Triton Power · TP-NG

Triton Power TP-NG40-S-K-UL

40 kW standby / 34 kW prime · Natural Gas · Liquid-cooled

40 kW natural gas generator with PSI 4.3L engine. UL2200 listed for commercial and industrial standby applications.

Standby power
40 kW / 34 kW prime
Voltage options
120/208V, 120/240V, 277/480V
Frequency / Phase
60 Hz · 1/3-phase
Engine
PSI 4.3L · 4.3L
EPA / Emissions
EPA Stationary Spark Ignition
Alternator
Leroy Somer LSA42.3

Overview#

The Triton Power TP-NG40-S-K-UL is a 40 kW natural gas standby generator powered by a PSI (Power Solutions International) 4.3L naturally aspirated V-6 engine at 1800 RPM. Part of Triton's EPA-certified natural gas generator lineup, this unit is UL2200 listed for the US and Canadian markets and pairs with a Leroy Somer Class H insulation alternator. The TP-NG40 delivers 40 kW standby and 34 kW prime power, making it suitable for small to mid-size commercial and light industrial standby applications.

The PSI 4.3L engine platform is designed from the ground up for gaseous fuel operation, offering reliable combustion characteristics and low maintenance requirements compared to converted diesel engines. Available in single-phase and three-phase configurations, the TP-NG40 supports 120/208V, 120/240V, and 277/480V output. Sound levels are rated at 64 dBA, allowing installation in noise-sensitive commercial environments.

Our service experience#

The 40 kW rating fills a common sizing need for small commercial buildings, restaurants, and retail locations with moderate electrical loads. The PSI 4.3L shares its platform with the TP-NG35, so parts commonality is high between the two models. Natural gas units in this range are straightforward to maintain, with no diesel fuel filtration or injector service required.

Engineering specifications

Acoustic

Sound @ 7m, full load
64 dBA

Ready to order this model?

Configure your Triton Power TP-NG40-S-K-UL

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Triton Power TP-NG40-S-K-UL

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

420,000 BTU/hr420.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Frequently Asked Questions

What engine does the Triton TP-NG40-S-K-UL use?
The TP-NG40-S-K-UL is powered by a PSI (Power Solutions International) 4.3L naturally aspirated V-6 engine designed specifically for natural gas fuel. PSI engines are purpose-built for gaseous fuel applications, providing clean combustion, long service life, and compliance with EPA Stationary Spark Ignition emissions standards.
What natural gas supply pressure is needed for the TP-NG40?
Natural gas generators in this class typically require a minimum gas supply pressure of 5-7 inches of water column (WC) at the gas train inlet. The gas line must be sized to deliver adequate volume at the required pressure under full load conditions. A licensed plumber should verify supply capacity before installation.
Is the TP-NG40 available in single-phase?
Yes. The TP-NG40-S-K-UL is available in both single-phase (120/240V) and three-phase (120/208V, 277/480V) configurations. The single-phase option is suitable for smaller commercial facilities, while three-phase is standard for industrial and larger commercial installations.

Why we recommend Triton Power

Triton Power is our value brand for mobile and portable diesel generators, and an emerging option for industrial standby. When MQ Power's pricing is a stretch or lead times are too long, Triton delivers comparable capability at a lower price point with faster availability.

We are developing our Triton Power sales relationship and building fleet experience. Every engine platform Triton uses — Perkins, John Deere, Kubota, Scania, Volvo — is one we already service daily across other brands. Triton's open architecture means our technicians can maintain these units with standard tooling and widely available parts.

See all Triton Powergenerators →

Similar models

Triton Power

Triton Power TP-NG35-UL

35 kW standby · Natural Gas · Liquid-cooled

35 kW natural gas generator with PSI 4.3L engine. UL2200 listed for commercial and industrial standby applications.

EPA Stationary Spark Ignition3-phasecommercial-standbyindustrial

Triton Power

Triton Power TP-NG100-S-K-UL

100 kW standby · Natural Gas · Liquid-cooled

100 kW natural gas generator with PSI 5.7LT CAC engine. UL2200 listed for commercial and industrial standby applications.

EPA Stationary Spark Ignition3-phasecommercial-standbyindustrial
Triton Power Triton Power TP-K30-T4i-UL 30 kW liquid-cooled standby generator

Triton Power

Triton Power TP-K30-T4i-UL

30 kW standby · Diesel · Liquid-cooled

30 kW diesel generator with Kubota V3300-E3BG-CHN-1 engine. UL2200-listed for commercial standby and light industrial applications.

3-phasecommercial-standbysmall-business

Need service or parts for the Triton Power TP-NG40-S-K-UL?

We service every major OEM and stock genuine parts for the most common models.