Generac · SD Series (Industrial Diesel)

Generac SD500

500 kW standby / 450 kW prime · Diesel · Liquid-cooled

500 kW diesel standby generator. Perkins 15.2L turbocharged-aftercooled inline-6, EPA Certified Stationary Emergency.

Generac Generac SD500 generator — specifications and details
Standby power
500 kW / 450 kW prime
Voltage options
120/208V, 120/240V, 277/480V, 346/600V
Frequency / Phase
60 Hz · 3-phase
Engine
Perkins 15.2L · 15.2L
Alternator
Generac K0500124Y23

Overview#

The Generac SD500 is a 500-kilowatt diesel standby generator powered by a Perkins 15.2-liter turbocharged and aftercooled inline-six engine. Rated at 500 kW standby and 450 kW prime, it is one of the largest single-engine models in Generac's SD Series industrial diesel lineup, targeting large commercial, industrial, healthcare, and critical facility applications.

The SD500 uses Generac's alternator with Class H insulation and permanent magnet excitation, paired with the Digital H control panel providing NFPA 110 Level I and II programmability, Modbus protocol, and a predictive maintenance algorithm. At 500 kW, this unit competes with the Caterpillar C18, Cummins C500D6, and Kohler 500REOZK.

The Perkins 15.2L platform#

The SD500 steps up from the 12.5L engine in the SD400 to the Perkins 15.2-liter platform, gaining nearly 3 liters of displacement. With a bore of 137 mm (5.39 in), stroke of 171 mm (6.73 in), and 16.0:1 compression ratio, the engine produces 755 horsepower at rated kW. Piston speed is 2,020 ft/min with BMEP of 358 psi -- these are higher mechanical loads than the smaller SD models, reflecting the engine running closer to its limits at the 500 kW standby rating.

The jump in physical size is substantial: the open-set genset grows from 137.5 x 57.6 inches on the SD400 to 154.4 x 71.0 inches, and dry weight nearly doubles from 6,649 lbs to 10,435 lbs. This size increase must be factored into equipment room planning and rigging.

Ventilation and exhaust considerations#

The SD500 demands 30,582 CFM of radiator cooling air -- more than 60% higher than the SD400's 18,685 CFM. Combustion air at 1,483 CFM and exhaust flow at 3,955 CFM are also significantly higher. Maximum exhaust backpressure tolerance is 2.01 inHg, which is tighter than the 1.5 inHg on smaller models. Proper silencer selection and exhaust routing are critical to stay within this limit.

Our service experience#

The 500 kW class serves large hospitals, data centers, and campus environments in Northern California. The SD500's Perkins 15.2L engine is a proven industrial platform. At 32 gph full load, fuel logistics require attention -- ensure adequate fuel storage and delivery capacity for extended outage scenarios. The 24 VDC battery system uses dual Group 8D batteries; we recommend equalized charging and testing both batteries individually at each service visit. The 48-quart oil capacity means oil changes are more involved than on smaller models -- verify proper disposal logistics during service planning.

Engineering specifications

Physical

Length
154.4 in
Width
71 in
Height
67.3 in
Dry weight
10,435 lb

Fuel system & runtime

Fuel use @ full load
32 GPH
Fuel use @ 75% load
24.2 GPH
Fuel use @ 50% load
17.5 GPH

Thermal & ventilation

Heat to coolant
648,307 BTU/hr
Exhaust flow
3,955 CFM
Exhaust temp
1022 °F
Combustion air
1,483 CFM
Ventilation air
30,582 CFM

Documents & downloads

Spec sheets & manuals

Ready to order this model?

Configure your Generac SD500

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Generac SD500

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

8.1 hours(0.3 days)

Fuel consumption ≈ 24.69 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Generac SD500 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
Fuel quality / degradationHard starting, filter clogging, reduced power output4,380+moderate
TurbochargerPower loss, excessive smoke, elevated exhaust temperatures15,000+moderate
Coolant systemOverheating, coolant leaks, water pump bearing wear12,000+moderate
Starter motorSlow cranking, failure to engage (24 VDC system)15,000+moderate
Battery bankFailed to start, low voltage alarm (dual 12V batteries in series)8,760+minor

Frequently Asked Questions

What engine does the Generac SD500 use?
The Generac SD500 uses a Perkins 15.2-liter, six-cylinder in-line turbocharged and aftercooled diesel engine running at 1800 RPM. The engine has a bore of 5.39 in (137 mm) and stroke of 6.73 in (171 mm) with a 16.0:1 compression ratio. It uses a 24 VDC electrical system with dual 12V batteries. The crankcase holds 47.55 qt (45L) of oil. The engine is EPA Certified for Stationary Emergency applications.
What is the fuel consumption of the Generac SD500?
At standby rating, the SD500 consumes 32.0 gallons per hour at full load (100%), 24.2 gph at 75% load, 17.5 gph at 50% load, and 11.2 gph at 25% load. Total fuel pump flow (combustion plus return) is 121 gph. The fuel pump lift is rated at 12 feet.
What are the dimensions and weight of the SD500?
The open-set SD500 (no base tank) measures 154.4 x 71.0 x 67.3 inches and weighs approximately 10,435 lbs. This is a significantly larger footprint than the SD400 (137.5 x 57.6 in) due to the Perkins 15.2L engine platform. Sub-base fuel tank and extended runtime options are available, with weather-protected and sound-attenuated enclosures in steel or aluminum.
What is the ventilation requirement for an indoor SD500 installation?
The SD500 requires 30,582 CFM of radiator cooling airflow and 1,483 CFM of combustion air. Heat rejection to coolant is 648,307 BTU/hr. Exhaust exits at 1,022 degrees F at 3,955 CFM. Maximum exhaust backpressure is 2.01 inHg. These substantial thermal and airflow requirements demand careful mechanical room engineering.

Compatible equipment

More in the SD Series (Industrial Diesel)

Generac's broadest diesel standby lineup — 10 to 1500 kW across four engine families for commercial and industrial applications.

Similar models

Generac Generac SD400 400 kW liquid-cooled standby generator

Generac

Generac SD400

400 kW industrial diesel at competitive pricing. Proven engine platform with 10,000+ dealer support network.

400 kW standby · Diesel · Liquid-cooled

400 kW diesel standby generator. 12.5L turbocharged-aftercooled inline-6, EPA Certified Stationary Emergency.

3-phasecommercial-standbyindustrial
Generac Generac SD600 600 kW liquid-cooled standby generator

Generac

Generac SD600

600 kW industrial diesel with Perkins engine. 10-15% below Kohler equivalent. Paralleling-ready for multi-unit systems.

600 kW standby · Diesel · Liquid-cooled

600 kW standby diesel generator with Perkins 18.1L inline-6 engine. EPA certified stationary emergency. Three-phase 120/208V to 346/600V. UL2200 listed.

3-phasecommercial-standbyindustrial-standby
Generac Generac SG500 500 kW liquid-cooled standby generator

Generac

Generac SG500

500 kW natural gas industrial standby. No diesel permitting needed. Paralleling for multi-MW gas-powered backup.

500 kW standby · Natural Gas · Liquid-cooled

500 kW standby natural gas generator with Generac 25.8L V12 turbocharged/aftercooled spark-ignited engine. EPA certified stationary emergency and non-emergency. Demand response ready.

3-phasecommercial-standbyindustrial-standby

Need service or parts for the Generac SD500?