Triton Power · TP-NG

Triton Power TP-NG400-S-K-UL

400 kW standby / 360 kW prime · Natural Gas · Liquid-cooled

400 kW natural gas generator with PSI 20L engine. UL2200 listed for commercial and industrial standby applications.

Standby power
400 kW / 360 kW prime
Voltage options
120/208V, 277/480V
Frequency / Phase
60 Hz · 3-phase
Engine
PSI 20L · 20L
EPA / Emissions
EPA Stationary Spark Ignition
Alternator
Leroy Somer LSA46.3

Overview#

The Triton Power TP-NG400-S-K-UL is a 400 kW natural gas standby generator powered by a PSI (Power Solutions International) 20L turbocharged V-16 engine running at 1800 RPM. This unit is part of Triton's EPA-certified natural gas generator lineup, UL2200 listed for the US and Canadian markets. The Leroy Somer Class H insulation alternator delivers 400 kW standby and 360 kW prime power in three-phase configuration at 120/208V and 277/480V.

The PSI 20L V-16 marks the transition from inline-6 engines to V-configuration powerplants in Triton's natural gas range. The 16-cylinder layout distributes combustion loads across more cylinders, reducing per-cylinder stress and providing smooth power delivery. The unit meets EPA Stationary Spark Ignition emissions standards and maintains 64 dBA sound output. At 400 kW, this generator serves large commercial buildings, industrial facilities, and campus-level backup power applications.

Our service experience#

The V-16 configuration introduces additional ignition system components compared to the inline-6 models lower in the range, but the PSI platform maintains good serviceability with accessible spark plugs and individual coil-on-plug ignition. At 400 kW, gas supply requirements are substantial, and we recommend a thorough gas utility survey before committing to installation. The larger displacement provides comfortable operating margins at rated load.

Engineering specifications

Acoustic

Sound @ 7m, full load
64 dBA

Ready to order this model?

Configure your Triton Power TP-NG400-S-K-UL

Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.

Estimate runtime for the Triton Power TP-NG400-S-K-UL

Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.

Estimate runtime on this tank

Fuel demand at 75% load

4,200,000 BTU/hr4200.0 cf/min @ 1,000 BTU/cf

On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.

Frequently Asked Questions

What engine configuration does the TP-NG400 use?
The TP-NG400-S-K-UL is powered by a PSI 20L turbocharged V-16 engine. The V-16 configuration provides the displacement and cylinder count needed for 400 kW standby output while maintaining smooth operation. This marks the transition from inline-6 to V-configuration engines in Triton's natural gas lineup.
How does the TP-NG400 compare to the diesel TP-P400-T3-UL?
Both units deliver 400 kW standby power. The TP-NG400 runs on pipeline natural gas and meets EPA Stationary Spark Ignition standards, while the TP-P400-T3-UL uses a Perkins diesel engine with Tier 3 emissions certification. The natural gas unit eliminates diesel fuel storage requirements and reduces particulate emissions. The diesel model offers fuel independence for sites without natural gas service.
What are the ventilation requirements for a 400 kW natural gas generator?
A 400 kW natural gas generator produces significant heat that must be managed through proper ventilation. Indoor installations require combustion air supply, radiator exhaust ducting, and room ventilation to maintain ambient temperature below engine manufacturer limits. Gas detection equipment is also recommended for indoor natural gas generator installations per NFPA 37 and local building codes.

Why we recommend Triton Power

Triton Power is our value brand for mobile and portable diesel generators, and an emerging option for industrial standby. When MQ Power's pricing is a stretch or lead times are too long, Triton delivers comparable capability at a lower price point with faster availability.

We are developing our Triton Power sales relationship and building fleet experience. Every engine platform Triton uses — Perkins, John Deere, Kubota, Scania, Volvo — is one we already service daily across other brands. Triton's open architecture means our technicians can maintain these units with standard tooling and widely available parts.

See all Triton Powergenerators →

Similar models

Triton Power

Triton Power TP-NG350-S-K-UL

350 kW standby · Natural Gas · Liquid-cooled

350 kW natural gas generator with PSI 14.6L HO engine. UL2200 listed for commercial and industrial standby applications.

EPA Stationary Spark Ignition3-phasecommercial-standbyindustrial

Triton Power

Triton Power TP-NG450-UL

450 kW standby · Natural Gas · Liquid-cooled

450 kW natural gas generator with PSI 21.9L engine. UL2200 listed for commercial and industrial standby applications.

EPA Stationary Spark Ignition3-phasecommercial-standbyindustrial
Triton Power Triton Power TP-P400-T3-UL 400 kW liquid-cooled standby generator

Triton Power

Triton Power TP-P400-T3-UL

400 kW standby · Diesel · Liquid-cooled

400 kW Tier 3 diesel generator with Perkins 2206D-E13TAG3 engine. UL2200-listed for commercial, healthcare, and data center standby.

Tier 33-phasecommercial-standbyhealthcare

Need service or parts for the Triton Power TP-NG400-S-K-UL?

We service every major OEM and stock genuine parts for the most common models.

Last reviewed: