generator

Triton Power

Triton Power TP-V550-T4F

550 kW standby · Diesel · Liquid-cooled

550 kW Tier 4 Final diesel generator with Volvo TWD1672GE engine. For commercial, industrial, and data center standby applications.

Tier 4 Final3-phasecommercial-standbyindustrial

Triton Power

Triton Power TP-V600-T2-UL

600 kW standby · Diesel · Liquid-cooled

600 kW Tier 2 UL-listed diesel generator with Volvo TAD1641GE engine. For commercial and industrial standby applications.

Tier 23-phasecommercial-standbyindustrial
Triton Power Triton Power TP-P600-T2-UL 600 kW liquid-cooled standby generator

Triton Power

Triton Power TP-P600-T2-UL

600 kW standby · Diesel · Liquid-cooled

600 kW Tier 2 diesel generator with Perkins 2806C-E18TAG3 engine. UL2200-listed for commercial, industrial, and data center standby.

Tier 23-phasecommercial-standbyindustrial

Services for the Triton Power TP-V625-T4F

Need service or parts for the Triton Power TP-V625-T4F?

We service every major OEM and stock genuine parts for the most common models.

Last reviewed: