Olympian

Olympian GEP110

110 kW standby · Diesel · Liquid-cooled

Olympian GEP110: 110 kW diesel generator powered by the Perkins 1104C-44TAG2 engine. 4.4L inline-4 for commercial standby and light industrial applications.

Standby power
110 kW
Voltage options
277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
Perkins 1104C-44TAG2 · 4.4L

Overview#

The Olympian GEP110 is a 110 kW diesel generator powered by the Perkins 1104C-44TAG2 — a 4.4-liter inline-4 engine representing the top of the Perkins 1100 Series four-cylinder range for generator applications. Delivering three-phase 277/480V power at 60 Hz, the GEP110 serves the upper end of the mid-range commercial standby market: larger office buildings, multi-story retail, hospitality properties, and light industrial facilities.

The 1104C variant of the Perkins 4.4-liter platform features enhanced fuel injection and turbocharging calibration compared to the 1104A used in the smaller GEP65 and GEP88, extracting maximum output from the four-cylinder architecture before the step up to the six-cylinder 1106 engine in the GEP150. This makes the GEP110 the most power-dense four-cylinder option in the Olympian GEP lineup.

At 110 kW, the GEP110 occupies a competitive class alongside the Cummins C100D6, Kohler 100REOZJF, and Generac SD100. The Olympian's value-tier pricing combined with Caterpillar dealer service access makes it attractive for commercial building operators who need 100+ kW backup power without the premium cost of a Cat C-Series unit. The four-cylinder engine also offers a smaller footprint than six-cylinder alternatives in this power class, which can be advantageous on space-constrained commercial sites.

Ready to order this model?

Configure your Olympian GEP110

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Olympian GEP110

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

33.7 hours(1.4 days)

Fuel consumption ≈ 5.94 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Olympian GEP110 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationHard starting, filter clogging, reduced power4,380+moderate
TurbochargerPower loss, excessive smoke under load12,000+moderate
BatteryFailed to start, slow crank8,760+minor

Frequently Asked Questions

Is the GEP110 the most powerful four-cylinder Olympian generator?
Yes. The GEP110 uses the Perkins 1104C-44TAG2, the highest-output variant of the 4.4-liter four-cylinder platform in the Olympian GEP lineup. For more than 110 kW, the step up is to the six-cylinder Perkins 1106 engine in the GEP150.
How does the GEP110 compare to the Cummins C100D6?
The GEP110 delivers 110 kW from a compact four-cylinder Perkins engine with Cat dealer service. The Cummins C100D6 offers 100 kW from the QSB platform with Cummins dealer support. The GEP110 provides slightly more power and Olympian value-tier pricing, while the Cummins benefits from broader QSB fleet commonality.

More in the Olympian GEP Series (Diesel)

Olympian GEP diesel generators — 15–500 kW value-tier units with Perkins engines, backed by the Caterpillar dealer network.

Similar models

Olympian

Olympian GEP150

150 kW standby · Diesel · Liquid-cooled

Olympian GEP150: 150 kW diesel generator powered by the Perkins 1106A-70TAG3 engine. 7.0L inline-6 for commercial standby and industrial applications.

3-phasecommercial-standbyindustrial

Olympian

Olympian GEP220

220 kW standby · Diesel · Liquid-cooled

Olympian GEP220: 220 kW diesel generator powered by the Perkins 1106A-70TAG4 engine. 7.0L inline-6 for commercial standby and industrial applications.

3-phasecommercial-standbyindustrial
Airman Airman EBOSS 125-65 110 kW liquid-cooled standby generator

Airman

Airman EBOSS 125-65

Only integrated diesel-battery hybrid portable generator on the market — LTO batteries, unlimited paralleling, dramatic fuel and emissions reduction.

110 kW standby · Diesel · Liquid-cooled

125 kVA hybrid energy system with 65 kWh LTO battery storage. Diesel-battery hybrid for reduced fuel and emissions.

3-phaseconstructionrental-fleet

Need service or parts for the Olympian GEP110?

We service every major OEM and stock genuine parts for the most common models.