Blue Star Power Systems · PSI Large Gaseous (265-500 kW)

Blue Star NG425-01

425 kW standby · Natural Gas / LPG · Liquid-cooled

425 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

Blue Star Power Systems Blue Star NG425-01 generator — specifications and details
Standby power
425 kW
Voltage options
120/208V, 240V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 3-phase
Engine
PSI 21.9L · 21.9L
EPA / Emissions
EPA Stationary Spark Ignition
Alternator
Stamford S4L1D-G41

Overview#

The Blue Star NG425-01 is a 425-kilowatt natural gas / LP standby generator built on the PSI 21.9-liter V12 platform. It is rated 425 kWe standby on natural gas and 300 kWe on LP at 60 Hz / 1800 RPM. Three-phase only (208V, 240V, 480V, 600V). This model shares its engine, footprint, and enclosure with the NG400-01 and NG450-01, providing stepped standby capacity on the same physical base.

The PSI 21.9L V12#

The PSI 21.9L is a 1,338-cubic-inch (21.9-liter) V12 turbocharged-aftercooled spark-ignition engine:

  • 684 bHp (510 kWm) at 1800 RPM standby — common rating across NG400/NG425/NG450
  • 10.5:1 compression ratio, natural gas optimized
  • Purpose-built for stationary spark-ignition — not a diesel or automotive conversion
  • EPA Stationary Spark Ignition certified under 40 CFR 60 Subpart JJJJ

Alternator configurations#

VoltagePhaseAlternatorConnection
120/208V3Stamford HCI534D12-lead WYE
240V3Stamford HCI534D12-lead DELTA
277/480V3Stamford S4L1D-G4112-lead WYE
347/600V3Stamford HCI534C4-lead WYE

All configurations carry 125°C standby temperature rise and ±0.5% voltage regulation.

When to spec the NG425-01#

  • 350–425 kW standby loads on natural gas or LP (three-phase sites)
  • Where the standard 77°F / 1,200 ft deration thresholds are acceptable
  • Facilities preferring the NG425-01's slight output step-up over the NG400-01 without moving to a larger footprint

Our service experience#

The PSI 21.9L V12 is one of the highest-volume platforms in Blue Star's large-gaseous line. Service procedures — spark plugs, ignition coils, charge-air cooler hoses, oil and air filters — are consistent with the NG400-01. The DSE DCP7310 controller is identical across the NG400/425/450 range, keeping technician training requirements flat across units.

Engineering specifications

Physical

Length
156 in
Width
86 in
Height
98 in
Dry weight
10,925 lb

Acoustic

Sound @ 7m, full load
87 dBA
Enclosure
Open

Fuel system & runtime

NG required pressure
11 in WC

Thermal & ventilation

Heat to coolant
1,760,700 BTU/hr
Heat radiated
524,640 BTU/hr
Exhaust flow
2,529 CFM
Exhaust temp
1136 °F
Combustion air
829 CFM
Ventilation air
39,995 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Blue Star NG425-01

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Blue Star NG425-01

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

4,462,500 BTU/hr≈ 4462.5 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Service intervals

Manufacturer-recommended intervals for the Blue Star NG425-01 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 4000 hours
Air filter
Every 1000 hours
Spark plugs
Every 1500 hours
Major overhaul
≈ 15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Turbocharger(s)Significant power loss, heavy exhaust smoke12,000+severe
Ignition system (multi-cylinder)Multiple misfires, output derating1,500+moderate
Charge air coolerReduced output, elevated intake temperatures10,000+moderate

Frequently Asked Questions

What is the standby rating of the NG425-01?
The Blue Star NG425-01 is rated 425 kWe standby on natural gas and 300 kWe standby on LP at 60 Hz / 1800 RPM. The LP-to-NG ratio at standby (71%) is typical for the PSI 21.9L V12 platform. Deration factors are standard: 1.5% per 10°F above 77°F inlet air temperature and 2.5% per 1,000 ft above 1,200 ft altitude.
What engine is in the NG425-01?
The PSI 21.9L — a 21.9-liter (1,338 cu in) V12 turbocharged-aftercooled spark-ignition engine producing 684 bHp (510 kWm) at 1800 RPM standby. The 21.9L V12 is the same platform used in the Blue Star NG400-01, NG425-01, and NG450-01 standby units, with electrical output tuned by the generator control system.
Is the NG425-01 available in single-phase?
No. The NG425-01 is three-phase only — 208V, 240V, 480V, and 600V configurations. Single-phase output is only available on Blue Star gaseous units up to 265 kW.
How does the NG425-01 compare to the NG400-01 and NG450-01?
All three use the PSI 21.9L V12 (684 bHp standby) and share the same 156×86×98 in footprint. The NG400-01 produces 400 kWe standby (300 kWe LP), the NG425-01 produces 425 kWe standby (300 kWe LP), and the NG450-01 produces 450 kWe standby (300 kWe LP). Selecting among them is primarily a matter of load margin — each shares identical alternator models at the 208V and 600V configurations.

Compatible equipment

More in the PSI Large Gaseous (265-500 kW)

265–500 kW natural gas and LP standby on PSI V8 and V12 platforms — structural steel base, prime and standby variants.

Similar models

Blue Star Power Systems Blue Star NG400-01 400 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG400-01

Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. Non-proprietary components serviceable by any qualified tech.

400 kW standby · Natural Gas / LPG · Liquid-cooled

400 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L turbocharged V12, DSE DCP7310 controller, structural steel base, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialhotel
Blue Star Power Systems Blue Star NG400-01P 400 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG400-01P

Open Basler controller + PSI V12 engine + Stamford alternator — prime-rated, no proprietary lock-in. Serviceable by any qualified tech.

400 kW standby · Natural Gas / LPG · Liquid-cooled

375 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 21.9L V12, DSE DCP7310 controller, structural steel base, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialhotel
Blue Star Power Systems Blue Star NG450-01 450 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG450-01

Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. Non-proprietary components serviceable by any qualified tech.

450 kW standby · Natural Gas / LPG · Liquid-cooled

450 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center

Services for the Blue Star NG425-01

Need service or parts for the Blue Star NG425-01?

We service every major OEM and stock genuine parts for the most common models.

Last reviewed: