Blue Star Power Systems · PSI Large Gaseous (265-500 kW)

Blue Star NG400-01P

400 kW standby / 375 kW prime · Natural Gas / LPG · Liquid-cooled

375 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 21.9L V12, DSE DCP7310 controller, structural steel base, three-phase 208-600V.

Blue Star Power Systems Blue Star NG400-01P generator — specifications and details
Standby power
400 kW / 375 kW prime
Voltage options
120/208V, 240V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 3-phase
Engine
PSI 21.9L · 21.9L
EPA / Emissions
EPA Stationary Spark Ignition
Alternator
Stamford S4L1D-F41

Overview#

The Blue Star NG400-01P is the prime-rated variant of the NG400-01, delivering 375 kWe continuously on natural gas (250 kWe on LP). It uses the identical PSI 21.9L V12 platform and physical enclosure as the standby NG400-01. Three-phase only — no single-phase option.

Standby vs. prime on the NG400 platform#

NG400-01 (Standby)NG400-01P (Prime)
Output NG400 kWe375 kWe
Output LP300 kWe250 kWe
Warranty2 yr / 2,000 hr1 yr / 1,500 hr
NG fuel @ 100%4,521 ft³/hr4,232 ft³/hr
Deration base97°F / 3,200 ft77°F / 1,200 ft
Temp rise125°C standby105°C prime

Both share the same OPU footprint (156 × 86 × 98 in, 10,850 lbs) and DSE DCP7310 controller.

Note on deration: The NG400-01P prime variant uses standard deration thresholds (77°F / 1,200 ft), while the standby NG400-01 has extended tolerance (97°F / 3,200 ft). At high-altitude or high-ambient sites, verify which rating applies to the duty cycle before specifying.

Alternator configurations#

The NG400-01P is three-phase only:

VoltagePhaseAlternatorConnection
120/208V3Stamford HCI534C12-lead WYE
240V3Stamford HCI534C12-lead DELTA
277/480V3Stamford S4L1D-F4112-lead WYE
347/600V3Stamford HCI534C4-lead WYE

All carry 105°C prime temperature rise and ±0.5% voltage regulation.

When to spec the NG400-01P#

  • 300–375 kW continuous or prime duty on natural gas or LP (three-phase only)
  • Large commercial, hospitality, hospital, or data center facilities with confirmed prime-duty load profiles
  • Projects requiring prime-rated certification at 400 kW class on gaseous fuel

Our service experience#

Service procedures are identical to the NG400-01. The prime-duty use pattern means higher annual hour accumulation on the V12 — budget for 12-cylinder spark plug and ignition coil service (more frequent than standby units) and confirm oil/coolant change intervals with PSI's prime-duty maintenance schedule.

Engineering specifications

Physical

Length
156 in
Width
86 in
Height
98 in
Dry weight
10,850 lb

Acoustic

Sound @ 7m, full load
87 dBA
Enclosure
Open

Fuel system & runtime

NG required pressure
11 in WC

Thermal & ventilation

Heat to coolant
1,539,180 BTU/hr
Heat radiated
460,320 BTU/hr
Exhaust flow
2,332 CFM
Exhaust temp
1052 °F
Combustion air
717 CFM
Ventilation air
30,000 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Blue Star NG400-01P

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Blue Star NG400-01P

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

4,200,000 BTU/hr≈ 4200.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Service intervals

Manufacturer-recommended intervals for the Blue Star NG400-01P under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 4000 hours
Air filter
Every 1000 hours
Spark plugs
Every 1500 hours
Major overhaul
≈ 15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Turbocharger(s)Significant power loss, heavy exhaust smoke12,000+severe
Ignition system (multi-cylinder)Multiple misfires, output derating1,500+moderate
Charge air coolerReduced output, elevated intake temperatures10,000+moderate

Frequently Asked Questions

What is the prime rating of the NG400-01P?
The Blue Star NG400-01P is rated 375 kWe prime on natural gas (250 kWe on LP) at 60 Hz / 1800 RPM, backed by a 1-year / 1,500-hour prime warranty. The standby counterpart is the NG400-01 at 400 kWe.
What are the deration factors for the NG400-01P?
The NG400-01P uses the standard deration factors: 1.5% per 10°F above 77°F inlet air temperature; 2.5% per 1,000 ft above 1,200 ft altitude. This differs from the standby NG400-01, which has extended tolerance (97°F and 3,200 ft). Confirm site conditions when comparing prime vs. standby specifications at altitude or in hot climates.
How does fuel consumption compare between NG400-01 and NG400-01P?
At 100% standby load (400 kW), the NG400-01 consumes 4,521 ft³/hr NG. At 100% prime load (375 kW), the NG400-01P consumes 4,232 ft³/hr NG — reflecting the lower prime output. LP at 100% prime is 1,185 ft³/hr vs. 1,401 ft³/hr at standby.
Is single-phase output available on the NG400-01P?
No. The NG400-01P is three-phase only, in 208V, 240V, 480V, and 600V configurations — identical to the standby NG400-01.
What alternators does the NG400-01P use?
Identical to the standby NG400-01: Stamford HCI534C for 208V and 240V three-phase; Stamford S4L1D-F41 for 480V; Stamford HCI534C for 600V. All carry 105°C prime temperature rise and ±0.5% voltage regulation.

Compatible equipment

More in the PSI Large Gaseous (265-500 kW)

265–500 kW natural gas and LP standby on PSI V8 and V12 platforms — structural steel base, prime and standby variants.

Similar models

Blue Star Power Systems Blue Star NG400-01 400 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG400-01

Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. Non-proprietary components serviceable by any qualified tech.

400 kW standby · Natural Gas / LPG · Liquid-cooled

400 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L turbocharged V12, DSE DCP7310 controller, structural steel base, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialhotel
Blue Star Power Systems Blue Star NG425-01 425 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG425-01

Open Basler controller + PSI V12 engine + Stamford alternator — no proprietary lock-in. Non-proprietary components serviceable by any qualified tech.

425 kW standby · Natural Gas / LPG · Liquid-cooled

425 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 21.9L V12 turbocharged-aftercooled, DSE DCP7310 controller, three-phase 208-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialdata-center
Blue Star Power Systems Blue Star NG350-02 350 kW liquid-cooled standby generator

Blue Star Power Systems

Blue Star NG350-02

Open Basler controller + PSI high-output engine + Stamford alternator — no proprietary lock-in. Serviceable by any qualified tech.

350 kW standby · Natural Gas · Liquid-cooled

350 kW natural gas standby generator from Blue Star Power Systems. PSI 14.6LHO high-output V8, DSE DCP7310 controller, structural steel base, three-phase 208-600V. Natural gas only — no LP rating.

EPA Stationary Spark Ignition3-phaselarge-commercialhotel

Services for the Blue Star NG400-01P