Triton Power · TP-JD

Triton Power TP-JD70-T4F

70 kW standby / 63 kW prime · Diesel · Liquid-cooled

70 kW Tier 4 Final diesel generator with John Deere 4045HFG04 engine. Turbocharged 4.5L inline-4 with Leroy Somer alternator and 180-gallon fuel tank.

Standby power
70 kW / 63 kW prime
Voltage options
120/208V, 277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
John Deere 4045HFG04 · 4.5L
EPA / Emissions
Tier 4 Final
Alternator
Leroy Somer LSA44.3

Overview#

The Triton Power TP-JD70-T4F is a 70 kW diesel standby generator powered by the John Deere 4045HFG04 turbocharged four-cylinder engine with 4.5 L displacement. Paired with a Leroy Somer alternator, this unit delivers reliable three-phase power at 1800 RPM while meeting EPA Tier 4 Final emissions standards. The 680-liter (180-gallon) integral fuel tank supports extended runtime for commercial standby and industrial applications.

With a sound level of 66 dBA, the TP-JD70-T4F balances power output with noise control suitable for commercial installations. The unit is available in 120/208V and 277/480V three-phase configurations, serving the mid-range commercial market between the 50 kW and 88 kW Triton offerings.

Our service experience#

The John Deere 4045 engine platform is one of the most widely serviced four-cylinder diesel engines in the industrial generator market, with strong parts availability through John Deere's dealer network. At 70 kW standby, the TP-JD70-T4F competes directly with Kohler and Cummins units in the light commercial segment at a competitive acquisition cost. The Tier 4 Final aftertreatment system requires periodic DPF monitoring, but the 4045 platform's reputation for durability and straightforward maintenance offsets that added complexity.

Engineering specifications

Physical

Length
124.4 in
Width
46.1 in
Height
70.9 in
Dry weight
4,960 lb

Acoustic

Sound @ 7m, full load
66 dBA

Fuel system & runtime

Integral fuel tank
113.6 gal
Fuel use @ full load
3.43 GPH
Fuel use @ 75% load
2.64 GPH
Fuel use @ 50% load
1.85 GPH

Ready to order this model?

Configure your Triton Power TP-JD70-T4F

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Triton Power TP-JD70-T4F

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

42.9 hours(1.8 days)

Fuel consumption ≈ 2.65 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Frequently Asked Questions

What engine powers the TP-JD70-T4F?
The TP-JD70-T4F uses a John Deere 4045HFG04 turbocharged four-cylinder engine with 4.5 L displacement, running at 1800 RPM and meeting EPA Tier 4 Final emissions standards.
What is the difference between standby and prime power ratings?
The unit is rated at 70 kW for standby applications (backup power during outages) and 63 kW for prime power (continuous duty with variable load). Standby ratings assume the generator is not the sole source of power.
How large is the fuel tank on the TP-JD70-T4F?
The generator includes a 680-liter (180-gallon) integral fuel tank, providing extended runtime without the need for external fuel storage.

Similar models

Triton Power Triton Power TP-JD50-T4F 50 kW liquid-cooled standby generator

Triton Power

Triton Power TP-JD50-T4F

50 kW standby · Diesel · Liquid-cooled

50 kW Tier 4 Final diesel generator with John Deere 3029HG530 engine. UL2200-listed for commercial standby with 92.5-gallon integral fuel tank.

Tier 4 Final3-phasecommercial-standbyretail-large

Triton Power

Triton Power TP-JD88-T4F

88 kW standby · Diesel · Liquid-cooled

88 kW / 110 kVA Tier 4 Final diesel generator with John Deere 4045HFG04 engine. Turbocharged 4.5L inline-4 with Leroy Somer LSA44.3 alternator and 180-gallon fuel tank.

Tier 4 Final3-phasecommercial-standbyindustrial
Triton Power Triton Power TP-P80-T3-UL 80 kW liquid-cooled standby generator

Triton Power

Triton Power TP-P80-T3-UL

80 kW standby · Diesel · Liquid-cooled

80 kW Tier 3 diesel generator with Perkins 1104D-E44TAG1 engine. UL2200-listed for commercial standby and institutional applications.

Tier 33-phasecommercial-standbyeducation

Need service or parts for the Triton Power TP-JD70-T4F?

We service every major OEM and stock genuine parts for the most common models.

Last reviewed: