Generac · SD Series (Industrial Diesel)

Generac SD030T

30 kW standby / 27 kW prime · Diesel · Liquid-cooled

30 kW industrial diesel standby generator. Tier 4 Final certified. Perkins turbocharged inline-4, EPA Tier 4 Final, Digital H control with NFPA 110 Level I/II.

Standby power
30 kW / 27 kW prime
Voltage options
120/240V, 120/208V, 277/480V, 346/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
Perkins 2.2L · 2.2L
EPA / Emissions
Tier 4 Final
Alternator
Generac K0025124Y21

Overview#

The Generac SD030T is a 30-kilowatt Tier 4 Final industrial diesel standby generator. Like its sibling the SD025T, the "T" designation indicates EPA Tier 4 Final certification with diesel particulate filter aftertreatment. This positions the SD030T for installations where non-emergency operating hours or local air quality regulations demand Tier 4 Final compliance.

Built on the Perkins 2.2-liter turbocharged inline-four platform, the SD030T pushes this engine closer to its rated capacity compared to the SD025T. The DPF system manages particulate emissions to meet Tier 4 Final standards, while the Digital H controller provides NFPA 110 Level I/II programmable operation, Modbus communications, and predictive maintenance monitoring.

Our Service Experience#

The SD030T shares the same DPF maintenance profile as the SD025T — regular exercise under load is essential to prevent soot buildup. At 30 kW, the Perkins 2.2L is working harder than in the 20-25 kW models, which actually benefits DPF health by producing higher exhaust temperatures during exercise. Monitor exhaust backpressure at every service visit and schedule forced regeneration if the unit runs fewer than 4 hours per month. The cooling system runs warmer at this power level — verify coolant condition and heater function semi-annually.

Engineering specifications

Physical

Length
83.6 in
Width
35 in
Height
46.3 in
Dry weight
1,291 lb

Fuel system & runtime

Fuel use @ full load
2.6 GPH
Fuel use @ 75% load
2 GPH
Fuel use @ 50% load
1.4 GPH

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Generac SD030T

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Generac SD030T

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

99.7 hours(4.2 days)

Fuel consumption ≈ 2.01 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Generac SD030T under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
DPF aftertreatment systemHigh backpressure alarm, forced regen required, soot accumulation2,000+moderate
Fuel quality / degradationHard starting, filter clogging, reduced power output4,380+moderate
BatteryFailed to start, slow cranking8,760+minor

Frequently Asked Questions

What makes the SD030T different from the SD035?
The SD030T is EPA Tier 4 Final certified with DPF aftertreatment, allowing operation in both emergency and non-emergency applications. The SD035 is only certified for stationary emergency use. Despite the lower kW rating, the SD030T costs more than the SD035 due to the Tier 4 Final aftertreatment system. Choose the SD030T when regulations require Tier 4 Final compliance.
What is the fuel consumption of the Generac SD030T?
The SD030T consumes approximately 2.6 gallons per hour at full load, 2.0 gph at 75% load, and 1.4 gph at 50% load. DPF regeneration cycles add modest additional fuel consumption periodically.
What voltages are available for the SD030T?
The SD030T is available in single-phase 120/240V and three-phase configurations: 120/208V, 120/240V, 277/480V, and 346/600V at 60 Hz.

Compatible equipment

Similar models

Generac

Generac SD025T

25 kW Tier 4 Final diesel — meets non-emergency EPA requirements. Perkins engine with DPF aftertreatment. Largest dealer network.

25 kW standby · Diesel · Liquid-cooled

25 kW industrial diesel standby generator. Tier 4 Final certified. Perkins turbocharged inline-4, EPA Tier 4 Final, Digital H control with NFPA 110 Level I/II.

Tier 4 Final3-phasecommercial-standbylight-industrial
Generac Generac SD035 35 kW liquid-cooled standby generator

Generac

Generac SD035

35 kW industrial diesel at 10-15% below Kohler equivalent. Generac 3.4L engine. Largest dealer network (10,000+).

35 kW standby · Diesel · Liquid-cooled

35 kW industrial diesel standby generator. Generac 3.4L turbocharged-aftercooled inline-4, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.

3-phasecommercial-standbylight-industrial
Generac Generac SD020 20 kW liquid-cooled standby generator

Generac

Generac SD020

20 kW industrial diesel with Perkins engine. 10-15% below Kohler at comparable kW. NFPA 110 Level I/II ready.

20 kW standby · Diesel · Liquid-cooled

20 kW industrial diesel standby generator. Perkins 2.2L turbocharged inline-4, EPA Certified Stationary Emergency, Digital H control with NFPA 110 Level I/II.

3-phasecommercial-standbylight-industrial