Triton Power · TP-V

Triton Power TP-V600-T2-UL

600 kW standby / 545 kW prime · Diesel · Liquid-cooled

600 kW Tier 2 UL-listed diesel generator with Volvo TAD1641GE engine. For commercial and industrial standby applications.

Standby power
600 kW / 545 kW prime
Voltage options
120/208V, 277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
Volvo TAD1641GE · 16.1L
EPA / Emissions
Tier 2
Alternator
Leroy Somer LSA47.2

Overview#

The Triton Power TP-V600-T2-UL is a 600 kW diesel standby generator powered by the Volvo TAD1641GE turbocharged inline six-cylinder engine with 16.1 L displacement. Rated at 600 kW / 750 kVA standby and 545 kW / 681 kVA prime, this unit is designed for stationary emergency standby applications. It carries UL2200 listing and meets EPA Tier 2 emissions standards.

Paired with a Leroy Somer alternator, the TP-V600-T2-UL delivers three-phase power at 120/208V and 277/480V configurations. The Volvo TAD1641GE is a proven platform in the 500-600 kW class, widely supported through Volvo Penta's global dealer network. At 600 kW, this unit bridges Triton's Volvo-powered lineup between the Tier 4 Final 550 kW model and the 625 kW Tier 4 Final offering.

Our service experience#

The Volvo TAD1641GE is a well-established engine in the power generation market, with strong parts availability and service support. As a Tier 2 UL-listed unit, the TP-V600-T2-UL is commonly specified for permanent emergency standby installations in commercial buildings, hospitals, and data centers where code compliance and reliability are the primary considerations.

Engineering specifications

Fuel system & runtime

Integral fuel tank
264 gal

Ready to order this model?

Configure your Triton Power TP-V600-T2-UL

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Triton Power TP-V600-T2-UL

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

8.1 hours(0.3 days)

Fuel consumption ≈ 32.40 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Frequently Asked Questions

What engine powers the Triton TP-V600-T2-UL?
The TP-V600-T2-UL uses a Volvo TAD1641GE turbocharged inline six-cylinder diesel engine with 16.1 L displacement. It meets EPA Tier 2 emissions standards and is rated for 1800 RPM operation.
Is the TP-V600-T2-UL UL-listed?
Yes, the TP-V600-T2-UL carries UL2200 listing for stationary engine generator assemblies, making it suitable for emergency standby applications where code compliance is required.
How does the TP-V600-T2-UL compare to the TP-V550-T4F?
The TP-V600-T2-UL provides 50 kW more standby power using the Volvo TAD1641GE engine with Tier 2 emissions certification and UL2200 listing for stationary emergency standby. The TP-V550-T4F uses the Volvo TWD1672GE with Tier 4 Final certification for nonroad and mobile applications.

Similar models

Triton Power Triton Power TP-V550-T4F 550 kW liquid-cooled standby generator

Triton Power

Triton Power TP-V550-T4F

550 kW standby · Diesel · Liquid-cooled

550 kW Tier 4 Final diesel generator with Volvo TWD1672GE engine. For commercial, industrial, and data center standby applications.

Tier 4 Final3-phasecommercial-standbyindustrial
Triton Power Triton Power TP-P600-T2-UL 600 kW liquid-cooled standby generator

Triton Power

Triton Power TP-P600-T2-UL

600 kW standby · Diesel · Liquid-cooled

600 kW Tier 2 diesel generator with Perkins 2806C-E18TAG3 engine. UL2200-listed for commercial, industrial, and data center standby.

Tier 23-phasecommercial-standbyindustrial

Triton Power

Triton Power TP-V625-T4F

625 kW standby · Diesel · Liquid-cooled

625 kW Tier 4 Final diesel generator with Volvo TWD1673GE engine. For commercial, industrial, and data center standby applications.

Tier 4 Final3-phasecommercial-standbyindustrial

Need service or parts for the Triton Power TP-V600-T2-UL?

We service every major OEM and stock genuine parts for the most common models.