Blue Star Power Systems · Gaseous Product Line (PSI 8.1L)

New

Blue Star NG150-01P

150 kW standby / 125 kW prime · Natural Gas / LPG · Liquid-cooled

125 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 8.1LT inline-six, DSE DCP7310 controller, 208-600V, continuous prime duty.

Standby power
150 kW / 125 kW prime
Voltage options
120/240V, 120/208V, 240V, 277/480V, 347/600V
Frequency / Phase
60 Hz · 1/3-phase
Engine
PSI 8.1LT · 8.1L
EPA / Emissions
EPA Stationary Spark Ignition
Alternator
Stamford UCI274F
commerciallight-commercialmedium-commercialschoolmulti-familyhotellight-industrial

Overview#

The Blue Star NG150-01P is the prime-rated variant of the NG150-01, rated 125 kWe continuous on natural gas (95 kWe on LP). It is built on the same PSI 8.1LT inline-six platform as the standby NG150-01 and shares an identical physical footprint. The "-P" suffix designates prime-continuous duty: unlimited hours per year at rated load, backed by a 1-year / 1,500-hour prime warranty.

Standby vs. prime: what the rating change means#

Prime-rated units are intended for applications where the generator runs as a primary or continuous power source rather than emergency backup:

When to spec the NG150-01P#

Alternator configurations#

The NG150-01P uses the same alternator selection as the NG150-01, with 105°C prime temperature rise rating (vs. 125°C standby):

VoltagePhaseAlternatorConnection
120/240V1Stamford UCDI274J112-lead DD
120/208V3Stamford UCI274G12-lead WYE
240V3Stamford UCI274G12-lead DELTA
277/480V3Stamford UCI274F12-lead WYE
347/600V3Stamford UCI274F4-lead WYE

Our service experience#

Service intervals and parts cross-references are identical to the NG150-01. The primary difference at service is the prime-duty hour accumulation — plan for more frequent oil and spark plug changes relative to a standby unit that runs infrequently. PSI recommends confirming service intervals with their published prime-duty maintenance schedule when the generator is used for continuous operation.

Engineering specifications

Physical

Length
110 in
Width
60 in
Height
66 in
Dry weight
5,225 lb

Acoustic

Sound @ 7m, full load
82 dBA
Enclosure
Open

Fuel system & runtime

NG required pressure
11 in WC

Thermal & ventilation

Heat to coolant
561,420 BTU/hr
Heat radiated
151,980 BTU/hr
Exhaust flow
1,129 CFM
Exhaust temp
1382 °F
Combustion air
355 CFM
Ventilation air
12,500 CFM

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Blue Star NG150-01P

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Blue Star NG150-01P

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

1,575,000 BTU/hr1575.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Service intervals

Manufacturer-recommended intervals for the Blue Star NG150-01P under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 250 hours or 12 months
Coolant change
Every 4000 hours
Air filter
Every 1000 hours
Spark plugs
Every 1500 hours
Major overhaul
15,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
TurbochargerLoss of power, excessive smoke under load12,000+moderate
Spark plugs / ignitionMisfire at load, rough running1,500+minor
Charge air coolerReduced power output, elevated intake temps10,000+moderate
BatteryFailed to start during outage8,760+minor

Frequently Asked Questions

What is the difference between the NG150-01 and NG150-01P?
The NG150-01 is the standby-rated variant at 150 kWe on natural gas. The NG150-01P is the prime-rated variant of the same physical unit, rated 125 kWe continuous on natural gas (95 kWe on LP). Prime rating allows unlimited hours of operation per year at rated load; standby rating is for infrequent emergency use only. Both units use the identical PSI 8.1LT engine and share the same physical footprint and weight.
What is the prime rating of the NG150-01P on natural gas vs LP?
The NG150-01P is rated 125 kWe prime on natural gas and 95 kWe prime on LP (propane). The LP rating is lower due to LP's different BTU content and combustion characteristics. Both fuels require 11 in. water column inlet pressure at the 1.5-inch NPT connection.
What warranty covers the NG150-01P?
Blue Star covers the NG150-01P with a 1-year / 1,500-hour prime warranty, as specified on the OEM spec sheet. The standby variant (NG150-01) carries a 2-year / 2,000-hour standby warranty.
What controller does the NG150-01P use?
The DSE DCP7310 digital control panel — identical to the standby NG150-01. It provides CAN Bus J1939 ECU communications, 8 programmable inputs, 10 contact outputs, RS485, NFPA 110 Level 1 compatibility, and IP 65 ingress protection.

Compatible equipment

Similar models

Blue Star Power Systems

New

Blue Star NG150-01

150 kW standby · Natural Gas / LPG · Liquid-cooled

150 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 8.1LT turbocharged inline-six, DSE DCP7310 controller, 208-600V output.

EPA Stationary Spark Ignition3-phasecommerciallight-commercial

Blue Star Power Systems

New

Blue Star NG200-01P

200 kW standby · Natural Gas / LPG · Liquid-cooled

175 kW prime-rated natural gas / LP generator from Blue Star Power Systems. PSI 11.1L inline-six, DSE DCP7310 controller, 208-600V, continuous prime duty.

EPA Stationary Spark Ignition3-phasecommercialmedium-commercial

Blue Star Power Systems

New

Blue Star PS150-01

150 kW standby · Natural Gas / LPG · Liquid-cooled

150 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 8.8LTCAC turbocharged-aftercooled V8, DSE DCP7310 controller, single- and three-phase 120-600V.

EPA Stationary Spark Ignition3-phaselarge-commercialschool-campus

Blue Star Power Systems

New

Blue Star PS130-01

130 kW standby · Natural Gas / LPG · Liquid-cooled

130 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 8.8LTCAC turbocharged V8, DSE DCP7310 controller, 208-600V output.

EPA Stationary Spark Ignition3-phasecommerciallight-commercial

Blue Star Power Systems

New

Blue Star GM100-03

100 kW standby · Natural Gas / LPG · Liquid-cooled

100 kW natural gas standby generator (80 kW on LP) from Blue Star Power Systems. PSI 5.7LTCAC turbocharged charge-air-cooled V8, Stamford UCI274C alternator, DSE DCP7310 controller, 208-600V output.

EPA Stationary Spark Ignition3-phasecommercialmedium-commercial

Blue Star Power Systems

New

Blue Star NG200-01

200 kW standby · Natural Gas / LPG · Liquid-cooled

200 kW natural gas / LP standby generator from Blue Star Power Systems. PSI 11.1L turbocharged inline-six, DSE DCP7310 controller, 208-600V output.

EPA Stationary Spark Ignition3-phasecommercialmedium-commercial