Blue Star Power Systems · Mobile Product Line (Volvo Penta)

New

Blue Star VD600-04FT4MP

600 kW standby / 570 kW prime · Diesel · Liquid-cooled

600 kW standby / 570 kW prime Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TWD1683GE six-cylinder engine, 572RSL6431 alternator, DSE DCP7310 controller, 550-gallon integrated fuel tank.

Standby power
600 kW / 570 kW prime
Voltage options
120/208V, 277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
Volvo Penta TWD1683GE · 16.12L
EPA / Emissions
Tier 4 Final
Alternator
Leroy-Somer 572RSL6431
constructiontemporary-powerindustrialmunicipalhealthcaredata-centerpump-station

Overview#

The Blue Star VD600-04FT4MP is a 600-kilowatt standby / 570-kilowatt prime EPA Tier 4 Final / EU Stage 5 mobile trailer diesel generator powered by the Volvo Penta TWD1683GE — a 16.12-liter, six-cylinder turbocharged and charge-air-cooled engine. It is the largest model in Blue Star's Tier 4 Final mobile lineup, sharing the 334.5 × 99.5 in trailer platform with the VD550-04FT4MP but producing 600/570 kWe from the higher-calibration TWD1683GE.

Blue Star Power Systems mounts the TWD1683GE on an aluminum road trailer with a 550-gallon integral fuel tank and 52.8-gallon DEF tank, paired with a Leroy-Somer 572RSL6431 alternator and DSE DCP7310 controller. At 25,000 lbs, the VD600-04FT4MP is the heaviest unit in the Blue Star Tier 4 Final mobile product line. Three-phase only; no 600V configuration — the mobile lineup is 208V–480V.

TWD1682 vs TWD1683: Same Block, Higher Calibration#

The VD550 (TWD1682GE) and VD600 (TWD1683GE) share the same 16.12-liter Volvo Penta TWD block and physical trailer. The numerical calibration increment (1682 → 1683) reflects a higher fuel delivery and boost mapping to reach 600/570 kWe vs 550/500 kWe. From a service and logistics standpoint, the two models are nearly identical in deployment requirements. The choice between them is driven entirely by load requirement.

Prime Power Ratings at This Output Class#

The VD600-04FT4MP standby rating is 600 kWe; the prime rating is 570 kWe — a 30 kWe spread that is narrower than the 50 kWe spread on the VD550. For prime power applications (continuous variable load, unlimited hours), size to 570 kWe. The 600 kWe rating applies only to emergency standby use. Verify the application rating with the site's power engineer before finalizing the specification.

When to specify the VD600-04FT4MP#

Our service experience#

The VD600-04FT4MP is the most demanding model in Blue Star's T4F mobile lineup. The TWD1683GE at 600 kWe standby / 570 kWe prime requires the full Volvo Penta TWD preventive maintenance schedule including aftertreatment system management. At 39.6 gph diesel and the associated DEF consumption rate, fuel and DEF logistics dominate operational planning on long deployments. The 334.5 in trailer length and 25,000 lb weight require permits and specialized towing in most jurisdictions. Site entry dimensions must be confirmed: the 99.5 in width exceeds standard lane width in some site configurations. Annual full-load testing at 39.6 gph is mandatory. Exhaust at 862°F and 3,991 CFM requires properly rated exhaust connections and transition hardware.

Engineering specifications

Physical

Length
334.5 in
Width
99.5 in
Height
144 in
Dry weight
25,000 lb

Acoustic

Sound @ 7m, full load
76 dBA
Enclosure
Open

Fuel system & runtime

Integral fuel tank
550 gal
Fuel use @ full load
39.6 GPH
Fuel use @ 75% load
29.9 GPH
Fuel use @ 50% load
21.6 GPH
DEF tank
52.8 gal

Thermal & ventilation

Heat to coolant
743,820 BTU/hr
Heat radiated
716,880 BTU/hr
Exhaust flow
3,991 CFM
Exhaust temp
862 °F
Combustion air
1,801 CFM
Ventilation air
26,926 CFM

Documents & downloads

Spec sheets & manuals

Request a quote

Get pricing & lead time on the Blue Star VD600-04FT4MP

Tell us about the application — kW, voltage, application, install timeline — and we'll respond within one business day with budgetary pricing, lead time, and any sizing notes.

Estimate runtime for the Blue Star VD600-04FT4MP

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Estimated runtime

18.0 hours(0.8 days)

Fuel consumption ≈ 30.55 GPH at 75% load. Estimate based on industry-typical 1800 RPM standby curves (≈0.07 GPH/kW at full load). Actual consumption varies by engine, ambient temperature, fuel quality, and tuning.

Service intervals

Manufacturer-recommended intervals for the Blue Star VD600-04FT4MP under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.

Oil & filter
Every 500 hours or 12 months
Coolant change
Every 6000 hours
Air filter
Every 1000 hours
Fuel filter
Every 500 hours
Major overhaul
20,000 hours
Load bank test
Every 12 months

Common failure modes

What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.

ComponentSymptomTypical hoursSeverity
DEF system (SCR catalyst)Derate warning, NOx fault, DEF quality alert4,380+moderate
Turbocharger(s)Major power loss, heavy exhaust smoke12,000+severe
Fuel quality / degradationInjector fouling, hard starting4,380+moderate
Battery bank (24V)Failed start, slow cranking8,760+minor

Frequently Asked Questions

What engine does the VD600-04FT4MP use?
The Volvo Penta TWD1683GE — a 16.12-liter, six-cylinder turbocharged and charge-air-cooled diesel. The TWD1683GE is the higher-output calibration of the same 16.12-liter TWD block used in the VD550-04FT4MP (TWD1682GE). Both engines share the same displacement, cylinder count, and architecture; the 1683 calibration produces 600 kWe standby and 570 kWe prime through higher fuel delivery and boost mapping. EPA Tier 4 Final and EU Stage 5 dual certification applies. The 52.8-gallon DEF tank is shared with the VD550. Rated power is available to 4,921 ft (1,500 m) at 122°F (50°C).
What controller does the VD600-04FT4MP use?
The DSE DCP7310 Digital Control Panel, with CAN Bus J1939 engine communication, digital metering, RS-485 interface, 8 programmable contact inputs, 10 contact outputs, and NFPA 110 Level 1 compatibility. The panel is cULus Listed and CE Approved with IP 65 ingress protection (with supplied gasket). A 24V battery system and battery charger are included. The 572RSL6431 alternator is the higher-output variant of the 572RSL series, stepping up from the 6429 winding used in the VD550.
How does the VD600-04FT4MP compare to the VD550-04FT4MP on the same trailer platform?
The VD550 (TWD1682GE, 550/500 kWe, 24,750 lbs, 38.3 gph, 572RSL6429) and VD600 (TWD1683GE, 600/570 kWe, 25,000 lbs, 39.6 gph, 572RSL6431) share identical 334.5 × 99.5 × 144 in trailer dimensions and the same 550-gallon fuel / 52.8-gallon DEF tanks. The difference is 250 lbs, 1.3 gph at full load, and 50 kWe standby / 70 kWe prime additional output. The VD600 prime rating of 570 kWe is a tighter margin below standby (30 kWe spread vs 50 kWe on the VD550). The two models are effectively the same deployment package at different output ceilings.
What are the fuel and DEF logistics for the VD600-04FT4MP?
The 550-gallon integral fuel tank at full standby load (39.6 gph) provides approximately 13.9 hours of runtime. At 75% load (29.9 gph), runtime extends to approximately 18.4 hours. The 52.8-gallon DEF tank typically supports 12–16 hours at full load. For 24-hour continuous deployments, one full refueling cycle and approximately one DEF refill are required. Combustion air draw is 1,801 CFM; ventilation requirement is 26,926 CFM; heat rejected to coolant is 743,820 BTU/hr; radiated heat is 716,880 BTU/hr; exhaust exits at 862°F at 3,991 CFM.

Compatible equipment

Similar models

Blue Star Power Systems

New

Blue Star VD550-04FT4MP

550 kW standby · Diesel · Liquid-cooled

550 kW standby / 500 kW prime Tier 4 Final / EU Stage 5 mobile trailer diesel generator built by Blue Star Power Systems. Volvo Penta TWD1682GE six-cylinder engine, 572RSL6429 alternator, DSE DCP7310 controller, 550-gallon integrated fuel tank.

Tier 4 Final3-phaseconstructiontemporary-power

Blue Star Power Systems

New

Blue Star PD600-01

600 kW standby · Diesel · Liquid-cooled

600 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Perkins 2806C-E18TAG3 six-cylinder engine with charge air cooling, Stamford HCI534E alternator, DSE DCP7310 controller.

Tier 23-phasecommercialindustrial

Blue Star Power Systems

New

Blue Star VD600-01

600 kW standby · Diesel · Liquid-cooled

600 kW EPA Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TWD1643GE 16.1L inline-six, 208-4160V output, available with medium-voltage option.

Tier 23-phaselarge-commercialhospital

Blue Star Power Systems

New

Blue Star VD600-03

600 kW standby · Diesel · Liquid-cooled

600 kW Tier 2 diesel standby generator from Blue Star Power Systems. Volvo Penta TWD1644GE 16.1L inline-six with dual-stage turbo, DSE DCP7310 controller, 208-600V.

Tier 23-phasecommerciallarge-commercial

Blue Star Power Systems

New

Blue Star VD600-04FT4

600 kW standby · Diesel · Liquid-cooled

600 kW standby / 570 kW prime Tier 4 Final diesel generator from Blue Star Power Systems. Volvo Penta TWD1683GE 16.12L inline-six with SCR/DPF/DOC, DSE DCP7310 controller, three-phase 208-600V.

Tier 4 Final3-phaselarge-commercialhospital-non-critical

Blue Star Power Systems

New

Blue Star PD550-01

550 kW standby · Diesel · Liquid-cooled

550 kW Tier 2 diesel standby generator built by Blue Star Power Systems. Perkins 2506C-E15TAG4 six-cylinder engine with charge air cooling, Stamford HCI534E alternator, DSE DCP7310 controller.

Tier 23-phasecommercialindustrial

Need service or parts for the Blue Star VD600-04FT4MP?

We service every major OEM and stock genuine parts for the most common models.